Plan Review Notes
Plan Review Notes For Permit 07050509
Permit Number 07050509
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-09 15:57:09*****DENIED*****
  
  
 01.PLEASE BE ADVISED THAT THE ZIP CODE FOR THIS
 PROJECT LOCATION IS 33401, NOT 33409 AS INDICATED ON
 SOME OF YOUR SUBMITTALS.
  
 02.APPLICABLE FIRE/LIFE SAFETY CODE IS THAT OF
 FLORIDA FIRE PREVENTION CODE 2004 EDITION AND NFPA 101,
 THE LIFE SAFETY CODE, 2003 EDITION.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.ALTHOUGH THERE WILL BE ONE TENANT ON THE 20TH
 FLOOR, A SUITE NUMBER SHALL BE REQUIRED AND INCLUDED IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 05.ON SHEET E-1, INDICATE THE SYMBOL/LEGEND FOR THE
 FIRE ALARM DEVICES.
  
 06.THE SUBMITTED FIRE ALARM PLANS REQUIRE SEPARATE
 PERMIT AND CAN BE SUBMITTED ONCE THE MASTER PERMIT HAS
 BEEN ISSUED.
  
 07.NFPA 72 (2002 EDITION) SHALL BE REFERENCED.SEE
 SHEET E-3
  
 08.SYSTEM OF OPERATION FOR DUCT SMOKE DETECTORS SHALL
 INTIATE A GENERAL FIRE ALARM AS PER WEST PALM BEACH
 FIRE PREVENTION BUREAU.SEE SHEET E-3
  
 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SPRINKLER REMODEL.
  
 10.PROVIDE A LIFE SAFETY PLAN INDICATING THE TRAVEL
 DISTANCE TO THE EXIT(S) AND ALSO THE LOCATION OF THE
 FIRE EXTINGUISHERS TO SATISFY THE 75' TRAVEL DISTANCE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW