| 2007-07-09 15:57:09 | *****DENIED***** |
| | |
| | |
| | 01.PLEASE BE ADVISED THAT THE ZIP CODE FOR THIS |
| | PROJECT LOCATION IS 33401, NOT 33409 AS INDICATED ON |
| | SOME OF YOUR SUBMITTALS. |
| | |
| | 02.APPLICABLE FIRE/LIFE SAFETY CODE IS THAT OF |
| | FLORIDA FIRE PREVENTION CODE 2004 EDITION AND NFPA 101, |
| | THE LIFE SAFETY CODE, 2003 EDITION. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.ALTHOUGH THERE WILL BE ONE TENANT ON THE 20TH |
| | FLOOR, A SUITE NUMBER SHALL BE REQUIRED AND INCLUDED IN |
| | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 05.ON SHEET E-1, INDICATE THE SYMBOL/LEGEND FOR THE |
| | FIRE ALARM DEVICES. |
| | |
| | 06.THE SUBMITTED FIRE ALARM PLANS REQUIRE SEPARATE |
| | PERMIT AND CAN BE SUBMITTED ONCE THE MASTER PERMIT HAS |
| | BEEN ISSUED. |
| | |
| | 07.NFPA 72 (2002 EDITION) SHALL BE REFERENCED.SEE |
| | SHEET E-3 |
| | |
| | 08.SYSTEM OF OPERATION FOR DUCT SMOKE DETECTORS SHALL |
| | INTIATE A GENERAL FIRE ALARM AS PER WEST PALM BEACH |
| | FIRE PREVENTION BUREAU.SEE SHEET E-3 |
| | |
| | 09.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE SPRINKLER REMODEL. |
| | |
| | 10.PROVIDE A LIFE SAFETY PLAN INDICATING THE TRAVEL |
| | DISTANCE TO THE EXIT(S) AND ALSO THE LOCATION OF THE |
| | FIRE EXTINGUISHERS TO SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |