Plan Review Notes
Plan Review Notes For Permit 07050509
Permit Number 07050509
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-09 20:19:30** UNSAT **
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS ON PLANS
 WHICH WERE NOT SUBMITTED IN THE DESIGN FOR REVIEW, A
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
 PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE
 RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE THE FIRE ALARM PLANS SUBMITTED IN
 PACKAGE MAY BEUSED FOR REFERENCE HOWEVER THE FA PLANS
 WILL BE REQUIRED UNDER A SEPARATE PERMIT. BASE PLANS
 STILL REQUIRE BASE DESIGN FOR CODE COMPLIANCE. SEE
 ELECTRICAL REVIEW NOTES ALONG WITH ANY POSSIBLE NOTES
 FROM THE FIRE MARSHAL.
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE MEP PLANS
 ARE MISSING THE REQUIRED INFORMATION PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023. THESE ARE MISSING THE PRINTED NAME AND LICENSE
 NUMBER OF THE DESIGNER ON SOME TITLE BLOCKS AS WELL AS
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER ON ALL
 SHEETS.
 ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST,
 2005 WHICH REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.
 PLEASE INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER
 CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.1.AB.1.1, 13-415.2 FOR THE ENERGY
 CALCULATIONS AS SUBMITTED.
 PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS
 *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED
 CONTROLS IS REQUIRED.
 PLEASE SEE THE FIXTURE SCHEDULE MUST BE COMPLETED FOR
 REVIEW FOR ALL TYPES OF FIXTURES. (CAN ALWAYS BE
 REVISED)
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE
 SEE THE PLANS NEED TO HAVE ALL FIXTURES LABELED AND
 CORRELATE WITH FIXTURE SCHEDULE AND ENERGY
 CALCULATIONS.
 PLEASE KNOW AS THIS IS NOT DONE AT THIS TIME AND ONLY
 SOME FIXTURES INDICATE IDENTIFICATION, REVIEW OF
 COORDINATION CAN NOT BE DONE.
 PLEASE SEE THE SQ FT ON PLANS DOES NOT CORRELATE WITH
 THE SUBMITTED ENERGY CALCULATIONS.
  
 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY
 BASED ON THE COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 6) NOTE: PLEASE STATE THE MINIMUM LEVELS FOR ADA
 COMPLIANCE ON THE ELECTRICAL PLANS FOR THE BASE FA
 SYSTEM. PLEASE SEE FBC 11-4.28.1, .2 AND .3(4).
  
 7) NOTE: PLEASE CLARIFY RISER AS THE *DARKENED* ITEMS
 ARE TYPICALLY NEW AND SOME ARE NOTED AS NEW YET THE
 PANEL SCHEDULE FOR ETH AND HV MENTIONS THESE ARE
 EXISTING?
 SOME OF THE OTHER EXISITNG ITEMS ARE VERY LIGHT WHICH
 INDICATE EXISTING.
 PLEASE CLARIFYA LITTLE MORE FOR WHAT IS NEW AND WHAT
 IS EXISTING?
 FBC 106.1.2
  
 8) NOTE: PLEASE PROVIDE MORE INFORMATION AND
 COORDINATION OF ETL AS SHOWN AND NOTED ON RISER. PLEASE
 INDICATE IF THIS PANEL CONTAINS A MAIN CIRCUIT BREAKER.
 IF NOT ONE WILL BE REQUIRED PER 240.21, 408.36.
 PLEASE SEE RISER MENTIONS THIS PANEL/SERVICE AS
 300AMPS, YET THE NOTE ON THE SAME RISER INDICATES THIS
 PANEL AS 400AMPS?
 PLEASE VERIFY AND CLARIFY THE NOTE WHICH MENTIONS THIS
 PANEL AS 43 SPACES? THIS IS NOT COMMON AND NOT
 PERMITTED PER 408.35
  
 9) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE FIXTURES WITH SOME NUMERICAL DESIGNATION,
 HOWEVER DOES INDICATE PANEL OR LOCATION OF
 TERMINATION?
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED.
 PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS
 MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL
 WITH NAME(S).
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4.
  
 *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.*
  
 (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR
 WORDS/IDENTIFICATION TO THAT AFFECT.
 PLEASE ALSO SEE THE HANDBOOK WHICH CONTAINS A MORE
 EXTENSIVE COMMENTARY FOR THIS SAME SECTION.
  
 10) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOADS ARE
 TO FIGURED AND SHOWN AT 125%.
  
 11) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW
 LOADS WERE DERIVED FOR LIGHTING, TRACK LIGHTING,
 RECEPTACLES AND ALL EQUIPMENT.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE
 INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE
 NEC 220, 215.3, 230.42 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ACCESS
 CONTROL LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE
 SAFETY CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION
 OF THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE
 NFPA-101 7.2.1.5, 7.2.1.6.2
  
 13) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE
 REQUIRED TO BE UNDER A SEPARATE PERMIT. THE BASE PLANS
 MAY BE REFERENCE WHEN PERMIT(S) ARE APPLIED AND THESE
 WILL BE TURN AROUND PERMITS AS LONG AS THE LV APPLIED
 FOR IS ON BASE PLANS.
  
 14) NOTE: PLEASE SEE PLANS SHOW A SERVER ROOM, HOWEVER
 ALSO SEEM TO INDICATE A SEPARATE AHU FOR THIS ROOM.
 THIS ROOM APPEARS IT MAY BE AN IT ROOM? PLEASE SEE
 NFPA-70 645 FOR REQUIRED DISCONNECTING MEANS FOR
 ELECTRICAL, SIZING OF CIRCUITS ETC.
 PLEASE SEE NFPA-75 AS THE WALLS ARE REQUIRED TO BE 1HR
 FIRE RATED AND ARCHITECTURAL SHEETS DO NOT INDICATE
 THESE WALLS AS RATED.
 PLEASE CLARIFY IF THERE IS GOING TO BE ANY UPS BACK UP
 SYSTEMS INSTALLED.
 ** PLEASE PROVIDE MORE INFORMATION.
  
 15) NOTE: PLEASE KNOW AS APPLIED THERE IS NOT
 SUITE/UNIT NUMBER INDICATED AND THIS PROJECT WILL
 REQUIRE ADDRESSING REVIEW. PLEASE BE SURE TO INDICATE
 ANY SUITE/UNIT NUMBER ON PLANS(TITLE BLOCK) WHEN
 ASSESSED.
 FAC 61G1-16.004
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT ELECTRICAL PLANS OR DESIGN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]