| Date |
Text |
| 2007-06-09 20:19:30 | ** UNSAT ** |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS ON PLANS |
| | WHICH WERE NOT SUBMITTED IN THE DESIGN FOR REVIEW, A |
| | COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE |
| | RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE |
| | CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS |
| | OF DECEMBER 8TH, 2006. |
| | PLEASE LIST THE FOLLOWING. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC) 2002 SHOWN. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | THIS IS REQUIRED AT A MINIMUM ON ARCHITECTURAL AND |
| | ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE FIRE ALARM PLANS SUBMITTED IN |
| | PACKAGE MAY BEUSED FOR REFERENCE HOWEVER THE FA PLANS |
| | WILL BE REQUIRED UNDER A SEPARATE PERMIT. BASE PLANS |
| | STILL REQUIRE BASE DESIGN FOR CODE COMPLIANCE. SEE |
| | ELECTRICAL REVIEW NOTES ALONG WITH ANY POSSIBLE NOTES |
| | FROM THE FIRE MARSHAL. |
| | |
| | 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE MEP PLANS |
| | ARE MISSING THE REQUIRED INFORMATION PER FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES |
| | 471.023. THESE ARE MISSING THE PRINTED NAME AND LICENSE |
| | NUMBER OF THE DESIGNER ON SOME TITLE BLOCKS AS WELL AS |
| | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER ON ALL |
| | SHEETS. |
| | ** THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND |
| | CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, |
| | 2005 WHICH REQUIRED LIGHTING CONTROLS. |
| | A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE |
| | WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED |
| | LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF |
| | ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN |
| | BE DONE. |
| | PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE |
| | INDICATE SCHEDULING. |
| | PLEASE INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER |
| | CODE. |
| | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. ( |
| | TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE 13-415.1.AB.1.1, 13-415.2 FOR THE ENERGY |
| | CALCULATIONS AS SUBMITTED. |
| | PLEASE SEE THE METHOD OF CONTROL IS BEING SHOWN AS |
| | *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED |
| | CONTROLS IS REQUIRED. |
| | PLEASE SEE THE FIXTURE SCHEDULE MUST BE COMPLETED FOR |
| | REVIEW FOR ALL TYPES OF FIXTURES. (CAN ALWAYS BE |
| | REVISED) |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING. PLEASE |
| | SEE THE PLANS NEED TO HAVE ALL FIXTURES LABELED AND |
| | CORRELATE WITH FIXTURE SCHEDULE AND ENERGY |
| | CALCULATIONS. |
| | PLEASE KNOW AS THIS IS NOT DONE AT THIS TIME AND ONLY |
| | SOME FIXTURES INDICATE IDENTIFICATION, REVIEW OF |
| | COORDINATION CAN NOT BE DONE. |
| | PLEASE SEE THE SQ FT ON PLANS DOES NOT CORRELATE WITH |
| | THE SUBMITTED ENERGY CALCULATIONS. |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK AS APPLIED WILL NEED TO BE REVISED SUBSTANTIALLY |
| | BASED ON THE COMMENT ABOVE (NOTE #4). |
| | PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO |
| | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT |
| | ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED. |
| | |
| | 6) NOTE: PLEASE STATE THE MINIMUM LEVELS FOR ADA |
| | COMPLIANCE ON THE ELECTRICAL PLANS FOR THE BASE FA |
| | SYSTEM. PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). |
| | |
| | 7) NOTE: PLEASE CLARIFY RISER AS THE *DARKENED* ITEMS |
| | ARE TYPICALLY NEW AND SOME ARE NOTED AS NEW YET THE |
| | PANEL SCHEDULE FOR ETH AND HV MENTIONS THESE ARE |
| | EXISTING? |
| | SOME OF THE OTHER EXISITNG ITEMS ARE VERY LIGHT WHICH |
| | INDICATE EXISTING. |
| | PLEASE CLARIFYA LITTLE MORE FOR WHAT IS NEW AND WHAT |
| | IS EXISTING? |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE PROVIDE MORE INFORMATION AND |
| | COORDINATION OF ETL AS SHOWN AND NOTED ON RISER. PLEASE |
| | INDICATE IF THIS PANEL CONTAINS A MAIN CIRCUIT BREAKER. |
| | IF NOT ONE WILL BE REQUIRED PER 240.21, 408.36. |
| | PLEASE SEE RISER MENTIONS THIS PANEL/SERVICE AS |
| | 300AMPS, YET THE NOTE ON THE SAME RISER INDICATES THIS |
| | PANEL AS 400AMPS? |
| | PLEASE VERIFY AND CLARIFY THE NOTE WHICH MENTIONS THIS |
| | PANEL AS 43 SPACES? THIS IS NOT COMMON AND NOT |
| | PERMITTED PER 408.35 |
| | |
| | 9) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE |
| | SEE THERE ARE FIXTURES WITH SOME NUMERICAL DESIGNATION, |
| | HOWEVER DOES INDICATE PANEL OR LOCATION OF |
| | TERMINATION? |
| | PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO |
| | ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. |
| | PLEASE SEE THE NUMERICAL DESIGNATION AS SHOWN ON PLANS |
| | MAY BE USED FOR THE CIRCUITS ON PANEL SCHEDULE OR LABEL |
| | WITH NAME(S). |
| | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| | THE NEC 408.4. |
| | |
| | *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL |
| | BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON |
| | THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| | PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A |
| | SWITCHBOARD.* |
| | |
| | (EXAMPLE LV1- (31) OFFICE 128/127 RECEPTS) OR |
| | WORDS/IDENTIFICATION TO THAT AFFECT. |
| | PLEASE ALSO SEE THE HANDBOOK WHICH CONTAINS A MORE |
| | EXTENSIVE COMMENTARY FOR THIS SAME SECTION. |
| | |
| | 10) NOTE: PLEASE SEE 422.13 AS WATER HEATER LOADS ARE |
| | TO FIGURED AND SHOWN AT 125%. |
| | |
| | 11) NOTE: PLEASE PROVIDE A COMPLETE LOAD SUMMARY ON HOW |
| | LOADS WERE DERIVED FOR LIGHTING, TRACK LIGHTING, |
| | RECEPTACLES AND ALL EQUIPMENT. |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. PLEASE |
| | INDICATE ANY HEAT LOADS, LARGEST MOTORS ETC. PLEASE SEE |
| | NEC 220, 215.3, 230.42 ETC. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ACCESS |
| | CONTROL LOCKS AS NOTED ON PLANS. PLEASE SEE THE LIFE |
| | SAFETY CODE AND SHOW COMPLIANCE FOR FAIL SAFE OPERATION |
| | OF THESE LOCKS AND DEVICES WHICH SHALL NOT IMPEDE THE |
| | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE SEE |
| | NFPA-101 7.2.1.5, 7.2.1.6.2 |
| | |
| | 13) NOTE: PLEASE KNOW ALL LOW VOLTAGE SYSTEMS WILL BE |
| | REQUIRED TO BE UNDER A SEPARATE PERMIT. THE BASE PLANS |
| | MAY BE REFERENCE WHEN PERMIT(S) ARE APPLIED AND THESE |
| | WILL BE TURN AROUND PERMITS AS LONG AS THE LV APPLIED |
| | FOR IS ON BASE PLANS. |
| | |
| | 14) NOTE: PLEASE SEE PLANS SHOW A SERVER ROOM, HOWEVER |
| | ALSO SEEM TO INDICATE A SEPARATE AHU FOR THIS ROOM. |
| | THIS ROOM APPEARS IT MAY BE AN IT ROOM? PLEASE SEE |
| | NFPA-70 645 FOR REQUIRED DISCONNECTING MEANS FOR |
| | ELECTRICAL, SIZING OF CIRCUITS ETC. |
| | PLEASE SEE NFPA-75 AS THE WALLS ARE REQUIRED TO BE 1HR |
| | FIRE RATED AND ARCHITECTURAL SHEETS DO NOT INDICATE |
| | THESE WALLS AS RATED. |
| | PLEASE CLARIFY IF THERE IS GOING TO BE ANY UPS BACK UP |
| | SYSTEMS INSTALLED. |
| | ** PLEASE PROVIDE MORE INFORMATION. |
| | |
| | 15) NOTE: PLEASE KNOW AS APPLIED THERE IS NOT |
| | SUITE/UNIT NUMBER INDICATED AND THIS PROJECT WILL |
| | REQUIRE ADDRESSING REVIEW. PLEASE BE SURE TO INDICATE |
| | ANY SUITE/UNIT NUMBER ON PLANS(TITLE BLOCK) WHEN |
| | ASSESSED. |
| | FAC 61G1-16.004 |
| | |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT ELECTRICAL PLANS OR DESIGN. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |