Plan Review Notes
Plan Review Notes For Permit 07050509
Permit Number 07050509
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-26 13:01:58BUILDING PLAN REVIEW
 PERMIT: 07050509
 ADD: 515 N.FLAGLER DR
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)750-8288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)SUBMIT THE PREVIOUS FLOOR PLAN OF THE SPACE SHOWING
 THE WALLS TO REMAIN AND THE ONES TO BE DEMOED. THE DEMO
 PLANS SHOWS ONLY THE BATHROOMS, WERE THERE ANY OFFICES
 IN THIS AREA?
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
 4)SUBMIT A LIFESAFETY PLAN SHOWING THE MEANS OF
 EGRESS: A CONTINUOUS AND
 UNOBSTRUCTED WAY OF TRAVEL FROM ANY
 POINT IN A BUILDING OR STRUCTURE TO A
 PUBLIC WAY, CONSISTING OF THREE SEPERATE
 AND DISTINCT PARTS: (1) THE WAY OF THE
 EXIT ACCESS, (2) THE EXIT, AND (3) THE
 THE WAY OF OF THE EXIT DISCHARGE.
 A MEANS OF EGRESS COMPRISES THE VERTICAL
 AND HORIZONTAL WAYS OF TRAVEL AND
 INCLUDE THE INTERVENING ROOM SPACE,DOORS
 CORRIDORS,PASSAGEWAYS,BALCONIES, STAIRS,
 RAMPS, ENCLOSURES, LOBBIES, HORIZONTAL
 EXITS, COURTS AND YARDS.
  
 5)FBC EXISTING SEC. 301.5A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 6)FBC 11-7.2 (2)(I)A PORTION OF THE MAIN COUNTER
 WWHICH IS A MINIMUM OF 36 INCHES IN LENGTH SHALL BE
 PROVIDED WITH A MAXIMUM HEIGHT OF 36 INCHES.
  
 7)SHEET A-7IN REFERENCE TO NOTE #5 FBC.1210.2 WALLS
 WITHIN 2 FEET OF UNIRALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, "HARD" NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. VINYL WALLCOVERING DOES NOT MEET
 THE REQUIREMENT OF "HARD"
  
 8)INDICATE HOW THE LUNCH ROOM WILL MEET THE
 REQUIREMENTS OF SECTION 11-4.24 SHOWING THE KNEE
 CLEARANCE/ CLEAR FLOOR SPACE/HEIGHT ETC. FBC. 11-4.1
 (3) AREAS USED ONLY BY ENPLOYEES AS WORK AREAS. AREAS
 THAT ARE USED ONLY AS WORK AREAS SHALL BE DESIGNED AND
 CONSTRUCTED SO THAT INDIVIDUALS WITH DISABILITIES CAN
 APPROACH, ENTER, AND EXIT THE AREAS.
  
 9)FBC 603.1 ALL BUCKS, HEADERS, BLOCKING ETC. IN
 PARTITIONS, SHALL BE APPROVED FIRE RETARDANT TREATED
 LUMBER.
  
 10) SHEET A-8. NOTE #3 INDICATE A CONCRETE DECK THEN
 NOTE #20 INDICATE A METAL DECK ABOVE. IS THERETWO
 DIFFERENT TYPES OF DECKS? CLARIFY.
  
 11)THE PRINTED NUMBER OF THE ARCHITECT IS ALSO
 REQUIRED ON EACH SHEET OF THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved