| Date |
Text |
| 2007-06-04 14:20:32 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED |
| | FOR THE CUT SECTIONS OF PIPE PER FBC-2004 FUEL GAS |
| | CODE.. PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 2. NOTE: NOT ALL PIPING MATERIAL AND PIPE SIZES ARE |
| | INDICATED ON THE GAS ISOMETRIC. PLEASE CORRECT THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 3. NOTE: THE 2 PSI LONGEST LENGTH INDICATED AS 120' IS |
| | WRONG. WITH THE GIVEN INFORMATION ON DRAWINGS 144' IS |
| | BEING INDICATED FOR THE UNDERGROUND PE TO THE POOL |
| | HEATER, BUT NOT ALL CORRESPONDING LENGTHS ARE INDICATED |
| | FOR THE CUT SECTIONS OF PIPE. PLEASE CORRECT THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THIS GOES ALONG WITH COMMENT NUMBER 1. |
| | |
| | 5. NOTE: 0.5 PSI CSST SIZING TABLE INDICATED IN THE |
| | SUBMITTED DRAWINGS 402.4(16) IS WRONG. THE CORRECT |
| | SIZING TABLE FOR THE 0.5 PSI CSST SHOULD BE 402.4(14). |
| | PLEASE CORRECT THIS AND THE CSST PIPE SIZING ON THE |
| | RESUBMITTAL. PLEASE REFERENCE THE ATTACHED SIZING |
| | TABLES AND THE RED LINE CSST CORRECTIONS INDICATING |
| | THIS. |
| | |
| | 6. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | 7. PLEASE PROVIDE A NOTICE OF COMMENCEMENT RECORDED |
| | WITH THE CLERK OF COURT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS REVIEWER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |