| Plan Review Notes For Permit 07050474 |
| Permit Number |
07050474 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-05-29 16:50:58 | ****************PROVISO**************** | | | ********FBC-2004 PLUMBING********* | | | A} 305.6 WATER SERVICE PIPE SHALL BE INSTALLED NOT | | | LESS THAN 12 INCHES DEEP OR LESS THAN 6 INCHES BELOW | | | THE FROST LINE. | | | | | | B} 608.6.1 CROSS CONNECTIONS BETWEEN PRIVATE WATER | | | SUPPLY AND A POTABLE PUBLIC SUPPLY SHALL BE PROHIBITED. | | | (NOTE: PLEASE CHECK EXISTING 4" GALV. STEEL PIPE, | | | INDUSTRIAL WELL WATER FOR CROSS CONNECTION TO PROPOSED | | | NEW POTABLEWATER LINE) | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|