Plan Review Notes
Plan Review Notes For Permit 07050466
Permit Number 07050466
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-11-12 13:25:29*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 2.THE NUMERICAL ADDRESS IN OUR PERMIT SYSTEM (7515)
 AND THE ONE NOTED ON THE PLANS AND APPLICATION (7915)
 DO NOT CORRELATE.VERIFY THAT THE CORRECT PCN IS BEING
 USED.
  
 3.INDICATE/ILLUSTRATE THE DISTANCE OF THE NEW
 GENERATOR FROM ANY DOORS AND WINDOWS OF THE BUILDING.
  
 *NEW COMMENT:
  
 A.ON SHEET SP-1 IN THE PROJECT SUMMARY UNDER CODES
 AND REGULATIONS, THERE IS A REFERENCE TO PALM BEACH
 COUNTY BUILDING DEPARTMENT CODES.PLEASE BE ADVISED
 THAT THE AHJ IS THE CITY OF WEST PALM BEACH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENTS HAVE BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLAMS
 FIRE PLAN REVIEW
 561-805-6722