Plan Review Notes
Plan Review Notes For Permit 07050466
Permit Number 07050466
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-04 09:03:132007-11-4 09:03:13
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS
 REVIEW ALONG WITH SEVERAL NEW COMMENTS DUE TO CHANGES
 ON PLANS.
  
 1) NOTE: PLEASE SEE THE PLANS AND PERMIT APPLICATION
 PACKAGEWILL BE SENT TO THE ADDRESSING REVIEWER. THE
 PLANS STILL CALL FOR 7915 S DIXIE, YET THE PERMIT
 APPLICATION AS SUBMITTED BY THE CONTRACTOR HAS AN
 APPLIED ADDRESS OF 7515 SOUTH DIXIE. THIS COORDINATION
 IS NEEDED AND CORRECTED BEFORE FINAL SIGNING OFF OF
 PROJECT FOR PERMIT ISSUANCE.
  
 2) NOTE: PLEASE SUBMIT ONE SET OF THE PREVIOUS
 SUBMITTED PLANS FOR REFERENCE.
  
 3) NOTE: PLEASE SEE THE PLANS NOW CONTAIN COMPLETED
 INFORMATION FOR PROPOSING A NEW SECOND LIFE SAFETY
 GENERATOR WHICH WAS NOT COMPLETE ON PREVIOUS PLANS.
 PLEASE SEE THE LIFE SAFETY GENERATOR IS NOW BEING SHOWN
 WITHOUT ANY ON-SITE FUEL WHICH IS REQUIRED PER
 700.12B3. MAY NOT RELY ON THE UTILITY FOR FUEL OF LIFE
 SAFETY ITEMS.
 THE NOTE WHICH MENTIONS * AFTER 2MINS* OF FAILURE TO
 START IS NOT ACCEPTABLE AS LIFE SAFETY SYSTEMS ARE
 REQUIRED WITHIN 10 SECONDS.
  
 4) NOTE: PLEASE ADJUST PERMIT APPLICATION AND VALUE FOR
 OTHER WORK WHICH ISNOW IN THE SCOPE OF PLANS. PLEASE
 SEE FBC 108.3 AS THE VALUE SHALL INCLUDE ALL LABOR, ALL
 MATERIALS, ALL EQUIPMENT, DESIGN COST ETC, EVEN IF
 *ANY* OF THESE ARE OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE NFPA-110 AS THE EMERGENCY
 ELECTRICAL LIFE SAFETY EQUIPMENT MAY NOT BE INSIDE THE
 MAIN ELECTRICAL ROOM. NFPA-110 7.2.2. TRANSFER
 EQUIPMENT MAY BE LOCATED IN ROOM IF MEETING THE
 EXCEPTIONS, HOWEVER AS THE PLANS SHOW THIS IS NOT
 POSSIBLE AS SHOWN.
 PLEASE KNOW THAT THE INTENT OF LIFE SAFETY SYSTEMS IS
 THAT THE IF THERE IS A FIRE OR EXPLOSION WITH THE MAIN
 NORMAL SOURCE ELECTRICAL EQUIPMENT IS THAT THIS WILL
 NOT AFFECT THE LIFE SAFETY EQUIPMENT IN PROVIDING
 ILLUMINATION AND OTHER ESSENTIAL SYSTEMS FOR THE
 OCCUPANTS OFANY STRUCTURE TO GET OUT OF THE BUILDING
 SAFELY.
 THE SYSTEM AS PROPOSED AND SHOWN IS NOT ACCEPTABLE TO
 THIS AHJ AND INFORMATION WILL ALSO BE FORWARDED TO THE
 FIRE MARSHAL FOR REVIEW.
 PLEASE SEE ALL OF 7.2.
  
 6) NOTE: PLEASE SEE THE SERVICE MEANS OF DISCONNECT FOR
 ALL EQUIPMENT AND FEEDERS IS STILL YET TO BE
 DETERMINED. PLEASE SEE 230.76 AND 230.79 FOR SERVICE
 MAINS.
 THIS IS REQUIRED ON BOTH SYSTEMS AS SHOWN. RISER SHOWS
 MLO EQUIPMENT ON BOTH.
 PLEASE SEE 225.31-225.39 AS THE FEEDERS FROM THE
 GENERATOR SHALL ALSO CONTAIN A MEANS OF DISCONNECT
 UNDER EMERGENCY CONDITIONS.
 PLEASE KNOW EVEN AS 700, 701 AND 702 CONTAINS
 EXCEPTIONS TO DISCONNECT POWER/FEEDERS AS REQUIRED PER
 225-32, THE EXCEPTIONS IS THAT THE GENERATOR MEANS OF
 DISCONNECT MUST MEET READILY ACCESSIBLE. NOT BEHIND
 LOCKED ENCLOSURES, LOCKED GATES, ETC.
 THE MEANS OF DISCONNECT SHALL ALSO NOT EXPOSE ANY
 PERSONNEL TO LIVE PARTS OR HAZARDS.
 THE PLANS MENTIONS *ONLY QUALIFIED PERSONNEL* HOWEVER
 IN AN EMERGENCY, THE ONLY PERSONNEL IS MOST LIKELY FIRE
 DEPARTMENT PERSONNEL AND THEY ALONG WITH STORE MANAGER,
 CLERKS ETC ARE NOT CONSIDERED *QUALIFIED*. PLEASE SEE
 NEC 100 FOR DEFINITION.
  
 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS FOR
 PLANS TO BE STAMPED AND REVIEWED BY DERM.
  
 8) NOTE: PLEASE SEE 445.13 AS THE CONDUCTORS FROM THE
 NEW LS GENERATOR DO NOT MEET 310.16. PLEASE SEE 75
 DEGREE COLUMN (110.14) AS THE FEEDERS DO NOT MEET
 300AMPS OR THE 115 PERCENT.
  
 9) NOTE: PLEASE BE SURE TO SUBMIT TWO COMPLETE PACKAGES
 OF ALL PLANS INCLUDING SPEC BOOKS.
 FBC ADMIN SECTION 106.1.3
  
 10) NOTE: LOAD ON GENERATOR STILL EXCEEDS THE RATING OF
 THE GENERATOR. NOT ENOUGH INFORMATION HAS BEEN
 SUBMITTED FOR LOAD SHEDDING.
 702.5
  
 11) NOTE: PLEASE KNOW AT THIS TIME DUE TO MANY ITEMS
 WHICH WILL BE REQUIRED TO BE CHANGED, A COMPLETE REVIEW
 CAN NOT BE DONE.
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME DUE TO CHANGES.
  
 12) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS SIGNAGE
 WILL REQUIRE 1 INCH MINIMUM LETTERING
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-11-04 07:44:092007-11-04 07:44:09
  
 IN ELECTRICAL FOR REVIEW. REMOVED FROM INCOMING, WILL
 RETURN TO INCOMING ONCE COMPLETE.