2007-06-08 15:16:51-----------------DENIED--------------------
  
 1. ABOVE GROUND FUEL TANKS WITH A CAPACITY OF 550
 GALLONS OR MORE SHALL BE SUBMITTED TO PALM BEACH COUNTY
 DERM FOR APPROVAL PRIOR TO ISSUANCE OF A CITY PERMIT.
 FAC 62-762. PLEASE CONTACT DERM AT 561-233-2400 FOR
 ADDITIONAL INFORMATION.
  
 2. PLEASE SEE FAC RULE 61G15-23.002: (2) EACH SHEET OF
 PLANS AND PRINTS WHICH MUST BE SEALED UNDER THE
 PROVISIONS OF CHAPTER 471, F.S., SHALL BE SEALED,
 SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET.
 IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME, ADDRESS, AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  