| 2007-06-07 19:47:29 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN |
| | NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE DO NOT SUBMIT EACH SHEET INDIVIDUALLY. |
| | ALL SHEETS FOR EACH SET SHOULD BE BOUND IN SOME FASHION |
| | INTO SETS. |
| | FBC 106.3 ADMIN SECTION. |
| | **ONE SET WAS MADE BY THIS OFFICE FOR EASE OF REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THE SEAL BEING USED BY THE ENGINEER |
| | OF RECORD AS MR. CARLOS VARGAS PE IS NO LONGER VALID IN |
| | THE STATE OF FLORIDA PER FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.001. |
| | PLEASE KNOW THAT A RULING BY THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS IN FEB 04 REQUIRED ALL SEALS TO |
| | BE CHANGED FOR THE WORDING OF *CERTIFICATE* IN SAID |
| | SEAL TO THE WORDING OF *LICENSE*. AN EXTENSION WAS |
| | GRANTED, HOWEVER ONLY TO THE DATE OF DECEMBER 31, 2005. |
| | PLEASE SEE THIS RULING WAS OVER THREE YEARS AGO, PLEASE |
| | OBTAIN NEW SEAL FROM THE STATE. PERMIT AND PLANS SHALL |
| | NOT BE ISSUED BASED ON THE SEAL AS SHOWN ON PLANS. FS |
| | 471 |
| | ** REQUIRED ON ALL SHEETS AND FOR ALL TRADE REVIEWER(S) |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR GERS USA AS REQUIRED PER FAC 61G15-23.002 AND FS |
| | 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ** REQUIRED ON ALL SHEETS AND FOR ALL TRADES EVEN IF |
| | COMMENT IS NOT MADE BY OTHER TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THE 2002 NFPA-110 IS TO BE STATED |
| | ON PLANS. PLEASE BE SURE TO SEE COMMENTS FROM OTHER |
| | TRADES FOR THE ADOPTED YEARS OF THE SPECIFIC EDITIONS |
| | TO CODE RELEVANT TO THE DESIGN AND SCOPE OF WORK. FBC |
| | 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR, EACH ATS AND FUEL TANK. |
| | PLEASE KNOW SOME ITEMS FOR CODE COMPLIANCE CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | 90.7, 110.3, 230.70, 230.76, 230.79 ETC. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE 240.4C FOR CONDUCTORS FROM THE |
| | GENERATOR TO THE MAINS ATS SWITCHBOARD. |
| | PLEASE SEE DEVICES RATED OVER 800AMPS. |
| | |
| | 7) NOTE: PLEASE SEE THE PLANS CALL FOR ONE ATS ON |
| | RISER, YET THEE-2 INDICATES TWO DIFFERENT *NEW* ATS |
| | SWITCHES. AS ONE IS MISSING FROM RISER, REVIEW OF THE |
| | SECOND CAN NOT BE DONE. |
| | PLEASE SEE THE PLANS ALSO INCLUDE A TRANSFER SWITCH |
| | INSIDE? |
| | PLEASE SEE THE RISER ALSO INDICATES AN EXISTING |
| | EMERGENCY PANEL, YET NO GENERATOR FOR EXISTING LEGALLY |
| | REQUIRED/LIFE SAFETY REQUIRED SYSTEMS WAS SHOWN ON |
| | PLANS. |
| | COORDINATION OF SERVICE, DISCONNECTS AND OTHER ITEMS |
| | CAN NOT BE DONE AT THIS TIME. |
| | PLEASE COMPLETE PLANS FOR ALL EXISTING SERVICE |
| | EQUIPMENT AND NEW SERVICE EQUIPMENT. |
| | 215.5, 700, 701, 702, 230, 408, 225 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE LOADS INDICATED ON THE PLANS |
| | EXCEEDS THAT OF THE RATING OF THE BREAKER. PLEASE |
| | EITHER INCREASE GENERATOR OR, PLEASE SUBMIT DETAILED |
| | INFORMATION ON *AUTOMATED* LOAD SHEDDING AS REQUIRED. |
| | 220, 702.5, 700.5, 701.6 |
| | |
| | 9) NOTE: PLEASE SEE THE ADDRESS AS STATED ON TITLE |
| | BLOCKS IS NOT THAT OF THE ADDRESS OF THE APPLIED |
| | LOCATION. PLEASE SEE PERMIT APPLICATION AND SYSTEM |
| | WHICH IS FOR 7515 S DIXIE. |
| | PLEASE ADJUST |
| | FAC 61G-23.002 |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT SUBMITTED PLANS. (MECHANICAL FOR DERM |
| | REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |