Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop P
Sequence Number 3
Notes
Date Text
2007-10-31 14:43:14DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, NOT ADDRESSED
 ******NO RESPONSE, NOT ADDRESSED
 B. OK
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 ****NO RESPONSE, NOT ADDRESSED
 ******NO RESPONSE, CABINET DOORS ARE STILL SHOWN ON
 ELEVATION.
 D. OK
 E. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, NOT ADDRESSED. NO COMMENT RESPONSES
 SUBMITTED.
 ******NO RESPONSE, NOT ADDRESSED
  
 **********NEW COMMENTS**********
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST
 SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE
 REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC
 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE
 THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR
 FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE
 SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD. ******NO
 RESPONSE, NOT ADDRESSED.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH
 REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN
 REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS
 TIME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]