| Plan Review Notes For Permit 07050394 |
| Permit Number |
07050394 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-14 11:05:26 | ** REDLINED PLANS ** | | | | | | 1) NOTE: RELINED MISSING *EQUIPMENT GROUNDING | | | CONDUCTORS* STILL NOT INSTALLED AFTER THE FIRST MEANS | | | OF DISCONNECT PER 250.110, 250.24, 250.122. (GUTTER TO | | | TENANT MAIN, MAIN PANEL TO SUB PANELS.) | | | FLOATING NEUTRAL KIT REQUIRED AT TENANT METER CAN. | | | 250.6 | | | | | | 2) NOTE: THE METHOD *A* ENERGY CALCULATIONS SUBMITTED | | | HAVE BEEN MARKED AS N/A. THE STATE HAS CONFIRMED SINCE | | | THE LAST REVIEW THAT METHOD A CAN NOT BE USED FOR | | | TENANT BUILD-OUTS AS THIS IS NOT A *WHOLE* BUILDING | | | WHICH IS BEING DONE. THE LIGHTING PERFORMANCE | | | CALCULATIONS PROVIDED ON ELECTRICAL SHEETS IS ALL THAT | | | IS NEEDED FOR ELECTRICAL REVIEWER PER 13-415.2 | | | | | | ELECTRICAL PLANS STAMPED. IF MAKING REVISIONS FOR ANY | | | OTHER CHANGES DURING PROJECT, PLEASE ADDRESS COMMENT #1 | | | ABOVE AT THAT TIME. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|