Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-14 11:05:26** REDLINED PLANS **
  
 1) NOTE: RELINED MISSING *EQUIPMENT GROUNDING
 CONDUCTORS* STILL NOT INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT PER 250.110, 250.24, 250.122. (GUTTER TO
 TENANT MAIN, MAIN PANEL TO SUB PANELS.)
 FLOATING NEUTRAL KIT REQUIRED AT TENANT METER CAN.
 250.6
  
 2) NOTE: THE METHOD *A* ENERGY CALCULATIONS SUBMITTED
 HAVE BEEN MARKED AS N/A. THE STATE HAS CONFIRMED SINCE
 THE LAST REVIEW THAT METHOD A CAN NOT BE USED FOR
 TENANT BUILD-OUTS AS THIS IS NOT A *WHOLE* BUILDING
 WHICH IS BEING DONE. THE LIGHTING PERFORMANCE
 CALCULATIONS PROVIDED ON ELECTRICAL SHEETS IS ALL THAT
 IS NEEDED FOR ELECTRICAL REVIEWER PER 13-415.2
  
 ELECTRICAL PLANS STAMPED. IF MAKING REVISIONS FOR ANY
 OTHER CHANGES DURING PROJECT, PLEASE ADDRESS COMMENT #1
 ABOVE AT THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 REVIEWER.
  