Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop P
Sequence Number 2
Notes
Date Text
2007-09-15 08:21:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE
 FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION
 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT CALCULATIONS SHOW 2 LAVS
 REQUIRED. PER SECTION 403.1 3 LAVS ARE REQUIRED. ALSO
 RESPONSE THAT BOTTLED WATER WILL BE SUBSTITUTED FOR THE
 DRINKING FOUNTAIN IS NOT APPROVED. PER SECTION 410.1
 BOTTLED WATER DISPENSERS CAN ONLY BE SUBSTITUTED FOR
 50% OF THE REQUIRED DRINKING FOUNTAINS. AS THERE IS
 ONLY ONE DRINKING FOUNTAIN THAT WOULD 100% OF THE
 REQUIRED DRINKING FOUNTAINS. PLEASE PROVIDE A DRINKING
 FOUNTAIN AND INDICATE THE LOCATION ON THE FLOOR PLAN.
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****NO RESPONSE, NOT ADDRESSED
 B. 11-4.24.4 SINK DEPTH
 ****RESPONSE NOTED, PLEASE PROVIDE MANUF.
 SPECIFICATIONS FOR THE SINK SHOWING DIMENTIONS TO SHOW
 COMPLIANCE.
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 ****NO RESPONSE, NOT ADDRESSED
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, NOT ADDRESSED
 E. 11-4.24.7 FAUCET
 ****RESPONSE NOTED, PROVIDE MANUF. SPECIFICATIONS FOR
 FAUCET TO SHOW COMPLIANCE
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 ****NO RESPONSE, NOT ADDRESSED
  
 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL
 FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES
 WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD,
 NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE
 "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED
 HOW THIS REQUIREMENT WILL BE COMPLIED WITH.
 ****NO RESPONSE, NOT ADDRESSED
  
 7. OK
 8. OK
 9. OK
 10. OK
  
 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO
 BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE
 PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED
 AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER
 DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS,
 THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS
 ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE
 CLARIFY. SECTION 604.9.
 ****RESPONES NOTED, BUT THE REQUIRED WATER HAMMER
 ARRESTORS ARE NOT INDICATED AT THE ICE MAKER. PLEASE
 SHOW THE REQUIRED WATER HAMMER ARRESTORS AT THE ICE
 MAKER.
  
 12. OK
 13. OK
 14. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ********NO RESPONSE, NOT ADDRESSED. NO COMMENT
 RESPONSES SUBMITTED.
  
 **********NEW COMMENTS**********
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1B. THE SIGNATURE FOR THE ARCHITECT ON THE FIRST
 SUBMITTAL AND THE SECOND SUBMITTAL DO NOT MATCH. THE
 REQUIREMENT FOR A SIGNATURE IS INDICATED IN FAC
 61G1-16.003, 61G1-16.004(5) AND FS 481.2055. SINCE
 THERE ARE DIFFERENCES IN THE SIGNATURES A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 OF THE ARCHITECT OF RECORD WILL BE REQUIRED FOR OUR
 FILES. COPIES OF BOTH THE FIRST SUBMITTAL AND THE
 SECOND SUBMITTAL SHALL BE RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE ARCHITECTURAL BOARD.
  
 2B. SEE ATTACHED SHEET CONCERNING FS 553.80(2)(B) WITH
 REFERENCE TO THE DESIGN PROFESSIONAL AND REPEATED PLAN
 REVIEW COMMENTS. THIS IS GIVEN AS A NOTICE ONLY AT THIS
 TIME.
  