| Plan Review Notes For Permit 07050394 |
| Permit Number |
07050394 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-09-07 13:24:43 | ***DENIED*** | | | | | | SOME PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. | | | 1) OK | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC. | | | 7.2.1.5. PLEASE ILLUSTRATE IN DOOR SCHEDULE. | | | | | | 4) IN ACCORDANCE WITH LOCAL REQUIREMENTS IN ADDITION TO | | | FAN SHUT DOWN, DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM. | | | | | | 5) OK | | | | | | 6) OK | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|