Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-25 14:19:35 
 *** DENIED 2ND REVIEW ***
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS
 BASED ON INFORMATION NOW PLACED ON PLANS OR INFORMATION
 NOW SUBMITTED WHICH WAS NOT ON PREVIOUS PLANS.
  
  
 1) NOTE: PLEASE SEE PREVIOUS COMMENT #3 BELOW REQUESTED
 THE REQUIRED INFORMATION ON TITLE BLOCKS FOR
 ENGINEERING FIRM AS THESE WERE MISSING THE CERTIFICATE
 OF AUTHORIZATION NUMBERS.
 PLEASE SEE THE CA NUMBER WHICH WAS ADDED TO MEP SHEETS
 IS IN FACT AS OF THIS REVIEW STILL *DELINQUENT* WITH
 THE STATE OF FLORIDA SINCE 2/28/07. PLEASE SEE THE
 ATTACHED PRINT OUT FROM THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION AS OF THIS REVIEW.
 PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND MEP
 SHEETS EVEN IF ANY OTHER TRADES DO NOT MAKE THE COMMENT
 AND/OR HAS PASSED THEIR REVIEW.
 AS THE LICENSURE OF THE FIRM IS NOT CURRENT THE PLANS
 BECOME VOID.
  
 2) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #5 WHICH
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13. MANY ITEMS
 WERE DONE HOWEVER PLEASE SEE THE FOLLOWING.
 PLEASE SEE SOME AREAS WHICH REQUIRES CONTROLS FOR
 SEPARATE SPACES DO NOT INDICATE ANY AUTOMATED CONTROLS
 ONLY THE STANDARD SWITCHES.13-415.1.ABC.1.1, .1.2.
 PLEASE SEE FBC CHAPTER 13 AS THE ENERGY CALCULATIONS
 NEED SOME CORRECTIONS.
 PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES
 AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA
 REPORT DOES NOT CORRELATE WITH PLANS. THIS IS THE SAME
 NOTE AS THE INFORMATION ON THE IDR STILL DOES NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES IS SHOWN AS 1(ONE)
 WHEN PLANS CONTAIN MANY MORE THAN THIS.
 PLEASE SEE THE WATTAGE ON EACH FIXTURE NEEDS TO BE
 PLACED ON THE IDR. (ONLY SHOW THE TOTAL WATTAGE FOR ONE
 FIXTURE).
 PLEASE SEE THE METHOD OF CONTROLS STILL SHOWS *MANUAL
 ON/OFF* WHEN THE METHOD OF CONTROLS IS NOT THE SAME.
 PLEASE SEE 13-415.A.1, 13-415.2
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS
 THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS
 SOME KIND OF STORAGE ROOM.
 THIS NOTE REMAINS AS THE PLANS NOW INDICATE THIS AS A
 MECHANICAL ROOM AND NO MECHANICAL EQUIPMENT IS SHOWN OR
 IN THE DESIGN OF THIS ROOM.
 PLEASE ALSO SEE SOME OTHER SHEETS STILL INCLUDE THIS AS
 A CLOSET. THE LOCATIONS OF THE PANEL AND THE OVER
 CURRENT PROTECTION DEVICES IS MOST IMPORTANT IN THE
 INTEREST OF LIFE SAFETY FOR READY ACCESS TO THE
 BREAKERS. THIS IS ALSO IMPORTANT AS THE STORAGE OF
 COMBUSTIBLES AND EASILY IGNITABLE MATERIALS COULD
 CREATE A FIRE OR LIFE SAFETY HAZARD.
 ANY IMPROPER INSTALLATION LOCATIONS WHERE AN OCCUPANT
 CAN NOT TURN OFF POWER IN A QUICK AND READY FASHION OR
 THE CAUSE OF FIRE, COULD RESULT IN SERIOUS INJURY OR
 DEATH. THIS IS ALSO A PROPERTY HAZARD.
 PLEASE ADJUST LOCATION.
 110.26, 408.7, 240.24, 90.4.
  
 7) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW
 HOWEVER A MAIN DISCONNECT IS NOW SHOWN:
 PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER
 WHAT IS BEING SHOWN AS THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER
 WITH EQUIPMENT GROUNDING CONDUCTORS.
  
 8) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE
 SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517
 AND 517.13.
 PLEASE EXPAND ON THE GROUNDING REQUIRED.
 THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE
 CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE
 FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO
 HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES
 THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO
 IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL
 INVOLVED.
 **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS
 IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE
 NOT.
  
 9) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON
 PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI
 RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR
 ELECTRICAL REVIEW OF CODE RELATED ITEMS
 440.11, 110.26, 210.63, 210.8B
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]