| 2007-08-25 14:19:35 | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS |
| | BASED ON INFORMATION NOW PLACED ON PLANS OR INFORMATION |
| | NOW SUBMITTED WHICH WAS NOT ON PREVIOUS PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS COMMENT #3 BELOW REQUESTED |
| | THE REQUIRED INFORMATION ON TITLE BLOCKS FOR |
| | ENGINEERING FIRM AS THESE WERE MISSING THE CERTIFICATE |
| | OF AUTHORIZATION NUMBERS. |
| | PLEASE SEE THE CA NUMBER WHICH WAS ADDED TO MEP SHEETS |
| | IS IN FACT AS OF THIS REVIEW STILL *DELINQUENT* WITH |
| | THE STATE OF FLORIDA SINCE 2/28/07. PLEASE SEE THE |
| | ATTACHED PRINT OUT FROM THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION AS OF THIS REVIEW. |
| | PLEASE KNOW THIS IS REQUIRED FOR ALL TRADES AND MEP |
| | SHEETS EVEN IF ANY OTHER TRADES DO NOT MAKE THE COMMENT |
| | AND/OR HAS PASSED THEIR REVIEW. |
| | AS THE LICENSURE OF THE FIRM IS NOT CURRENT THE PLANS |
| | BECOME VOID. |
| | |
| | 2) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #5 WHICH |
| | REQUESTED COMPLIANCE FOR FBC CHAPTER 13. MANY ITEMS |
| | WERE DONE HOWEVER PLEASE SEE THE FOLLOWING. |
| | PLEASE SEE SOME AREAS WHICH REQUIRES CONTROLS FOR |
| | SEPARATE SPACES DO NOT INDICATE ANY AUTOMATED CONTROLS |
| | ONLY THE STANDARD SWITCHES.13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE FBC CHAPTER 13 AS THE ENERGY CALCULATIONS |
| | NEED SOME CORRECTIONS. |
| | PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES |
| | AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA |
| | REPORT DOES NOT CORRELATE WITH PLANS. THIS IS THE SAME |
| | NOTE AS THE INFORMATION ON THE IDR STILL DOES NOT |
| | CORRELATE WITH PLANS. |
| | PLEASE SEE THE NUMBER OF FIXTURES IS SHOWN AS 1(ONE) |
| | WHEN PLANS CONTAIN MANY MORE THAN THIS. |
| | PLEASE SEE THE WATTAGE ON EACH FIXTURE NEEDS TO BE |
| | PLACED ON THE IDR. (ONLY SHOW THE TOTAL WATTAGE FOR ONE |
| | FIXTURE). |
| | PLEASE SEE THE METHOD OF CONTROLS STILL SHOWS *MANUAL |
| | ON/OFF* WHEN THE METHOD OF CONTROLS IS NOT THE SAME. |
| | PLEASE SEE 13-415.A.1, 13-415.2 |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS |
| | THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS |
| | SOME KIND OF STORAGE ROOM. |
| | THIS NOTE REMAINS AS THE PLANS NOW INDICATE THIS AS A |
| | MECHANICAL ROOM AND NO MECHANICAL EQUIPMENT IS SHOWN OR |
| | IN THE DESIGN OF THIS ROOM. |
| | PLEASE ALSO SEE SOME OTHER SHEETS STILL INCLUDE THIS AS |
| | A CLOSET. THE LOCATIONS OF THE PANEL AND THE OVER |
| | CURRENT PROTECTION DEVICES IS MOST IMPORTANT IN THE |
| | INTEREST OF LIFE SAFETY FOR READY ACCESS TO THE |
| | BREAKERS. THIS IS ALSO IMPORTANT AS THE STORAGE OF |
| | COMBUSTIBLES AND EASILY IGNITABLE MATERIALS COULD |
| | CREATE A FIRE OR LIFE SAFETY HAZARD. |
| | ANY IMPROPER INSTALLATION LOCATIONS WHERE AN OCCUPANT |
| | CAN NOT TURN OFF POWER IN A QUICK AND READY FASHION OR |
| | THE CAUSE OF FIRE, COULD RESULT IN SERIOUS INJURY OR |
| | DEATH. THIS IS ALSO A PROPERTY HAZARD. |
| | PLEASE ADJUST LOCATION. |
| | 110.26, 408.7, 240.24, 90.4. |
| | |
| | 7) NOTE: THIS IS THE SAME COMMENT AS PREVIOUS REVIEW |
| | HOWEVER A MAIN DISCONNECT IS NOW SHOWN: |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER |
| | WHAT IS BEING SHOWN AS THE FIRST MEANS OF DISCONNECT. |
| | PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER |
| | WITH EQUIPMENT GROUNDING CONDUCTORS. |
| | |
| | 8) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE |
| | SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517 |
| | AND 517.13. |
| | PLEASE EXPAND ON THE GROUNDING REQUIRED. |
| | THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE |
| | CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE |
| | FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO |
| | HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES |
| | THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO |
| | IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL |
| | INVOLVED. |
| | **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS |
| | IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE |
| | NOT. |
| | |
| | 9) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON |
| | PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI |
| | RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR |
| | ELECTRICAL REVIEW OF CODE RELATED ITEMS |
| | 440.11, 110.26, 210.63, 210.8B |
| | |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |