2007-09-01 14:01:51BUILDING PLAN REVIEW
 PERMIT: 07050394
 ADD: 2581 METRO CENTRE BLVD
 CONT: ANDERSON-MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-4) COMPLIED.
  
 5) 2ND REQUEST, SHEET A-2 INDICATES THERE IS ATTACHED
 TO THESE PLANS A REPORT ABOUT LEAD SHIELDING STUDY IN
 REGARDS TO X-RAY ROOMS, NOT ATTACHED TO EITHER SET OF
 PLANS.
 435.5.1 SHIELDING.
 EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY
 PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN
 INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS
 OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5,
 FLORIDA ADMINISTRATIVE CODE .
  
 435.5.1.1
 STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL
 BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND
 WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7
 FEET (2.1 M).
  
 435.5.1.2
 DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL
 HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT
 REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE
 INSTALLED.
  
 435.5.1.3
 PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT
 ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS
 OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF
 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC
 PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH
 FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE
 BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD,
 USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 435.5.1.3.1
 THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING:
 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S
 RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS;
 GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY
 WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S
 BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL.
 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS
 OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS,
 FLOOR AND CEILING OF THE ROOM CONCERNED.
 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED.
 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT
 AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM
 CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE
 TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS
 MAY BE PRESENT.
 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT
 AND THE MAXIMUM TECHNIQUE FACTORS.
 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS
 WHICH WILL BE PERFORMED WITH THE EQUIPMENT.
  
 6) SEMI-COMPLIED. DOORS & CABINET FLOOR ARE TO BE
 REMOVED FROM THE LOUNGE SINK FRONT
 FOR A FRONTAL APPROACH.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 7-8 COMPLIED.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  