| 2007-09-01 14:01:51 | BUILDING PLAN REVIEW |
| | PERMIT: 07050394 |
| | ADD: 2581 METRO CENTRE BLVD |
| | CONT: ANDERSON-MOORE CONSTRUCTION |
| | TEL: (561)662-1819 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) 2ND REQUEST, SHEET A-2 INDICATES THERE IS ATTACHED |
| | TO THESE PLANS A REPORT ABOUT LEAD SHIELDING STUDY IN |
| | REGARDS TO X-RAY ROOMS, NOT ATTACHED TO EITHER SET OF |
| | PLANS. |
| | 435.5.1 SHIELDING. |
| | EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY |
| | PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN |
| | INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS |
| | OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5, |
| | FLORIDA ADMINISTRATIVE CODE . |
| | |
| | 435.5.1.1 |
| | STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL |
| | BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND |
| | WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 |
| | FEET (2.1 M). |
| | |
| | 435.5.1.2 |
| | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL |
| | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT |
| | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE |
| | INSTALLED. |
| | |
| | 435.5.1.3 |
| | PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT |
| | ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS |
| | OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF |
| | 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC |
| | PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH |
| | FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE |
| | BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, |
| | USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR |
| | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN |
| | INTO CONSIDERATION. |
| | |
| | 435.5.1.3.1 |
| | THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: |
| | 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S |
| | RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; |
| | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY |
| | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S |
| | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. |
| | 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS |
| | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, |
| | FLOOR AND CEILING OF THE ROOM CONCERNED. |
| | 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. |
| | 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT |
| | AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM |
| | CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE |
| | TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS |
| | MAY BE PRESENT. |
| | 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT |
| | AND THE MAXIMUM TECHNIQUE FACTORS. |
| | 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS |
| | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. |
| | |
| | 6) SEMI-COMPLIED. DOORS & CABINET FLOOR ARE TO BE |
| | REMOVED FROM THE LOUNGE SINK FRONT |
| | FOR A FRONTAL APPROACH. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK. |
| | |
| | 7-8 COMPLIED. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |