Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-16 08:55:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. PLEASE INDICATE THE RELEVENT CODES ON THE PLANS THAT
 HAVE BEEN ADOPTED BY THE STATE OF FLORIDA AND
 AMENDMENTS BY THE CITY OF WEST PALM BEACH.
  
 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(1) &
 FS 481.219, 481.2055 THE FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. (SEE ATTACHED SHEET).
  
 3. SHT A-1 PLUMBING FIXTURE CALCULATIONS. SEPARATE
 FACILITIES FOR MEN & WOMEN ARE REQUIRED PER SECTION
 403.2 AND PER TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. PLEASE INDICATE THE LOCATION OF THE DRINKING
 FOUNTAIN.
  
 4. SHT A-2 ROOM 132 LOUNGE & DETAIL 8 SHT A-7. THE
 ACCESSIBLE SINK SHALL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE - (FORWARD APPROACH
 REQUIRED, MAX 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCET
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 6. SHT A-5 FINISH SCHEDULE. ROOMS 108, 109 & 136 WALL
 FINISH INDICATES EPOXY PAINT. SECTION 1210.2 REQUIRES
 WALS WITHIN 2' OF W/C'S TO HAVE SMOOTH, HARD,
 NONABSORBENT SURFACES. EXPOX PAINT DOES NOT MEET THE
 "HARD" REQUIREMENT OF THIS SECTION. PLEASE INDICATED
 HOW THIS REQUIREMENT WILL BE COMPLIED WITH.
  
 7. ALL ELECTRICAL & PLUMBING SHEETS. THE CERTIFICATE OF
 AUTHORIZATION OF THE BUSINESS IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. 61G15-23.002(2) & FS 471.025.
 RESEARCH INDICATES THAT THE CERTIFICATE OF
 AUTHORIZATION ON THE STATE DBPR WEBSITE IS IN THE
 DELINQUENT STATUS. (SEE ATTACHED SHEET). PLEASE UPDATE
 & UPGRADE THE CERTIFICATE OF AUTHORIZATION STATUS PRIOR
 TO RESUBMITTING.
  
 8. SHT P-1 PLEASE INDICATE THE USE OF THE FLOOR DRAIN
 IN THE ROOM ADJACENT TO ROOM 130, (X-RAY). SECTION
 106.1.1. IF THE USE IS TO BE INDIRECT WASTE, THEN A
 FLOOR SINK, OR A HUB DRAIN WILL BE REQUIRED PER
 SECTIONS 803.2 & 803.2.3.
  
 9. SHT P-1 FLOOR DRAINS IN TOILET ROOMS 108 & 109 ARE
 INDICATED AS VENTS. PLEASE CORRECT. SECTION 106.1.1.
  
 10. SHTS P-1 & P-2 THE MOP SINK IN THE JANITOR ROOM IS
 INDICATED AS A FLOOR DRAIN. PLEASE INDICATE THE CORRECT
 FIXTURE. SECTION 106.1.1.
  
 11. SHT P-3 FITTINGS ABOVE ALL FIXTURE STOPS APPEARS TO
 BE AIR CHAMBERS AND THIS SYMBOL IS NOT INDICATED ON THE
 PLUMBING PIPING LEGEND. AIR CHAMBERS ARE NOT APPROVED
 AND IF THESE ARE AIR CHAMBERS, PLEASE DELETE FROM RISER
 DIAGRAM. PDI-WH 201.-IF WATER HAMMER ARRESTORS,
 THEY ARE ONLY REQUIRED ON QUICK CLOSING VALVES SUCH AS
 ICE MAKERS, DISH WASHERS OR WASH MACHINES ETC. PLEASE
 CLARIFY. SECTION 604.9.
  
 12. SHT P-4 WATER HEATER DETAIL. PLEASE INDICATE WHAT
 THE PIPING ON TOP OF THE PRESSURE/TEMPERATURE VALVE IS
 FOR. SECTION 106.1.1.--THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE INDICATE METHOD OF
 CONTROL.
  
 13. SHT P-4 PLUMBING GENERAL NOTES & SPECIFICATIONS
 NOTE NUMBER 3. AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE FROM NOTE. SECTION 604.9 & PDI-WH 201.
  
 14. AN RPZV BACKFLOW IS REQUIRE ON THE WATER SERVICE TO
 THE SPACE. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved