Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-07 19:30:47----------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. AHU-3: 8" ROUND SUPPLY DROP IN CORRIDOR 131 MISSING
 GRILL AND CFM DESIGNATION. TWO RETURN DROPS ARE MISSING
 SIZE, GRILL AND CFM DESIGNATIONS IN EXAM ROOMS 1 AND 8.
 NOT ABLE TO CHECK AIR BALANCE FOR THIS SYSTEM DUE TO
 THE MISSING INFORMATION STATED ABOVE.
  
 2. AHU #5 ON FLOOR PLAN SHOWS 1800 CFM SUPPLY AND 1890
 CFM R/A+O.A. IS THIS INTENTIONAL?
  
 3. IF AHU 3 BALANCES WITH EQUAL SUPPLY AND RETURN AS IS
 THE CASE WITH AHU 1 AND 2, THIS SPACE WILL BE AT A
 NEGATIVE PRESSURE.
 AHU-1: 0 (BALANCED)
 AHU-2: 0 (BALANCED)
 AHU-3: 0 (IF BALANCED)
 AHU-4: +50 CFM
 AHU-5: -90 CFM
 EF'S: -250 CFM
 A NET NEGATIVE 290 CFM.
 MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT
 BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS. FBC
 13-409.1.ABC.2
  
 4. AIRFLOW SCHEDULE: OUTDOOR AIR VENTILATION RATES ARE
 TO BE DETERMINED BY FBC,M TABLE 403.3 OR ASHRAE
 62.1-2004
  
 5. COND. UNIT INSTALLATION DETAIL: OUTDOOR EQUIPMENT
 SHALL BE INSTALLED TO MEET 140 MPH WIND LOAD
 REQUIREMENTS PER FBC,M 301.13 AND FBC CH.16. HEIGHT OF
 CONDENSER STAND TO BE IN COMPLIANCE WITH THE CLEARANCE
 REQUIREMENTS OF FBC TABLE 1509.7. DO NOT INSTALL STRAPS
 OR CABLES FOR WIND LOADS OVER EQUIPMENT IN A MANNER
 THAT WILL INTERFERE WITH EQUIPMENT SERVICE ACCESS.
  
 6. ENERGY CALCULATIONS: PLEASE SHOW TOTAL TONNAGE OF
 EQUIPMENT ON FRONT PAGE, AND LIST ALL COOLING EQUIPMENT
 TO SHOW THE COOLING CAPACITY OF EACH OF THE 5 SYSTEMS
 ON PAGE 4 OF THE INPUT DATA REPORT.
  