| Plan Review Notes For Permit 07050394 |
| Permit Number |
07050394 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-07-05 11:58:32 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | 3) DOOR LOCKS TO BE IN COMPLIANCE WITH NFPA 101, SEC. | | | 7.2.1.5. | | | | | | 4) FIRE ALARM EQUIPMENT IS SHOWN ON ELECTRICAL SHEETS. | | | NEW DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | 5) PLEASE INDICATE IF THIS BUILDING IS PROTECTED BY AN | | | AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | 6) PLEASE SHOW LOCATION OF FIRE EXTINGUISHERS (2A-10B,C | | | RATED) THAT SHALL BE MOUNTED AT DISTANCES NOT TO EXCEED | | | 75' TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|