Plan Review Notes
Plan Review Notes For Permit 07050394
Permit Number 07050394
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-07 20:42:22*** UNSAT ***
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT
 THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN
 NOT BE REVIEWED FOR CODE COMPLIANCE.
  
 1) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS
 ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH,
 2006.
 PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL
 SHEETS AS WELL AS ARCHITECTURAL.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70 (NEC).
 2003 NFPA-101 (LS CODE)
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM PER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE
 ENGINEERING FIRM PER FAC 61G15-23.002 AND FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE ELECTRICAL PLANS APPEAR TO BE
 SIGNED WITH INITIALS, IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ENGINEER OF RECORD, PLEASE PROVIDE A
 LETTER FOR SIGNATURE VERIFICATION. PLEASE BE SURE THE
 LETTER IS SIGNED, DATED SEALED AND CORRECTLY
 NOTARIZED.
 PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE
 FOR ANY FUTURE REFERENCE. FS 471.025
 PLEASE SEE FS 117.05 FOR CORRECT NOTARY REQUIREMENTS.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS THE ENERGY
 CALCULATIONS NEED SOME CORRECTIONS.
 PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES
 AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA
 REPORT DOES NOT CORRELATE WITH PLANS.
 PLEASE SEE 13-415.AB1.1, 13-415.2
 PLEASE SEE FBC CHAPTER 13FOR MISSING COMPLIANCE FOR
 ALL LIGHTING CONTROLS. NO DESIGN IS SUBMITTED AT THIS
 TIME AND REVIEW FOR COMPLIANCE FOR ANY SYSTEM, DEVICES
 ETC CAN NOT BE DONE AT THIS TIME.
 PLEASE SUBMIT SCHEDULING FOR ANY SYSTEM INSTALLED.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR TYPE OF DEVICES
 CHOSEN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS
 THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS
 SOME KIND OF STORAGE ROOM.
 PLEASE ADJUST LOCATION.
 110.26, 408.7, 240.24 ETC
  
 7) NOTE: PLEASE SEE PLANS INDICATE SERVICE EQUIPMENT AS
 BEING 800AMPS, YET THE RISER DOES NOT SHOW ANY OF
 THIS.
 PLEASE COMPLETE RISER FOR THE SIZE OF SERVICE, LOAD ON
 EXISTING SERVICE AND NEW LOAD BEING ADDED.
 PLEASE COMPLETE, SHOW LOCATION AND IDENTIFY ALL SERVICE
 EQUIPMENT ON PLANS.
 215.5, 110.26, 230 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS AFTER WHAT IS BEING SHOWN AS THE FIRST MEANS
 OF DISCONNECT.
 PLEASE KNOW AS THE RISER DOES NOT SHOW ANY MAIN AT THIS
 TIME ON THE LINE OF THE PARTIAL GUTTER AS SHOWN, IT CAN
 NOT BE DETERMINED IF A FLOATING NEUTRAL IS REQUIRED AT
 THIS TIME.?
 PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER
 WITH EQUIPMENT GROUNDING CONDUCTORS.
  
 9) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE
 SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517
 AND 517.13.
 PLEAS KNOW AT THIS TIME, IT APPEARS 517 MAY NOT APPLY
 BASE DON PLANS, HOWEVER PLEASE PROVIDE MORE
 INFORMATION.
  
 10) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND SUMMARIES
 ON HOW LOADS FOR EACH WERE DERIVED.
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 (LIGHTING, WATER HEATER)
 PLEASE SEE NEC 220, 215.3, 230.42,422.13 ETC.
  
 11) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON
 APPLICATION AS WELL AS TITLE BLOCKS.
 FAC 61G1-16.004
 FBC 106.1.2
  
 12) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS PER
 FBC CHAPTER 11 FOR ADA.
 11-4.28.1,.2 AND .3(4).
 SOME LEVELS ARE ALREADY ON PLANS FOR COMPLIANCE HOWEVER
 PLEASE LIST OTHERS.
  
 13) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON
 PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI
 RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR
 ELECTRICAL REVIEW OF CODE RELATED ITEMS
 440.11, 110.26, 210.63, 210.8B
  
 **PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]