| Date |
Text |
| 2007-06-07 20:42:22 | *** UNSAT *** |
| | |
| | ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT |
| | THIS TIME FOR REVIEW, THERE ARE SOME ITEMS WHICH CAN |
| | NOT BE REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 1) NOTE: PLEASE STATE ALL OF THE RELEVANT CODES AS |
| | ADOPTED FROM THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| | 2006. |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ELECTRICAL |
| | SHEETS AS WELL AS ARCHITECTURAL. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | 2003 NFPA-101 (LS CODE) |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON |
| | TITLE BLOCKS FOR THE ARCHITECTURAL FIRM PER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE |
| | ENGINEERING FIRM PER FAC 61G15-23.002 AND FS 471.023. |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE SEE ELECTRICAL PLANS APPEAR TO BE |
| | SIGNED WITH INITIALS, IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ENGINEER OF RECORD, PLEASE PROVIDE A |
| | LETTER FOR SIGNATURE VERIFICATION. PLEASE BE SURE THE |
| | LETTER IS SIGNED, DATED SEALED AND CORRECTLY |
| | NOTARIZED. |
| | PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE |
| | FOR ANY FUTURE REFERENCE. FS 471.025 |
| | PLEASE SEE FS 117.05 FOR CORRECT NOTARY REQUIREMENTS. |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13 AS THE ENERGY |
| | CALCULATIONS NEED SOME CORRECTIONS. |
| | PLEASE SEE THE NUMBER OF FIXTURES, THE TYPE OF FIXTURES |
| | AND WATTAGE OF FIXTURES AS LISTED ON THE INPUT DATA |
| | REPORT DOES NOT CORRELATE WITH PLANS. |
| | PLEASE SEE 13-415.AB1.1, 13-415.2 |
| | PLEASE SEE FBC CHAPTER 13FOR MISSING COMPLIANCE FOR |
| | ALL LIGHTING CONTROLS. NO DESIGN IS SUBMITTED AT THIS |
| | TIME AND REVIEW FOR COMPLIANCE FOR ANY SYSTEM, DEVICES |
| | ETC CAN NOT BE DONE AT THIS TIME. |
| | PLEASE SUBMIT SCHEDULING FOR ANY SYSTEM INSTALLED. |
| | PLEASE INDICATE ALL OVER RIDE TIMES FOR TYPE OF DEVICES |
| | CHOSEN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 6) NOTE: PLEASE KNOW IT WILL NOT BE PERMITTED TO ACCESS |
| | THE ELECTRICAL PANELS THROUGH WHAT IS BEING SHOWN AS |
| | SOME KIND OF STORAGE ROOM. |
| | PLEASE ADJUST LOCATION. |
| | 110.26, 408.7, 240.24 ETC |
| | |
| | 7) NOTE: PLEASE SEE PLANS INDICATE SERVICE EQUIPMENT AS |
| | BEING 800AMPS, YET THE RISER DOES NOT SHOW ANY OF |
| | THIS. |
| | PLEASE COMPLETE RISER FOR THE SIZE OF SERVICE, LOAD ON |
| | EXISTING SERVICE AND NEW LOAD BEING ADDED. |
| | PLEASE COMPLETE, SHOW LOCATION AND IDENTIFY ALL SERVICE |
| | EQUIPMENT ON PLANS. |
| | 215.5, 110.26, 230 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS AFTER WHAT IS BEING SHOWN AS THE FIRST MEANS |
| | OF DISCONNECT. |
| | PLEASE KNOW AS THE RISER DOES NOT SHOW ANY MAIN AT THIS |
| | TIME ON THE LINE OF THE PARTIAL GUTTER AS SHOWN, IT CAN |
| | NOT BE DETERMINED IF A FLOATING NEUTRAL IS REQUIRED AT |
| | THIS TIME.? |
| | PLEASE SEE 250.24, 250.110, 250.122 AND COMPLETE RISER |
| | WITH EQUIPMENT GROUNDING CONDUCTORS. |
| | |
| | 9) NOTE: PLEASE EXPAND ON REQUIREMENTS OF 660. PLEASE |
| | SEE 517 OF THE NEC AND EXPAND ON ANY LOCATIONS PER 517 |
| | AND 517.13. |
| | PLEAS KNOW AT THIS TIME, IT APPEARS 517 MAY NOT APPLY |
| | BASE DON PLANS, HOWEVER PLEASE PROVIDE MORE |
| | INFORMATION. |
| | |
| | 10) NOTE: PLEASE SUBMIT LOAD CALCULATIONS AND SUMMARIES |
| | ON HOW LOADS FOR EACH WERE DERIVED. |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | (LIGHTING, WATER HEATER) |
| | PLEASE SEE NEC 220, 215.3, 230.42,422.13 ETC. |
| | |
| | 11) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER ON |
| | APPLICATION AS WELL AS TITLE BLOCKS. |
| | FAC 61G1-16.004 |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS PER |
| | FBC CHAPTER 11 FOR ADA. |
| | 11-4.28.1,.2 AND .3(4). |
| | SOME LEVELS ARE ALREADY ON PLANS FOR COMPLIANCE HOWEVER |
| | PLEASE LIST OTHERS. |
| | |
| | 13) NOTE: COULD NOT LOCATE ALL CONDENSING UNITS ON |
| | PLANS, REQUIRED DISCONNECTS AND REQUIRE GFI |
| | RECEPTACLES. PLEAS INCLUDE ON ELECTRICAL PLANS FOR |
| | ELECTRICAL REVIEW OF CODE RELATED ITEMS |
| | 440.11, 110.26, 210.63, 210.8B |
| | |
| | **PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |