| 2007-06-19 17:12:59 | BUILDING PLAN REVIEW |
| | PERMIT: 07050394 |
| | ADD: 2581 METROCENTRE BLVD |
| | CONT: SISCA CONSTRUCTION |
| | TEL: (561)248-9041 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) EXISTING BUILDING CODE, LEVEL OF ALTERATION? NOTE : |
| | THIS IS FOR THE WHOLE BUILDING |
| | E) THE OCCUPANT LOAD, SEE 1004. |
| | F) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | G) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | H ) NUMBER OF STORIES (BUILDING) |
| | I ) SQ. FT. UNDER ROOF (TOTAL FOR BUILDING) |
| | |
| | 4)THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE |
| | SPRINKLED, NO FIRE SPRINKLER PLANS SHOW IN THE INDEX OF |
| | SHEETS SO IT WILL BE ASSUMED THE BUILDING IS NOT FIRE |
| | SPRINKLED. THE REQUIREMENT FOR |
| | DEAD END CORRIDORS IS 20'-0". PLEASE LOOK AT CORRIDOR |
| | 110 AND 131 ON THE LEFT SIDE OF THE SHEET, THEY EXCEED |
| | THE 20'-0" LIMIT. FBC 1016.3 BUILDING. |
| | |
| | 5) SHEET A-2 X-RAY ROOM# 130 INDICATES 3 OF THE 4 WALLS |
| | BEING LEAD LINED, 1 WALL IDENTIED AS WALL TYPE (5) |
| | DOESN'T CONTAIN LEAD, WHY? PLEASE PROVIDE MANUFACTURERS |
| | SPEC FOR THE LEAD LINED WALLS. |
| | 106.1.2* ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 6) SHEET A-2 LOUNGE OR ROOM# 132 NEEDS TO REMOVE THE |
| | DOORS FROM UNDERTHE SINKSHELVING AND CABINET FLOOR TO |
| | COMPLY WITH: SINKS: |
| | 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK |
| | |
| | 7)PLEASE PROVIDE THE MINIMUM RADIANT FLUX OF THE |
| | FLOOR CARPET.804.5.1 MINIMUM CRITICAL RADIANT FLUX . |
| | INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT |
| | PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS |
| | THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN |
| | CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S. |
| | IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL |
| | COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART |
| | 1630). |
| | |
| | 8) PLANSDO NOT INDICATE TO WHICH FLOOR THIS OFFICE IS |
| | LOCATED, ABOVE THE FIRST OR GROUND FLOOR THE DENSE |
| | FILING MAY BE A LIVE LOAD ISSUE. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |