2007-06-19 17:12:59BUILDING PLAN REVIEW
 PERMIT: 07050394
 ADD: 2581 METROCENTRE BLVD
 CONT: SISCA CONSTRUCTION
 TEL: (561)248-9041
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) EXISTING BUILDING CODE, LEVEL OF ALTERATION? NOTE :
 THIS IS FOR THE WHOLE BUILDING
 E) THE OCCUPANT LOAD, SEE 1004.
 F) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 H ) NUMBER OF STORIES (BUILDING)
 I ) SQ. FT. UNDER ROOF (TOTAL FOR BUILDING)
  
 4)THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLED, NO FIRE SPRINKLER PLANS SHOW IN THE INDEX OF
 SHEETS SO IT WILL BE ASSUMED THE BUILDING IS NOT FIRE
 SPRINKLED. THE REQUIREMENT FOR
 DEAD END CORRIDORS IS 20'-0". PLEASE LOOK AT CORRIDOR
 110 AND 131 ON THE LEFT SIDE OF THE SHEET, THEY EXCEED
 THE 20'-0" LIMIT. FBC 1016.3 BUILDING.
  
 5) SHEET A-2 X-RAY ROOM# 130 INDICATES 3 OF THE 4 WALLS
 BEING LEAD LINED, 1 WALL IDENTIED AS WALL TYPE (5)
 DOESN'T CONTAIN LEAD, WHY? PLEASE PROVIDE MANUFACTURERS
 SPEC FOR THE LEAD LINED WALLS.
 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A-2 LOUNGE OR ROOM# 132 NEEDS TO REMOVE THE
 DOORS FROM UNDERTHE SINKSHELVING AND CABINET FLOOR TO
 COMPLY WITH: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK
  
 7)PLEASE PROVIDE THE MINIMUM RADIANT FLUX OF THE
 FLOOR CARPET.804.5.1 MINIMUM CRITICAL RADIANT FLUX .
 INTERIOR FLOOR FINISH IN VERTICAL EXITS, EXIT
 PASSAGEWAYS AND EXIT ACCESS CORRIDORS SHALL NOT BE LESS
 THAN CLASS I IN GROUPS I-2 AND I-3 AND NOT LESS THAN
 CLASS II IN GROUPS A, B, E, H, I- 4, M, R-1, R-2 AND S.
 IN ALL OTHER AREAS, THE INTERIOR FLOOR FINISH SHALL
 COMPLY WITH THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, PART
 1630).
  
 8) PLANSDO NOT INDICATE TO WHICH FLOOR THIS OFFICE IS
 LOCATED, ABOVE THE FIRST OR GROUND FLOOR THE DENSE
 FILING MAY BE A LIVE LOAD ISSUE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]