| Notes |
| Date |
Text |
| 2007-10-23 10:45:00 | ***DENIED*** | | | | | | ALL PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED WITH THIS | | | SUBMITTAL. | | | | | | 1) RESPONSE LETTER INDICATES THAT FIRE ALARM SHOP | | | DRAWINGS WITH HEAD LOCATION HAS BEEN SUBMITTED. THIS IS | | | NOT INDICATED ON DRAWING INDEX AND CAN'T BE LOCATED | | | WITH THIS SUBMITTAL. RESPONSE #6 INDICATES SUBMITTAL OF | | | REVISED PLANS. PLEASE CORRELATE THIS INFORMATION. BASE | | | PLANS ARE REQUIRED TO SHOW LAYOUT OF FIRE PROTECTION | | | EQUIPMENT IN ADDITION TO SEPARATE SHOP DRAWINGS PRIOR | | | TO INSTALLATION. | | | | | | 2) NO SHOP DRAWINGS SUBMITTED ILLUSTRATING WALK IN | | | COOLERS. | | | | | | 3) FLAME SPREAD INFORMATION COULD NOT BE LOCATED. | | | | | | 4) OK | | | | | | 5) OK | | | | | | 6) FIRE ALARM LAYOUT CAN BE LOCATED ON POWER PLAN OF | | | ELECTRICAL SHEETS. CAN NOT FIND AT THIS TIME. | | | | | | 7) OK | | | | | | 8) OK | | | | | | NEW COMMENT: | | | | | | 1) IF FIRE ALARM IS PART OF THE SCOPE OF THIS WORK, | | | DUCT SMOKE DETECTORS SHALL BE WIRED TO THE SYSTEM, AND | | | INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|