Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-10-23 10:45:00***DENIED***
  
 ALL PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED WITH THIS
 SUBMITTAL.
  
 1) RESPONSE LETTER INDICATES THAT FIRE ALARM SHOP
 DRAWINGS WITH HEAD LOCATION HAS BEEN SUBMITTED. THIS IS
 NOT INDICATED ON DRAWING INDEX AND CAN'T BE LOCATED
 WITH THIS SUBMITTAL. RESPONSE #6 INDICATES SUBMITTAL OF
 REVISED PLANS. PLEASE CORRELATE THIS INFORMATION. BASE
 PLANS ARE REQUIRED TO SHOW LAYOUT OF FIRE PROTECTION
 EQUIPMENT IN ADDITION TO SEPARATE SHOP DRAWINGS PRIOR
 TO INSTALLATION.
  
 2) NO SHOP DRAWINGS SUBMITTED ILLUSTRATING WALK IN
 COOLERS.
  
 3) FLAME SPREAD INFORMATION COULD NOT BE LOCATED.
  
 4) OK
  
 5) OK
  
 6) FIRE ALARM LAYOUT CAN BE LOCATED ON POWER PLAN OF
 ELECTRICAL SHEETS. CAN NOT FIND AT THIS TIME.
  
 7) OK
  
 8) OK
  
 NEW COMMENT:
  
 1) IF FIRE ALARM IS PART OF THE SCOPE OF THIS WORK,
 DUCT SMOKE DETECTORS SHALL BE WIRED TO THE SYSTEM, AND
 INITIATE A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756