 *** REDLINED PLANS/PROVISO ***
  
 1) NOTE: AS IT IS THE UNDERSTANDING BY THIS OFFICE, A
 FIRE ALARM SYSTEM IS REQUIRED BY THE FIRE MARSHAL PER
 CODE AND A SYSTEM IS TO BE INSTALLED. REVIEW FOR
 LOCATIONS AND MINIMUM LEVELS FOR ADA COMPLIANCE PER FBC
 11.-4.28.1, .2 AND .3(4) WILL BE DONE UNDER THE
 SEPARATE PERMIT AND PLANS.
  
 THE BASE BUILDING BUILD OUT PLANS WILL BE REQUIRED TO
 BE REVISED TO SHOW ALL LOCATIONS AS REQUIRED PER FBC AS
 NOTED AND FS 633 FOR BASE BUILDING MINIMUM FIRE CODE
 DESIGNS.
 THESE LOCATIONS AND LEVELS HAVE NOT YET BEEN REVIEWED
 AND BASE PLANS MUST BE REVISED TO SHOW MINIMUM
 DESIGNS.
  
 **IF THERE ARE ANY QUESTIONS ON THE ABOVE, PLEASE
 CONTACT THIS OFFICE/REVIEWER TO GO OVER WHAT IS
 NEEDED.
  