Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop M
Sequence Number 2
Notes
Date Text
2007-08-20 15:49:09RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.
2007-08-16 15:51:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 ** THE FOLLOWING COMENTS ARE FOR THE MECHANICAL PLAN
 PAGE 3.1A **
  
 1) 5 SUPPLY AIR DUCTS (FLEX) STILL NEED TO BE SIZED,
 SEE YELLOW HIGH LIGHT ON PLAN.
  
 2) A/C EQUIPMENT LISTING SHOWS TWO AHU AS #1, PLEASE
 CORRECT.
  
 3) PLEASE SHOW AN EXHAUST FAN WITH CFM'S IN THE SMALL
 BATHROOM AT THE BACK OF THE BUILDING,SEE FBC MECH.
 403.2.
  
 4) ADD UP THE CFM'S AT EACH SUPPLY AIR GRILL TO AHU #1
 THEY EQUAL 5,000. THE EQUIPMENT LISTING STATES AHU #1
 ONLY SUPPLIES 3,000 CFM'S, PLEASE EXPLAIN WERE THE
 OTHER 2,000 CFM'S ARE COMING FROM.
  
 ** THE FOLLOWING COMMENTS ARE FOR THE KITCHEN HOOD
 PLANS **
  
 5) PAGE 1 OF 3 AND 3 OF 3 SHOWS AN EXISTING FIRE DAMPER
 IN THE EXHAUST GREASE DUCT THIS FIRE DAMPER WILL NEED
 TO BE REMOVED, PLEASE STATE SO ON PLAN, SEE FBC
 MECH.506.3.7 AND FIRE DAMPER MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS REGARDING
 GREASE DUCTS.
  
 6) PAGE 1 OF 1 HAS A NOTE THAT STATES " THE AIR
 VELOCITY THROUGH THE DUCT SHALL NOT BE LESS THAN 1,500
 FPM" AND THE FBC MECH. 506.3.4 STATES THE SAME. PAGE 3
 OF 3SHOWS EF-1 TO BE 5,620 CFM'S THE GREASE DUCT IS
 24X24, 4 SQ. FT., 4 X 1,500 = 6,000 PLEASE ADJUST FAN
 SPEED.
  
 7) SEE FBC MECH. 507.13.2 THE MINIMUM NET AIRFLOW FOR
 TYPE I HOODS USED FOR HEAVY-DUTY COOKING APPLIANCES
 SHALL BE DETERMINED AS FOLLOWS:WALL-MOUNTED CANOPY400
 CFM PER LINEAR FOOT OF HOOD. THE THREE HOODS EQUAL 26
 LINEAR FEET, 26 X 400 = 10,400 CFM'S, PLEASE ADJUST FAN
 SPEED.
  
 8) PAGE 3 OF 3 SHOWS THE EXISTING DRYWALL CHASE DOES
 NOT IN CLOSE THE BOTTOM CORNER OF THE GREASE DUCT, SEE
 FBC MECH. 506.3.10. PLEASE CORRECT.
  
 9) AS A FIRE DAMPER IS NOT APPROVED FOR A GREASE DUCT,
 THE DUCT WILL NEED TO COMPLY WITH FBC MECH. 506.3.10 OR
 THE EXCEPTION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].