| 2007-08-20 15:49:09 | RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD. |
| 2007-08-16 15:51:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER |
| | 1 CITY OF WEST PALM BEACH AMENDMENTS. |
| | |
| | *** DENIED *** |
| | ** THE FOLLOWING COMENTS ARE FOR THE MECHANICAL PLAN |
| | PAGE 3.1A ** |
| | |
| | 1) 5 SUPPLY AIR DUCTS (FLEX) STILL NEED TO BE SIZED, |
| | SEE YELLOW HIGH LIGHT ON PLAN. |
| | |
| | 2) A/C EQUIPMENT LISTING SHOWS TWO AHU AS #1, PLEASE |
| | CORRECT. |
| | |
| | 3) PLEASE SHOW AN EXHAUST FAN WITH CFM'S IN THE SMALL |
| | BATHROOM AT THE BACK OF THE BUILDING,SEE FBC MECH. |
| | 403.2. |
| | |
| | 4) ADD UP THE CFM'S AT EACH SUPPLY AIR GRILL TO AHU #1 |
| | THEY EQUAL 5,000. THE EQUIPMENT LISTING STATES AHU #1 |
| | ONLY SUPPLIES 3,000 CFM'S, PLEASE EXPLAIN WERE THE |
| | OTHER 2,000 CFM'S ARE COMING FROM. |
| | |
| | ** THE FOLLOWING COMMENTS ARE FOR THE KITCHEN HOOD |
| | PLANS ** |
| | |
| | 5) PAGE 1 OF 3 AND 3 OF 3 SHOWS AN EXISTING FIRE DAMPER |
| | IN THE EXHAUST GREASE DUCT THIS FIRE DAMPER WILL NEED |
| | TO BE REMOVED, PLEASE STATE SO ON PLAN, SEE FBC |
| | MECH.506.3.7 AND FIRE DAMPER MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS REGARDING |
| | GREASE DUCTS. |
| | |
| | 6) PAGE 1 OF 1 HAS A NOTE THAT STATES " THE AIR |
| | VELOCITY THROUGH THE DUCT SHALL NOT BE LESS THAN 1,500 |
| | FPM" AND THE FBC MECH. 506.3.4 STATES THE SAME. PAGE 3 |
| | OF 3SHOWS EF-1 TO BE 5,620 CFM'S THE GREASE DUCT IS |
| | 24X24, 4 SQ. FT., 4 X 1,500 = 6,000 PLEASE ADJUST FAN |
| | SPEED. |
| | |
| | 7) SEE FBC MECH. 507.13.2 THE MINIMUM NET AIRFLOW FOR |
| | TYPE I HOODS USED FOR HEAVY-DUTY COOKING APPLIANCES |
| | SHALL BE DETERMINED AS FOLLOWS:WALL-MOUNTED CANOPY400 |
| | CFM PER LINEAR FOOT OF HOOD. THE THREE HOODS EQUAL 26 |
| | LINEAR FEET, 26 X 400 = 10,400 CFM'S, PLEASE ADJUST FAN |
| | SPEED. |
| | |
| | 8) PAGE 3 OF 3 SHOWS THE EXISTING DRYWALL CHASE DOES |
| | NOT IN CLOSE THE BOTTOM CORNER OF THE GREASE DUCT, SEE |
| | FBC MECH. 506.3.10. PLEASE CORRECT. |
| | |
| | 9) AS A FIRE DAMPER IS NOT APPROVED FOR A GREASE DUCT, |
| | THE DUCT WILL NEED TO COMPLY WITH FBC MECH. 506.3.10 OR |
| | THE EXCEPTION. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL: [email protected]. |