Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-09-11 17:00:39*****UNSAT*****
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS TAKEN FROM THE
 PREVIOUS FIRE PLAN REVIEW CONDUCTED BY FIRE MARSHAL
 MIKE CARSILLO:
  
 02.PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER
 SYSTEM IS TO BE EXTENDED, HOWEVER THERE ARE NO FIRE
 SPRINKLER PLANS PROVIDED SHOWING SPRINKLER LAYOUT.
  
 06.ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 08.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW
 AWNING TO BE PROPOSED.
  
 09.PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON
 PAGE 2.0E.
  
 11.PLEASE EXPLAIN PURPOSE OF HANGING BEADS.WHAT
 MATERIAL AND WHAT FLAME SPEAD RATING.
  
 15.COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM
 EQUIPMENT WITHIN SPACE.PLEASE ADVISE.
  
 16.INFORMATION SHALL BE PROVIDED REGARDING ANY
 PROPOSED CANDLE USE.
  
 NEW COMMENT
  
 AA.ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 CLEMATIS STREET, DISPLAY THE NUMERICAL ADDRESS ON THE
 BUILDING.PLEASE BE ADVISED THAT THE ADDRESS NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722