Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-25 13:06:112007-08-25 13:06:11
  
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME MINOR NEW
 COMMENTS.
 MOST ITEMS WERE ADDRESSED AND PLANS ARE GENERALLY IN
 GOOD SHAPE. THERE ARE A FEW LIFE SAFETY COMMENTS
 HOWEVER THAT NEED TO BE ADDRESSED AT THIS TIME. SOME OF
 THE OTHER COMMENTS EVEN THOUGH MINOR IN NATURE SHOULD
 BE CORRECTED AT THIS TIME AS PLANS ARE COMING BACK FOR
 CORRECTIONS.
  
  
 1) NOTE: PLEASE SEE MINOR MISPRINT OF THE NEC , NFPA-70
 ON 2.2E. SHOWS 2002. SHOULD BE 2005 EDITION OF THE
 CODE.
  
 2) NOTE: PLEASE SEE THE COMPLETE AND TOTAL VALUE FOR
 SCOPE OF WORK HAS NOT BEEN ADJUSTED. THE INCREASE FROM
 110K TO 250K DOES NOT ACCURATELY DEPICT ALL LABOR,
 MATERIALS, EQUIPMENT, DESIGNS COST ETC AS REQUIRED AND
 STATED UNDER THE FBC ON PREVIOUS REVIEW.
 PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE.
 PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE AS
 REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR,
 EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES
 ARE OWNER SUPPLIED.
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SEE LOCATIONS FOR OVER RIDES SHOULD BE GONE
 OVER.
 THIS WAS ON PREVIOUS NOTE #5
 ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.2
  
 4) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR
 EMERGENCY/EXIT LIGHTING.
 THIS IS THE SAME NOTE AS SOME OF THESE FIXTURES DO NOT
 SEEM TO COMPLY
  
 5) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND
 MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9
 AND NEC 700.12F.
 PLEASE SEE THAT THIS NOTE REMAINS AS THERE ARE SEVERAL
 AREAS IN WHICH STILL NEED A BATTERY BACK UP FIXTURE OF
 SOME TYPE. FOR EXAMPLE, PLEASE SEE CORRIDOR OUTSIDE
 BATH ROOMS, KITCHEN CORRIDOR, DINING AREAS WHICH ALL
 REQUIRE A MINIMUM AMOUNT OF LIGHTING LEVELS UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-33.004
 FOR LIGHTING LEVELS.
  
 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN.
 FBC 106.3.5.1.2
 THIS IS GOING TO REQUIRE A FA SYSTEM (SEE BLDG AND FIRE
 COMMENTS) THEREFORE THE BASE BUILDING PLANS ARE
 REQUIRED TO INDICATE A BASE SYSTEM.
 THIS IS A NEW COMMENT AS INFORMATION FOR BUILDING AHS
 BECOME AVAILABLE DUE TO THE EXTENDED SCOPE OF WORK
 BEING DONE THROUGH-OUT BUILDING.
  
 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING
 WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS.
  
 8) NOTE: PLEASE SEE RISER SHOWS 100AMP BUS FOR PANEL
 *C* AND PANEL SCHEDULE SHOWS THIS AS 125AMPS> PLEASE
 CORRELATE AT THIS TIME.
  
 9) NOTE: PLEASE SEE THE RECORDED NOC WILL NEED TO BE
 RE-RECORDED BEFORE PICKING UP PERMIT AS IT HAS BECOME
 VOID PER FS 713.13(2).
 THIS IS ONLY NOTED AT THIS TIME BY REVIEWER.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]