| | *** DENIED 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME MINOR NEW |
| | COMMENTS. |
| | MOST ITEMS WERE ADDRESSED AND PLANS ARE GENERALLY IN |
| | GOOD SHAPE. THERE ARE A FEW LIFE SAFETY COMMENTS |
| | HOWEVER THAT NEED TO BE ADDRESSED AT THIS TIME. SOME OF |
| | THE OTHER COMMENTS EVEN THOUGH MINOR IN NATURE SHOULD |
| | BE CORRECTED AT THIS TIME AS PLANS ARE COMING BACK FOR |
| | CORRECTIONS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MINOR MISPRINT OF THE NEC , NFPA-70 |
| | ON 2.2E. SHOWS 2002. SHOULD BE 2005 EDITION OF THE |
| | CODE. |
| | |
| | 2) NOTE: PLEASE SEE THE COMPLETE AND TOTAL VALUE FOR |
| | SCOPE OF WORK HAS NOT BEEN ADJUSTED. THE INCREASE FROM |
| | 110K TO 250K DOES NOT ACCURATELY DEPICT ALL LABOR, |
| | MATERIALS, EQUIPMENT, DESIGNS COST ETC AS REQUIRED AND |
| | STATED UNDER THE FBC ON PREVIOUS REVIEW. |
| | PLEASE KNOW A VALUE MAY BE ASSESSED BY THIS OFFICE. |
| | PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| | WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE AS |
| | REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR, |
| | EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES |
| | ARE OWNER SUPPLIED. |
| | |
| | 3) NOTE: PLEASE SEE FBC CHAPTER 13. |
| | PLEASE SEE LOCATIONS FOR OVER RIDES SHOULD BE GONE |
| | OVER. |
| | THIS WAS ON PREVIOUS NOTE #5 |
| | ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3, |
| | 13-415.2 |
| | |
| | 4) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR |
| | EMERGENCY/EXIT LIGHTING. |
| | THIS IS THE SAME NOTE AS SOME OF THESE FIXTURES DO NOT |
| | SEEM TO COMPLY |
| | |
| | 5) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND |
| | MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9 |
| | AND NEC 700.12F. |
| | PLEASE SEE THAT THIS NOTE REMAINS AS THERE ARE SEVERAL |
| | AREAS IN WHICH STILL NEED A BATTERY BACK UP FIXTURE OF |
| | SOME TYPE. FOR EXAMPLE, PLEASE SEE CORRIDOR OUTSIDE |
| | BATH ROOMS, KITCHEN CORRIDOR, DINING AREAS WHICH ALL |
| | REQUIRE A MINIMUM AMOUNT OF LIGHTING LEVELS UNDER |
| | NORMAL AND EMERGENCY CONDITIONS. |
| | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 |
| | FOR LIGHTING LEVELS. |
| | |
| | 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| | SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. |
| | FBC 106.3.5.1.2 |
| | THIS IS GOING TO REQUIRE A FA SYSTEM (SEE BLDG AND FIRE |
| | COMMENTS) THEREFORE THE BASE BUILDING PLANS ARE |
| | REQUIRED TO INDICATE A BASE SYSTEM. |
| | THIS IS A NEW COMMENT AS INFORMATION FOR BUILDING AHS |
| | BECOME AVAILABLE DUE TO THE EXTENDED SCOPE OF WORK |
| | BEING DONE THROUGH-OUT BUILDING. |
| | |
| | 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING |
| | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. |
| | |
| | 8) NOTE: PLEASE SEE RISER SHOWS 100AMP BUS FOR PANEL |
| | *C* AND PANEL SCHEDULE SHOWS THIS AS 125AMPS> PLEASE |
| | CORRELATE AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE THE RECORDED NOC WILL NEED TO BE |
| | RE-RECORDED BEFORE PICKING UP PERMIT AS IT HAS BECOME |
| | VOID PER FS 713.13(2). |
| | THIS IS ONLY NOTED AT THIS TIME BY REVIEWER. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |