| Date |
Text |
| 2007-06-16 13:28:04 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, |
| | SIZED, AND APPROVED OR REJECTED BY ENVIRONMENTAL |
| | COMPLIANCE OFFICE. PLEASE CONTACT RODNEY COMPO, (561) |
| | 822-2272, [email protected] OR CALVIN WILLIAMS, (561) |
| | 822-2284 [email protected]. THEIR FAX NUMBER IS (561) |
| | 822-2287. THEIR DETERMINATION SHALL BE SUBMITTED WHEN |
| | THE PLANS ARE RESUBMITTED FOR REVIEW. ARTICLE III |
| | SECTION 90-24. |
| | |
| | 2. SHTS 3.0P & 3.2A THE DISHWASHER SHALL CONNECT TO THE |
| | SANT. SYSTEM, NOT THE GREASE SYSTEM PER ARTICLE III |
| | SECTION 90-24(7)(F). |
| | |
| | 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR A GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO & |
| | INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS |
| | APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE |
| | PIPE SIZES. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | - NOT ALL PIPE SIZES SHOWN. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE |
| | BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE. |
| | PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS |
| | SUBMITTAL. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN |
| | SUBMITTED. |
| | |
| | 4. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN |
| | THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING |
| | PER SECTION 404.3. |
| | |
| | 5. SHTS A1.1 1 OF 1 & A1.2 TITLE BLOCK INDICATES METRO |
| | DESIGN GROUP. A CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED IN THE TITLE BLOCK. THIS COMMENT HAS BEEN |
| | ONGOING FOR AT LEAST A FEW YEARS AND IF THE DESIGN |
| | PROFESSIONALS CONTINUE TO USE METRO DESIGN GROUP ON |
| | THEIR PLANS WITHOUT A CERTIFICATE OF AUTHORIZATION |
| | PLANS WILL BE RETAINED AND SENT TO THE STATE FOR |
| | REVIEW. PLEASE PUT THE CERTIFICATE OF AUTHORIZATION IN |
| | THE TITLE BLOCK. FAC 61G1-16.004(2), 61G15-23.002 & FS |
| | 481.219, 481.2055, 471.025. |
| | |
| | 6. SUBMIT A WATER RISER DIAGRAM SHOW ALL PIPE SIZES, |
| | VALVES, REQUIRED WATER HAMMER ARRESTORS ETC. SECTION |
| | 106.3.5.1.3(3)(8)(10)(13). |
| | |
| | 7. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO |
| | THE SPACE. PLEASE INDICATE IF THERE IS AN EXISTING |
| | BACKFLOW ON THE PLANS. SECTION 608.13.2. |
| | |
| | 8. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE |
| | INDICATED METHOD. SECTION 607.3.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |