Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-16 13:28:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED,
 SIZED, AND APPROVED OR REJECTED BY ENVIRONMENTAL
 COMPLIANCE OFFICE. PLEASE CONTACT RODNEY COMPO, (561)
 822-2272, [email protected] OR CALVIN WILLIAMS, (561)
 822-2284 [email protected]. THEIR FAX NUMBER IS (561)
 822-2287. THEIR DETERMINATION SHALL BE SUBMITTED WHEN
 THE PLANS ARE RESUBMITTED FOR REVIEW. ARTICLE III
 SECTION 90-24.
  
 2. SHTS 3.0P & 3.2A THE DISHWASHER SHALL CONNECT TO THE
 SANT. SYSTEM, NOT THE GREASE SYSTEM PER ARTICLE III
 SECTION 90-24(7)(F).
  
 3. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING
 INFORMATION IS REQUIRED FOR A GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO &
 INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS
 APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE
 PIPE SIZES.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - NOT ALL PIPE SIZES SHOWN.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE
 BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE.
 PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS
 SUBMITTAL.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN
 SUBMITTED.
  
 4. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN
 THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING
 PER SECTION 404.3.
  
 5. SHTS A1.1 1 OF 1 & A1.2 TITLE BLOCK INDICATES METRO
 DESIGN GROUP. A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED IN THE TITLE BLOCK. THIS COMMENT HAS BEEN
 ONGOING FOR AT LEAST A FEW YEARS AND IF THE DESIGN
 PROFESSIONALS CONTINUE TO USE METRO DESIGN GROUP ON
 THEIR PLANS WITHOUT A CERTIFICATE OF AUTHORIZATION
 PLANS WILL BE RETAINED AND SENT TO THE STATE FOR
 REVIEW. PLEASE PUT THE CERTIFICATE OF AUTHORIZATION IN
 THE TITLE BLOCK. FAC 61G1-16.004(2), 61G15-23.002 & FS
 481.219, 481.2055, 471.025.
  
 6. SUBMIT A WATER RISER DIAGRAM SHOW ALL PIPE SIZES,
 VALVES, REQUIRED WATER HAMMER ARRESTORS ETC. SECTION
 106.3.5.1.3(3)(8)(10)(13).
  
 7. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE SPACE. PLEASE INDICATE IF THERE IS AN EXISTING
 BACKFLOW ON THE PLANS. SECTION 608.13.2.
  
 8. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE
 INDICATED METHOD. SECTION 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved