| Plan Review Notes For Permit 07050385 |
| Permit Number |
07050385 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-01 09:23:28 | *** DENIED *** | | | 1) SEE MECHANICAL PLAN, SHOWS ADDRESS AS 220 CLEMATIS | | | PLEASE CORRECT TO 225. | | | | | | 2) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN, 12 SUPPLY | | | AIR DUCTS NEED TO BE SIZED, ONE SUPPLY AIR DUCT IS NOT | | | SHOWN ONLY THE GRILL IS, AND TWO SUPPLY AIR GRILLS ARE | | | NOT SHOWING THE CFM'S. PLEASE CORRECT. | | | | | | 3) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST | | | FANS. | | | | | | 4) PLEASE SHOW THE RETURN AIR GRILLS OR HOW THE RETURN | | | AIR IS GETTING TO THE AHU'S (ONLY ONE 48X24 RETURN AIR | | | TRANSFER GRILL IS SHOWING AT THIS TIME). | | | | | | 5) ONLY ONE AHU IS SHOWING A OUTSIDE AIR DUCT PLEASE | | | PROVIDE OUTSIDE AIR CALCULATIONS, SEE 2004 FBC/M | | | 401.2. | | | | | | 6) SEE AHU 1 IS SUPPLYING 4,600 CFM'S, MOST UNITS | | | SUPPLY 400 CFM'S PER TON, PLEASE CORRECT OR PROVIDE | | | MORE INFORMATION REGARDING THIS UNIT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|