Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-01 09:23:28*** DENIED ***
 1) SEE MECHANICAL PLAN, SHOWS ADDRESS AS 220 CLEMATIS
 PLEASE CORRECT TO 225.
  
 2) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLAN, 12 SUPPLY
 AIR DUCTS NEED TO BE SIZED, ONE SUPPLY AIR DUCT IS NOT
 SHOWN ONLY THE GRILL IS, AND TWO SUPPLY AIR GRILLS ARE
 NOT SHOWING THE CFM'S. PLEASE CORRECT.
  
 3) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST
 FANS.
  
 4) PLEASE SHOW THE RETURN AIR GRILLS OR HOW THE RETURN
 AIR IS GETTING TO THE AHU'S (ONLY ONE 48X24 RETURN AIR
 TRANSFER GRILL IS SHOWING AT THIS TIME).
  
 5) ONLY ONE AHU IS SHOWING A OUTSIDE AIR DUCT PLEASE
 PROVIDE OUTSIDE AIR CALCULATIONS, SEE 2004 FBC/M
 401.2.
  
 6) SEE AHU 1 IS SUPPLYING 4,600 CFM'S, MOST UNITS
 SUPPLY 400 CFM'S PER TON, PLEASE CORRECT OR PROVIDE
 MORE INFORMATION REGARDING THIS UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.