| 2007-06-16 13:49:02 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR A GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO & |
| | INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS |
| | APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE |
| | PIPE SIZES. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | - NOT ALL PIPE SIZES SHOWN. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE |
| | BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE. |
| | PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS |
| | SUBMITTAL. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN |
| | SUBMITTED. |
| | |
| | 2. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN |
| | THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING |
| | PER SECTION 404.3. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |