2007-06-16 13:49:02DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT 3.2A GAS RISER DIAGRAM. THE FOLLOWING
 INFORMATION IS REQUIRED FOR A GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 - MANY PIPE SIZES ARE NOT SHOWN. SHOW PIPE SIZE UP TO &
 INCLUDING THE SHUT OFF VALVE. INDICATE THE GAS
 APPLIANCE LOCATION ON THE RISER DIAGRAM TO DETERMINE
 PIPE SIZES.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - NOT ALL PIPE SIZES SHOWN.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 - THE BTU LOAD SHOWN ON THE OVEN DOES NOT REFLECT THE
 BTU LOAD INDICATED ON THE GAS LOAD CALCULATIONS TABLE.
 PLEASE CLARIFY. INDICATE THE MODEL NUMBER FOR EACH GAS
 SUBMITTAL.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 - THE MANUF. SHEETS FOR THE CANDY STOVE HAVE NOT BEEN
 SUBMITTED.
  
 2. SHT 3.2A GAS RISER DIAGRAM. THE UNION INDICATED IN
 THE CEILING IS NOT APPROVED. NO UNIONS IN THE CEILING
 PER SECTION 404.3.
  