2007-06-14 11:52:371. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. PLANS INDICATE THAT THE EXISTING FIRE SPRINKLER
 SYSTEM IS TO BE EXTENDED INTO THIS SPACE. NO FIRE
 SPRINKLER PLANS PROVIDED WITH DRAWINGS.
  
 3. EXITS SHALL BE PROVIDED DURING CONSTRUCTION RELATED
 ACTIVITIES.
  
 4. PLEASE ILLUSTATE ON THE PLANS WHAT IS PRESENT BEYOND
 THE EXIT DOORS. (EXIT DISCHARGE LOCATIONS)
  
 5. SEPERATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 6. ALL WALK-IN COOLERS AND FREEZERS ARE TO BE FIRE
 SPRINKLER PROTECTED.
  
 7. THERE DOES NOT APPEAR TO ENOUGH DIRECTIONAL EXIT
 SIGNS OR EMERGENCY LIGHTS DISPLAYED ON THE REFLECTED
 CEILING PLAN.
  
 8. PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE NEW
 AWNING BEING PROPOSED.
  
 9. PLEASE EXPLAIN PURPOSE OF LCP KEYPADS SHOWN ON PAGE
 2.0E.
  
 10. PLEASE PROVIDE MORE DETAILS ON WHAT FIRE ALARM
 MONITORING EQUIPMENT THAT THE FIRE SPRINKLER SYSTEM
 WILL BE CONNECTED TO. WHERE IS IT CONNECTED AND TO
 WHOM.
  
 11. PLEASE EXPLAIN PURPOSE OF HANGING BEADS. WHAT
 MATERIAL AND WHAT FLAME SPREAD RATING.
  
 12. COULD LOCATE ONLY ONE FIRE EXTINGUISHER ON PAGE
 1.0A. PLEASE INDICATE OTHERS.
  
 13. PLEASE INDICATE WHAT THE CROOKED LINES ON PAGE 1.0A
 REPRESENT.
  
 14. OCCUPANT LOAD WILL BE DETERMINED BY FIRE RESCUE AND
 WILL BE REQUIRED TO BE POSTED.
  
 15. COULD NOT LOCATE ANY EXISTING OR NEW FIRE ALARM
 EQUIPMENT WITHIN SPACE. PLEASE ADVISE.
  
 16. INFORMATION SHALL BE PROVIDED REGARDING ANY
 PROPOSED CANDLE USE.
  