| 2007-06-05 08:49:06 | ** UNSAT ** |
| | |
| | *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR |
| | CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| | YET ABLE TO BE MADE. |
| | |
| | 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE |
| | UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER |
| | 8TH, 2006. |
| | 2004 FBC W/2006 REVISIONS. (SHOWS 2006 REVISIONS TO THE |
| | 2002 NEC) |
| | 2005 NFPA-70 (NEC)> |
| | 2002 NFPA-72 (MISPRINT NFPI) |
| | 2003 NFPA-101 (OK). |
| | |
| | 2) NOTE: PLEASE SEE THE ADDRESS ON PLAN TITLE BLOCKS |
| | DOES NOT COORDINATE WITH THE APPLIED ADDRESS ON THE |
| | PERMIT APPLICATION AND DOES NOT COORDINATE WITH THE |
| | ACTUAL SITE ADDRESS. |
| | PLEASE ADJUST. |
| | FAC 61G1-16.004 |
| | |
| | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE |
| | SCOPE OF WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE |
| | AS REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR, |
| | EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES |
| | ARE OWNER SUPPLIED. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE |
| | ALSO BE SURE TO GO OVER CIRCUITS AS THERE ARE SEVERAL |
| | CIRCUITS INDICATED ON PLANS WHICH SERVE MORE THAN ONE |
| | ITEM OR AREA. (EXAMPLE B-17, B-36,LCP CIRCUITS ETC). |
| | FBC 106.3.5.1.2, 408.4 ETC. |
| | |
| | 5) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THERE |
| | ARE SEVERAL ITEMS *QUOTING* CODE REQUIRED ITEMS WHICH |
| | NEED TO BE SHOWN IN DETAIL. |
| | PLEASE SEE MISSING THE OVER RIDES AT THE LOCATION ON |
| | PLANS. |
| | PLEASE SEE THE MISSING CONTROLS FOR SEPARATE SPACES. |
| | PLEASE SEE MISSING DETAILS FOR DEVICES AND SYSTEM. |
| | PLEASE SEE THE FIXTURE SCHEDULE IS NOT COMPLETE, ONLY |
| | 12 OF THE 14 INDICATED FIXTURES CONTAINS ANY |
| | INFORMATION FOR TYPE, WATTAGE, ETC. |
| | PLEASE SEE NO INFORMATION FOR PERFORMANCE OF LIGHTING. |
| | (SCHEDULING INDICATES 6AM TO MIDNIGHT). |
| | |
| | ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3, |
| | 13-415.2 |
| | |
| | 6) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR |
| | EMERGENCY/EXIT LIGHTING. |
| | |
| | 7) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND |
| | MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9 |
| | AND NEC 700.12F. |
| | |
| | 8) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES PER |
| | 210.62 AND LOADS TO BE COMPLETED PER 220.43A AND |
| | 220.14G. |
| | |
| | 9) NOTE: PLEASE SEE MISSING THE REQUIRED GFI PROTECTION |
| | FOR ALL RECEPTACLES SERVING KITCHEN AREAS PER 210.8B2. |
| | PROTECTION REQUIRED TO BE SHOWN AT THE DEVICE OR ON |
| | PANEL SCHEDULE. (MAY NOT QUOTE THE REQUIRED CODE |
| | REQUIREMENT IN LIEU OF SHOWING THE DETAIL FOR THIS) |
| | |
| | 10) NOTE: PLEASE SEE CLARIFY NEW OR EXISTING GFI |
| | RECEPTACLES REQUIRED PER 210.63, 210.8B3 |
| | |
| | 11) NOTE: PLEASE INDICATE THE LOCATION OF THE SERVICE |
| | ON PLANS. |
| | 110.26, 408.7 |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING |
| | METHODS AFTER THE FIRST MEANS OF DISCONNECT. 250.110, |
| | 250.24, 250.122 ETC. |
| | PLANS INDICATE A NOTE FOR A FLOATING NEUTRAL HOWEVER NO |
| | EQUIPMENT GROUNDING CONDUCTORS ARE SHOWN INSTALLED? |
| | |
| | 13) NOTE: PLEASE SEE THE RISER CONDUCTORS FOR PANEL *B* |
| | DIFFER FROM THE PANEL *A* SCHEDULE FOR THE SAME |
| | CONDUCTORS. |
| | PLEASE COORDINATE. |
| | 240.4, 310.16 |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 14) NOTE: PLEASE CLARIFY THE *DOUBLE TUB* BEING SHOWN |
| | FOR THE LIGHTING PANEL WHEN THE LIGHTING PANEL ONLY |
| | INDICATES 12 CIRCUITS. |
| | |
| | 15) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON 2.2EWHICH |
| | IS SHOWN ON THE PAGE WITH OUT GOING TO ANYTHING? FBC |
| | 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEEANY PLUMB REVIEW COMMENTS FOR ANY |
| | STAMPING OF PLANS FROM THE DIVISIONS OF HOTELS AND |
| | RESTAURANT MANG. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-05 07:02:44 | IN ELEC FOR REVIEW. |