Plan Review Notes
Plan Review Notes For Permit 07050385
Permit Number 07050385
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-05 08:49:06** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE
 UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER
 8TH, 2006.
 2004 FBC W/2006 REVISIONS. (SHOWS 2006 REVISIONS TO THE
 2002 NEC)
 2005 NFPA-70 (NEC)>
 2002 NFPA-72 (MISPRINT NFPI)
 2003 NFPA-101 (OK).
  
 2) NOTE: PLEASE SEE THE ADDRESS ON PLAN TITLE BLOCKS
 DOES NOT COORDINATE WITH THE APPLIED ADDRESS ON THE
 PERMIT APPLICATION AND DOES NOT COORDINATE WITH THE
 ACTUAL SITE ADDRESS.
 PLEASE ADJUST.
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE COMPLETE
 SCOPE OF WORK AS SHOWN SEEMS LOW. PLEASE SEE THIS VALUE
 AS REQUIRED PER THE FBC 108.3 SHALL INCLUDE ALL LABOR,
 EQUIPMENT AND MATERIALS EVEN IF ANY EQUIPMENT/SUPPLIES
 ARE OWNER SUPPLIED.
  
 4) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SUBMITTED. PLEASE
 ALSO BE SURE TO GO OVER CIRCUITS AS THERE ARE SEVERAL
 CIRCUITS INDICATED ON PLANS WHICH SERVE MORE THAN ONE
 ITEM OR AREA. (EXAMPLE B-17, B-36,LCP CIRCUITS ETC).
 FBC 106.3.5.1.2, 408.4 ETC.
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE THERE
 ARE SEVERAL ITEMS *QUOTING* CODE REQUIRED ITEMS WHICH
 NEED TO BE SHOWN IN DETAIL.
 PLEASE SEE MISSING THE OVER RIDES AT THE LOCATION ON
 PLANS.
 PLEASE SEE THE MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE SEE MISSING DETAILS FOR DEVICES AND SYSTEM.
 PLEASE SEE THE FIXTURE SCHEDULE IS NOT COMPLETE, ONLY
 12 OF THE 14 INDICATED FIXTURES CONTAINS ANY
 INFORMATION FOR TYPE, WATTAGE, ETC.
 PLEASE SEE NO INFORMATION FOR PERFORMANCE OF LIGHTING.
 (SCHEDULING INDICATES 6AM TO MIDNIGHT).
  
 ** PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3,
 13-415.2
  
 6) NOTE: PLEASE SEE MISSING CIRCUITING PER 700.12FFOR
 EMERGENCY/EXIT LIGHTING.
  
 7) NOTE: PLEASE SEE MISSING MINIMUM EGRESS LIGHTING AND
 MINIMUM LEVELS PER THE LIFE SAFETY CODE 101, 7.8, 7.9
 AND NEC 700.12F.
  
 8) NOTE: PLEASE SEE MISSING WINDOW RECEPTACLES PER
 210.62 AND LOADS TO BE COMPLETED PER 220.43A AND
 220.14G.
  
 9) NOTE: PLEASE SEE MISSING THE REQUIRED GFI PROTECTION
 FOR ALL RECEPTACLES SERVING KITCHEN AREAS PER 210.8B2.
 PROTECTION REQUIRED TO BE SHOWN AT THE DEVICE OR ON
 PANEL SCHEDULE. (MAY NOT QUOTE THE REQUIRED CODE
 REQUIREMENT IN LIEU OF SHOWING THE DETAIL FOR THIS)
  
 10) NOTE: PLEASE SEE CLARIFY NEW OR EXISTING GFI
 RECEPTACLES REQUIRED PER 210.63, 210.8B3
  
 11) NOTE: PLEASE INDICATE THE LOCATION OF THE SERVICE
 ON PLANS.
 110.26, 408.7
 FBC 106.1.2
  
 12) NOTE: PLEASE INDICATE THE EQUIPMENT GROUNDING
 METHODS AFTER THE FIRST MEANS OF DISCONNECT. 250.110,
 250.24, 250.122 ETC.
 PLANS INDICATE A NOTE FOR A FLOATING NEUTRAL HOWEVER NO
 EQUIPMENT GROUNDING CONDUCTORS ARE SHOWN INSTALLED?
  
 13) NOTE: PLEASE SEE THE RISER CONDUCTORS FOR PANEL *B*
 DIFFER FROM THE PANEL *A* SCHEDULE FOR THE SAME
 CONDUCTORS.
 PLEASE COORDINATE.
 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.2
  
 14) NOTE: PLEASE CLARIFY THE *DOUBLE TUB* BEING SHOWN
 FOR THE LIGHTING PANEL WHEN THE LIGHTING PANEL ONLY
 INDICATES 12 CIRCUITS.
  
 15) NOTE: PLEASE CLARIFY THE LOAD SHOWN ON 2.2EWHICH
 IS SHOWN ON THE PAGE WITH OUT GOING TO ANYTHING? FBC
 106.1.2
  
 16) NOTE: PLEASE SEEANY PLUMB REVIEW COMMENTS FOR ANY
 STAMPING OF PLANS FROM THE DIVISIONS OF HOTELS AND
 RESTAURANT MANG.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-05 07:02:44IN ELEC FOR REVIEW.