2007-06-19 11:26:08BUILDING PLAN REVIEW
 PERMIT: 07050385
 ADD: 225 CLEMATIS ST.
 CONT: CASTLE FLORIDA BUILDING CORP.
 TEL: (561)272-1207
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COVERSHEET UNDER GENERAL NOTES, PLEASE CORRECT THE
 FOLLOWING, PLANS SUBMITTED AFTER DEC.8, 2006 WERE TO BE
 DESIGNED TO THE 2004 FBC WITH 2006 REVISIONS. THIS ALSO
 HOLDS TRUE FOR THEEXISTING BUILDING CODE, FLORIDA
 ACCESSIBILITY CHAPTER 11AND ENERGY CHAPTER 13.
  
 4)THE COVER SHEET STATES THIS IS A III-B BUILDING.
 PLEASE PROVIDE CALCULATION FOR AREA INCREASES. 110.2*
 W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICHTHE PROJECT WAS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 THIS IS THE TOTAL SQUAREFOOTAGE FOR THE FIRST
 FLOOR AND THE HEIGTH IN FLOORS.
 NOTE HEIGHT NOR AREA INCREASES CAN NOT BE TAKEN
 UNTIL THE TOTAL BUILDING IS FIRE SPRINKLED!!!!!! D) IF
 AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED, E)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT.
 G) NUMBER OF FLOORS
 H) SQ. FT. FOOTPRINT
 I) SQ. FT. UNDER ROOF (TOTAL)
  
 5)SHEET 1.0A INDICATES A NEW FRONT ROLLING OR
 SWINGING GLASS DOOR SYSTEMWITH A CLEAR SPAN OF
 38'-0".ACENTER COLUMN REMOVED AND A30" SECTION OF
 BEARING WALL ALSO REMOVED TO EXSPAN THE OPENING FROM
 25' TO 38'. PLEASE PROVIDE ADDITIONAL STRUCTURAL PLANS
 AS HOW THE 2ND FLOOR LOADS, GRAVITY LOADS WILL BE
 CARRIED WITH THE REMOVAL AND RE-ORIENTATION OF COLUMN.
  
 6) 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTIONDRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. NEGATIVE PRESSURES ARE
 TAKEN FROM THE ROOF LEVEL OF BUILDING!
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) ) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) SWING DOORS, FRONT ENTRY DOOR
 B) MULLIONS- THE NOA SUBMITTED FOR FIXED SINGLE IMPACT
 WINDOWS CONFIGURATION "O"
  
 10)PLANS INDICATE THE USE OF 7'"X7" FIXED INSULATED
 GLASS,ON AN INTERIOR WALL, PLEASE PROVIDE THE
 MANUFACTURERS SPEC.
  
 11)DOORS 2,4,6,7,8& 9 ALL ARE MISSING THE 18" ON THE
 LATCH SIDE OF DOOR.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH IN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 12)11-5.1 INDICATE COMPLIANCE WITH 5% OF SEATING
 SHALL BE ACCESSIBLE.
  
 13) COVERSHEETINDICATES FLAME SPREAD AND SMOKE
 DEVELOPMENT BUT NO INFORMATION AS TO WHAT TYPE OF
 MATERIALS WILL BE USED ON THE WALLS? PLEASE PROVIDE THE
 FLAME SPREAD AND SMOKE DEVELOPMENT RATINGS.
  
 14)PLEASE CORRECT THE ADDRESS ON THE PLANS, THE
 LOCATION FOR THE PROJECT ACCORDING TOTHE PLAN IS 220
 CLEMATIS ST.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II