Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop E
Sequence Number 8
Notes
Date Text
2008-12-23 09:22:36** DENIED/PASSED REVISIONS**
  
 SEE LIST BELOW AS THERE ARE SHEETS SUBMITTED WHICH
 CONTAIN NOTES FOR CORRECTIONS.
 OTHER SHEETS SUBMITTED ARE OK AND CONTAIN ELECTRICAL
 REVIEW STAMPS.
  
 1) NOTE: SHEETS E105,106,109,112,115 NOW ALL CONTAIN
 NEW CAMERA SYSTEM. THIS WAS NOT PART OF THE BASE
 BUILDING PLANS. TO DATE ONLY ONE LOW VOLTAGE PERMIT HAS
 BEEN APPLIED FOR WHICH IS FOR BUILDING AUTOMATION
 SYSTEM. NO PERMITS HAVE BEEN APPLIED FOR PHONE, DATA
 CATV ETC.
 ANY CAMERA SYSTEM NOW PROPOSED WILL ALSO BE REQUIRED TO
 BE UNDER SEPARATE PERMIT, PLANS AND FEES.
 PLEASE SEE FBC 1019.1.2 AS MANY OF THE CAMERAS SHOWN
 ARE IN THE VERTICAL EXIT AREAS. THESE ARE NOT PERMITTED
 IN THE EGRESS STAIRS.
  
 2) NOTE: PLEASE SEE SHEET E1.12 AS THE REVISION DATE
 SHOWN FOR REV # 16 IS 9/5/08 YET THE REVISION #17 IS
 BEFORE #16 WITH A DATE OF 7/28/08. THIS MUST BE A
 MISPRINT OF SOME TYPE. THIS SHOULD BE REVERSED.
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  