| 2008-03-22 12:31:17 | REVIEW #: 4TH |
| | ACTION: TEMP FAIL |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | NOTE: THESE COMMENTS DO NOT CORRESPOND DIRECTLY WITH |
| | PREVIOUS REVIEW COMMENTS BUT THEY REPRESENT UNRESOLVED |
| | ISSUES FROM PREVIOUS REVIEW COMMENTS. ALL OTHER |
| | PREVIOUS REVIEW COMMENTS AND ISSUES HAVE BEEN |
| | RESOLVED. |
| | |
| | 1. THE PREVIOUSLY INDICATED 2,000 GALLON FUEL STORAGE |
| | TANK HAS BEEN MARKED AS FUTURE TO BE DONE UNDER |
| | SEPARATE PERMIT. HOWEVER, WHERE THE PLANS PREVIOUSLY |
| | CALLED FOR A 250 GALLON DAY TANK IN THE GENERATOR ROOM, |
| | THE GENERATOR SPECS, VIA A HAND-WRITTEN NOTE, CALL FOR |
| | A 600 GALLON SUB-BASE FUEL TANK. AS WAS STATED MULTIPLE |
| | TIMES IN PREVIOUS REVIEWS, ABOVE GROUND FUEL STORAGE |
| | TANKS IN EXCESS OF 550 GALLONS ARE REQUIRED TO HAVE |
| | DERM APPROVAL. NO DOCUMENTATION OF SUCH APPROVAL HAS |
| | BEEN PROVIDED. |
| | |
| | 2. THE INCORRECT VERSION OF ENERGY CALCULATIONS HAVE |
| | BEEN RESUBMITTED AS STATED IN ELECTRICAL PLAN REVIEW |
| | COMMENTS DATED 3/8/08. PLEASE RESUBMIT ON CORRECT FORM |
| | IN ACCORDANCE WITH FBCB 13-400.3.A. THIS PERMIT MAY NOT |
| | BE ISSUED PRIOR TO SATISFACTION OF THIS REQUIREMENT IN |
| | ACCORDANCE WITH FBCB 13-103.3. |
| | |
| | THE MECHANICAL PLANS HAVE BEEN REVIEWED AND STAMPED. |
| | THE REVIEW STATUS WILL BE IN A TEMPORARY FAIL STATUS |
| | PENDING CORRECTION OF THE ABOVE LISTED ITEMS. PLEASE |
| | CONTACT THIS OFFICE TO MAKE ARRANGEMENTS TO CORRECT |
| | THESE ITEMS SO THE PERMIT CAN BE ISSUED. |
| | |