| 2008-03-08 22:33:56 | ** DENIED REVIEW ** |
| | |
| | ***TEMPORARY FAILED STATUS *** |
| | |
| | ** ALL THREE SETS OF ELECTRICAL PLANS WERE STAMPED. |
| | |
| | 1) NOTE: PLEASE SEE THE VERSION OF ENERGY CALCULATIONS |
| | NEEDS TO MEET 13-400.3.A WHICH IS VERSION 2.5.THE |
| | SUBMITTED VERSION 3.0 IS NOT ADOPTED BY THE FBC. PLEASE |
| | TRANSFER INFORMATION INTO 2.5 AND SUBMIT. |
| | THIS REVIEWER HAS PERSONALLY SPOKEN WITH MR. MO MADANI |
| | WITH THE DEPARTMENT OF COMMUNITY AFFAIRS/FLORIDA |
| | BUILDING COMMISSION. |
| | THE ADDITIONAL WATTAGE FIGURED INTO CALCULATIONS BY THE |
| | NOTE ADDED TO COVER SHEET NEED NOT BE IN CALCULATIONS. |
| | FOR EXAMPLE: THE ADDITIONAL PARKING LOT FIXTURE (22 |
| | INSTEAD OF 21) AND 9 ADDITIONAL *J* FIXTURES (36 |
| | INSTEAD OF 29) ON THE IDR FOR EXTERIOR LIGHTING. |
| | THESE DO NOT NEED TO PART OF A RE-SUB AS LONG AS THERE |
| | ARE NO COMMENTS FROM OTHER TRADES.THIS IS STILL |
| | PENDING ANY CORRECTIONS OR INFORMATION NEEDED BY THE |
| | MECHANICAL OR BUILDING REVIEWER OF THESE SAME |
| | CALCULATIONS. |
| | |
| | 2) NOTE: PLEASE KNOW AS FOR INFORMATIONAL PURPOSE AND |
| | TO PERHAPS HELP IN THE ISSUANCE OF PERMIT. THE PLANS |
| | WERE REVISED TO REMOVE THE ON-SITE 2000 GALLON DIESEL |
| | TANK AND MENTIONS WILL BE DONE AT LATER DATE UNDER |
| | SEPARATE PERMIT HOWEVER THE PLANS STILL SHOW A 600 |
| | GALLON TANK WHICH DOES REQUIRE REVIEW AND STAMPED PLANS |
| | FROM DERM. (DEPARTMENT OF ENVIRONMENTAL RESOURCE |
| | MANAGEMENT). |
| | THIS IS GIVEN FOR INFORMATION AND WILL BE NOTED IN |
| | MECHANICAL REVIEW. |
| | IF SHEETS ARE BROUGHT IN BEFORE MECHANICAL REVIEW THIS |
| | MAY AVOID A FAIL FROM THE MECHANICAL REVIEW. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |