Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop M
Sequence Number 3
Notes
Date Text
2008-01-19 10:51:29REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS.
  
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 4: OK
  
 5. THERE IS AN 8 INCH ROUND BRANCH DUCT PENETRATING THE
 WALL BETWEEN LOBBY 1-115 AND DATA CLOSET 1-116.FIRE
 AND SMOKE DAMPER IS REQUIRED AT THIS DUCT PENETRATION
 IN ACCORDANCE WITH FBC, M 607.5.3 AND 607.5.4. ALSO,
 THIS DUCT CONTINUES AND PENETRATES ABOVE DOUBLE DOORS
 AT THE SOUTHEAST END OF CORRIDOR 1-159. THERE IS A FIRE
 DAMPER AT THIS LOCATION BUT A SMOKE DAMPER IS ALSO
 REQUIRED IN ACCORDANCE WITH FBC, M 607.5.4.
  
 6 THROUGH 25: OK
  
 A AND B: SUBMITTAL PACKAGE INDICATES PROPOSED OUTDOOR
 ABOVE GROUND FUEL TANK IS TO BE 2,000 GALLONS. AS
 STATED IN PREVIOUS REVIEW, ABOVE GROUND FUEL STORAGE
 TANKS >550 GALLONS REQUIRE PRIOR APPROVAL BY PALM BEACH
 COUNTY DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT
 (DERM). FOR MORE INFORMATION ON THIS APPROVAL PROCESS
 PLEASE CONTACT DERM AT 561-233-2400 OR AT:
 WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP
  
 NO INFORMATION WAS PROVIDED REGARDING 250 GALLON DAY
 TANK SHOWN ON PG E2.01 DETAIL #1. THE FOLLOWING ARE
 EXAMPLES OF REQUIREMENTS WHICH SHALL BE DEMONSTRATED
 PRIOR TO PERMIT:
  
 -FUEL TANKS WITHIN STRUCTURES SHALL BE PROVIDED WITH
 SPILL CONTAINMENT CONSISTING OF EITHER A WALL, A CURB,
 OR A DIKE HAVING A CAPACITY AT LEAST EQUAL TO THAT OF
 THE LARGEST SURROUNDED TANK IN ACCORDANCE WITH NFPA
 37-02 SECTION 6.3.2.4. SHOW COMPLIANCE WITH THIS
 SECTION.
  
 -VENT PIPING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 30-00 CHAPTER 3.
  
 -FUEL PIPING, VALVES AND FITTINGS SHALL BE IN
 ACCORDANCE WITH NFPA 37-02 SECTION 6.8 AND NFPA 30-00
 CHAPTER 3 FOR INDOOR AND OUTDOOR TANKS.
  
 CODES REFERENCED:
 FBC, MECHANICAL 2004 SECTION 915 ENGINE AND GAS
 TURBINE-POWERED EQUIPMENT AND APPLIANCES
 NFPA 37-02 STANDARD FOR THE INSTALLATION AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES NFPA
 30-00 FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE
  
 DEMONSTRATE COMPLIANCE WITH THE ABOVE REQUIREMENTS
 PRIOR TO PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]