Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-01 15:25:432008-1-01 15:25:43
  
 *** DENIED REVIEW ***
  
 THIS IS THE THIRD REVIEW FOR PROPOSED BUILDING; HOWEVER
 THIS IS ONLY FIRST REVIEW UNDER PERMIT APPLICATION.
 PERMIT WAS APPLIED FOR ON DECEMBER 20TH, 2007.
  
 ** A CONDITION KNOWN AS A *PROVISO* MAY BE GRANTED FOR
 SOME ITEMS BELOW AND ARE NOTED AS SUCH. SOME OF THESE
 OTHER ITEMS ARE IN NEED OF ADDRESSING AT THIS TIME. AS
 PLANS APPEAR TO BE COMING BACK FOR COMMENTS FROM OTHER
 TRADES, PLEASE ADDRESS AT THIS TIME..
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEWS WITH
 RESPECT TO MEANS OF EGRESS PHOTO-METRICS FOR STAIRS.
 UPON REVIEW OF THE PLANS COULD NOT LOCATE ON PLANS ANY
 MINIMUM LEVELS FOR OUTSIDE STAIRS WHICH ARE AT MANY
 LOCATIONS AROUND THE BUILDING.THE LEVELS WHICH WERE
 ADDED FOR THE TYPICAL INSIDE STAIRS WERE LOCATED AND
 REVIEWED. THE INSIDE WAS OK.
 PLEASE SEE NFPA-101 7.8 AND 7.9
  
 2) NOTE: PLEASE KNOW THAT DIVISION SPEC BOOKS WERE
 STILL NOT SUBMITTED AND PLANS REFERENCE THESE ITEMS FOR
 REQUIREMENTS. UNLESS THESE ARE SUBMITTED, SIGNED,
 DATED, SEALED AND FILED AS PART OF THE PROJECT AND FOR
 PUBLIC RECORD ANY AND ALL REFERENCES ON PLANS WHICH ARE
 SIGNED, DATED, SEALED AND FILED FOR PUBLIC RECORD SHALL
 CONTAIN THE SPECIFIC INFORMATION.
 ANY REFERENCES MUST BE ON PLANS. EXAMPLE: LIGHTNING
 PROTECTION SYSTEM NOTED ON PLANS.
 PLEASE SEE OTHERS.
 FBC 106.3.5.1.2, 106.3.1( INFORMATION REQUIRED ON
 PLANS)
  
 3) NOTE: PLEASE SEE MEN AND WOMEN BATHROOMS AS NO
 FIXTURES SHOWN CONTAIN NOTES FOR BATTERY BACK UP
 FIXTURES AND FIXTURES ON EACH FLOOR SUCH AS L AND L2 DO
 NOT CONTAIN NOTES ON FIXTURE LEGEND WHICH STATES THESE
 ARE TO BE BATTERY BACK UP.
 THIS IS TYPICAL OF THE BATHROOMS ON EACH FLOOR.
 ** THIS MAY BE PART OF THE *PROVISO*.
  
 4) NOTE: PLEASE SEE THE GENERATOR IS NOW SHOWN FULLY AS
 A SEPARATELY DERIVED UNIT; HOWEVER PLEASE SEE THE
 SUBMITTAL FOR THE FIRE PUMP ATS/CONTROLLER STILL
 APPEARS TO BE ONLY A THREE POLE UNIT.
 PLEASE CONFIRM THIS AS THE ATS FOR THE EMERGENCY
 SERVICE IS OK AT THE 4-POLE AS REQUIRED.
 250.20, ETC. PLEASE CONFIRM AS THE GEN IS SD. NFPA-20
 9.6, 10.8.
 NFPA-110 6.2.15
  
 5) NOTE: PLEASE CLARIFY CONTROL OF FIXTURES F-1 IN
 LOBBY 1-115, AS NO NOTE IS DIRECTLY CORRESPONDING TO
 THESE FIXTURES THE NEAREST NOTE IS #6. IS THIS
 CORRECT?
 THIS IS A ITEM WHICH CAN BE RED-LINED AND GIVEN ON
 *PROVISO*.
  
 6) NOTE: PLEASE SEE THE PLANS REFLECT PATTERSON FIRE
 PUMP AND SPECS/SUBMITTALS INDICATE AURORA AND
 PATTERSON.
 WHICH ONE WILL BE PART OF THE PERMITTED PLANS/PACKAGE.
 IF PLANS REMAIN WITH THE PATTERSON SPECS THEN ONLY THE
 AURORA SPECS NEED TO BE REMOVED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO THE
 INPUT DATA REPORT (IDR) AND ALL LIGHTING ON PLANS TO
 COORDINATE WITH THE IDR FOR NUMBERS OF FIXTURES, THE
 TYPES AND WATTAGES.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR NEEDS TO BE
 ADJUSTED FOR SOME ON PLANS OR IDR.
 FOR EXAMPLE:
 PLEASE SEE THE AMOUNT OF *K*, *K1* AND *K2* FIXTURES
 ARE IN QUESTION. THE AMOUNT ON PLANS APPEARS HIGHER
 THAN THE IDR. AS THE WATTAGE FOR WHAT IS BEING ASSUMED
 AS *K1* ON PLANS AND FIXTURE LEGEND COULD AFFECT THIS
 COUNT. PLEASE CLARIFY LOADING DOCK LIGHTS AND HOW THEY
 ARE PLANS ON THE IDR.
 FOR EXAMPLE:
 PLEASE SEE THE AMOUNT OF *J* FIXTURES ON PLANS EXCEED
 THAT SHOWN IN THE IDR.
 FOR EXAMPLE:
 PLEASE CLARIFY *Z* FIXTURES
 FOR EXAMPLE:
 PLEASE CLARIFY THE 128 WATT FIXTURE SHOWN ON THE IDR.
 FOR EXAMPLE:
 PLEASE CLARIFY THE FIXTURE LEGEND AND THE POLE DETAIL
 ON SHEET E5.01 WHICH INDICATES A TYPE SC FIXTURE
 HOWEVER NO FIXTURE COULD BE LOCATED ON THE SITE PLANS
 OR 400W FIXTURE WAS LOCATED IN THE IDR.
  
 ************************
  
 ** THE FOLLOWING ARE ITEM IS NOTED IN RESPONSE AND ON
 PLANS WHICH WAS NOT REQUESTED BY REVIEWER.
 THESE ITEMS STILL NEED TO BE CLARIFIED HOWEVER WILL NOT
 PREVENT ISSUANCE OF PERMIT.
  
 8) NOTE: ** ITEM #1**
 PLEASE SEE PLANS STATE AND SHOW THE COMPLETE TABLE PER
 310.16 WAS ADDED TO PLANS AT THE SPECIFIC REQUEST BY
 THIS REVIEWER WHEN IN FACT THIS WAS NOT THE CASE.
 PLEASE SEE SHEET E5.03.
 THIS WAS PREVIOUS NOTES # 10.
 THE PANEL SCHEDULES DID NOT SHOW ANY BRANCH CIRCUIT
 CONDUCTOR SIZE FOR THE LISTED OVER CURRENT PROTECTION
 DEVICES. THE REQUEST WAS TO LIST THE *MINIMUM* ON PANEL
 SCHEDULES OR TO SET UP SOME SORT OF TABLE WHICH WOULD
 CORRELATE THE SPECIFIC OVER CURRENT PROTECTION DEVICES
 WITH THE CONDUCTOR SIZES. FOR EXAMPLE:
 15AMP = #14
 20AMP = #12
 30AMP = #10
 40AMP= #8
 ETC ETC.
 VOLTAGE DROP AS REFERENCED FOR FBC 13-413.1.ABC.1.1 AND
 .1.2 WAS FOR WORST CASE.
  
 ** THIS DOES NOT NEED TO BE REMOVED HOWEVER WILL BE
 REQUIRED TO BE REVISED TO ACCURATELY SHOW ACTUAL
 CONDUCTORS INSTALLED FOR STANDARD OVER CURRENT
 PROTECTION DEVICE AND THE CONDUCTORS INSTALLED FOR
 WORST CASE.
 ** IN THE MEETING HELD BEFORE PLANS WERE RE-SUBMITTED
 THE DESIGNER OF RECORD FOR ELECTRICAL ASKED IF 310.16
 COULD BE PLACED ON PLANS IN LIEU OF ANY *TABLE*. THE
 RESPONSE FROM THIS REVIEW WAS THAT WOULD BE OK, HOWEVER
 WAS NOT REQUIRED OR REQUESTED.
  
 PLEASE KNOW THE LENGTH AND WORST CASE DESIGN CAN BE
 PART OF THE *PROVISO*.
 ** PLEASE DO NOT PLACE STATEMENTS ON PLANS FOR ITEMS
 NOT REQUESTED BY REVIEWER.
  
 9) NOTE: *** ITEM #2***
  
 PLEASE SEE RESPONSE MENTIONS 215.3 AND 230.42 DID NOT
 APPLY FOR CONTINUOUS LOADS TO BE SHOWN AT 125% AND THE
 REVIEWER WAS REQUESTING THIS ABOVE THE *MINIMUM* CODE
 REQUIREMENTS.
 PLEASE PROVIDE INFORMATION OR DOCUMENTATION HOW THESE
 SECTIONS OF THE CODE DO NOT APPLY TO CONTINUOUS LOADS.
 (LOADS OF WHICH ARE 3 OR MORE HOURS, SEE NEC 100 FOR
 *CONTINUOUS LOADS* ALONG WITH 210.20A).
 IF PLANS DID NOT INDICATE ANY CONTINUOUS LOAD FACTORS
 WERE ALREADY FIGURED OR IN DESIGN HOW WOULD THIS OFFICE
 KNOW IF ANY CONSIDERATION WAS IN DESIGN?
  
 THIS WOULD BE THE FIRST TIME AND THE ONLY TIME WHERE
 THIS HAS BEEN AN ISSUE. THE FACT IS THAT MOST PLANS
 ALREADY HAVE THE CONTINUOUS LOADS SHOWN AT 125% IN
 COMMERCIAL APPLICATIONS.
 PLEASE PROVIDE ANY DOCUMENTATION WHERE THESE SECTIONS
 DO NOT APPLY AND WHAT IS BEING REQUESTED IS ABOVE THE
 MINIMUM CODE.
 IF THE PLANS/SERVICE/CONDUCTORS AND FEEDERS ETC DO NOT
 NEED TO BE SIZED ACCORDING TO THESE SECTIONS AS NOTED
 PLEASE PROVIDE DOCUMENTATION ACCORDINGLY.
 ** PLEASE DO NOT MAKE STATEMENTS THAT THIS REVIEWER IS
 REQUIRING OR REQUESTING ANYTHING ABOVE THE *MINIMUM*
 CODE.
 IF DOCUMENTATION CAN BE PROVIDED FROM NFPA THAT THESE
 SPECIFIC ITEMS DO NOT APPLY THEN THE SERVICE SIZE,
 CONDUCTORS, FEEDERS ETC, CAN BE DECREASED. THE RESPONSE
 STATES ALL OF THESE ITEMS WERE INCREASED DUE TO THIS
 REVIEWER'S COMMENTS AND ARE ABOVE THE MINIMUM. **ONLY
 THE MINIMUM IS REQUIRED. THIS OFFICE DOES NOT AND WILL
 NOT REQUIRE OR REQUEST ITEMS ABOVE MINIMUM DESIGN.
 PLEASE CLARIFY.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  