| Date |
Text |
| 2008-01-31 15:13:39 | PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050361 |
| | ADD: 800 CLEMATIS ST |
| | CONT: THE MORGANTI GROUP, INC*PLAN REVIEW ONLY* |
| | TEL: (561)262-6771 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING TYPE;IB |
| | 2NDREVIEW- PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE2007 REVISIONS. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 2-6) COMPLIED. |
| | |
| | 7)PROVISO: NOTE TO CONTRACTOR : 109.3.10* IMPACT OF |
| | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO |
| | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY |
| | OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR |
| | DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF |
| | CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL |
| | NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE |
| | FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING |
| | STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE |
| | AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT, |
| | INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | |
| | 8) PROVISO: NOTE TO CONTRACTOR: 109.3.10.1 HURRICANE |
| | PROTECTION. IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND |
| | DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A |
| | CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH |
| | HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING |
| | HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE |
| | CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO |
| | MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR |
| | PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAIL TO |
| | COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS |
| | EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT |
| | TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 9-10) COMPLIED. |
| | |
| | 11A) 3RD REQUEST, THIS COMMENT WAS ONLY PARTIALLY |
| | COMPLIED WITH YES A SURVEY IS PRESENT BUT NOT |
| | INCORPORATED INTO THE SET OF PLANS. THE REAL ISSUE IS |
| | THE PROPERTY LINE ON THE WEST END OF THE BUILDING IS |
| | WITHIN THE BUILDING LINE. ALTHOUGH VINCE NOEL WITH |
| | ENGINEERING HAS NO SAY IN MATTERS WITH THE FLORIDA |
| | BUILDING CODE. IT HAS BEEN SAID REPEATEDLY THAT WE ARE |
| | IN AGREEMENT THAT THE REPLAT CAN HAPPEN OVER THE LIFE |
| | OF THE BUILDING PERMIT. BUT THERE IS A PROPERTY LINE |
| | THAT IS WITH THE BUILDING. ONE OF TWO WAYS TO CREATE |
| | CODE COMPLIANCE IS TO BUILD A 4HR WALL ON THE PROPERTY |
| | LINE WHICH THERE CAN BE NO OPENINGS AGAIN SEE TABLE 602 |
| | AND TABLE 704.8, THE THER WAY IS TO UNIFY THE LOTS NOT |
| | A REPLAT! THIS IS COMPLETED BY A UNITY OF TITLE, THIS |
| | IS CLEARLY THE WAY TO GO ALLOWING OPENINGS WITHIN THE |
| | WEST WALL OF THE BUILDING. |
| | |
| | 11B-26E) COMPLIED. |
| | |
| | 26F) BUILDING PROVISO: SHOP DRAWINGS REQUIRED,PLEASE |
| | NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1 ELECTROLYSIS |
| | PROTECTION FOR UNDERGROUND HYDRAULIC ELEVATOR |
| | CYLINDERS. |
| | ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE |
| | CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT |
| | TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL |
| | CYLINDER AND GROUND CATHODE. |
| | 1.THE PLASTIC CASING SHALL BE CAPPED AT THE |
| | BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED |
| | TO ENSURE WATER TIGHTNESS. |
| | 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF |
| | POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC |
| | PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH |
| | (3.175 MM). |
| | 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A |
| | MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS |
| | BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE |
| | PROTECTIVE PLASTIC CASING. |
| | 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS |
| | SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE |
| | EXISTING PHYSICAL DIMENSIONS PERMIT |
| | |
| | 27-29) COMPLIED. |
| | |
| | 30) SHEET S-7/ S-13 |
| | |
| | 30A) COMPLIED. |
| | |
| | 30B) COMPLIED. |
| | |
| | 30C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 30D) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A-K) COMPLIED. |
| | |
| | L) ROOFING ASSEMBLIES, SIPLAST/ COPAL MODIFIED |
| | BITUMEN OVER LWCDECK, THE SUBSYSTEMS LOCATED ON |
| | SHEETS 8-20 ARE NOT HIGHLIGHTED AS TO WHICH SYTEM SHALL |
| | BE INSTALLED. |
| | EACH SUBSYSTEM HAS A SPECIFIC DESIGN PRESSURE, |
| | NOTELIMITATIONS 7 AND 9. LIMITATION NUMBER 7 ALLOWS |
| | ENHANCED FASTENING TO RAS 117 WHEREAS LIMITATION NUMBER |
| | 9 WILL NOT |
| | ALLOW ENHANCED FASTENING. |
| | M- PRE-ENGINEERED A/C STANDSNO LETTER THAT THIS |
| | PRODUCT WAS REVIEWED FOR CODE COMPLIANCE FROM THE |
| | DESIGN TEAM. |
| | N- PROVISO: CLIP SYSTEM FOR THE CURTAINWALL SYSTEM |
| | TOBE SUBMITTED AS PART OF THE WINDOW SHOP DRAWINGS. |
| | |
| | 31-32) COMPLIED. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | ***** UNSAT2ND REVIEW **** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |