| 2007-10-22 17:05:40 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW, COMMENT NUMBERS TO REMAIN THE |
| | SAME TO AVOID CONFUSION: |
| | |
| | SUBMITTED AS PLAN REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR |
| | EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS |
| | INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW |
| | TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR |
| | ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS & TABLE 1106.3. |
| | ****RESPONSE NOTED, BUT THE RESPONSE DOES NOT ADDRESS |
| | THE COMMENT. --THE SQUARE FOOTAGE BEING DRAINED BY |
| | EACH ROOF DRAIN IS NOT INDICATED.--NO CALCULATION |
| | FOR THE LOWER ROOFS OR UPPER ROOFS FOR THE STAIRWAY |
| | WERE FOUND.--THE CALCULATIONS FOUND ON SHT. A2.06 |
| | WERE INDICATED AS OVERFLOW SCUPPER SECONDARY ROOF |
| | CALCULATIONS.--SHOW THE SQUARE FOOTAGE OF EACH AREA |
| | WITH THE VERTICAL CONTRIBUTION FOR THAT AREA, NOT TOTAL |
| | AREA FOR THE WHOLE ROOF AS NOT ALL AREAS DRAIN THE SAME |
| | TOTAL AREA. |
| | |
| | 5. OK |
| | |
| | 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN |
| | THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3. |
| | ****RESPONSE NOTED, BUT THE TURNING AREAS ARE NOT |
| | INDICATED IN THE TOILET ROOMS. |
| | |
| | 7. OK |
| | |
| | 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4 |
| | FLUSH CONTROLS. |
| | ****RESPONSE NOTED, BUT NO INFORMATION ON THE URINAL |
| | FLUSH CONTROLS FOUND. |
| | |
| | 9. OK |
| | |
| | 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | A. 11-4.21.2 SIZE AND CLEARANCE |
| | ****RESPONSE NOTED, BUT THE SHOWER IS INDICATED AS |
| | 36"X40". THE REQUIREMENT IS FOR THE SHOWER TO BE |
| | 36"X36". |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | |
| | 11. OK |
| | 12. OK |
| | NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR |
| | FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL |
| | BE ADA APPROVED OFFSET TYPE. |
| | |
| | 13. OK |
| | 14. OK |
| | |
| | 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS |
| | ALLOWED IN THE CLEAR FLOOR SPACE). |
| | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED |
| | ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE |
| | SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET). |
| | B. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | C. 11-4.24.7 FAUCETS |
| | |
| | 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311 |
| | SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 & ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED |
| | ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE |
| | SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET). |
| | B. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | C. 11-4.24.7 FAUCETS |
| | |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | |
| | 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF |
| | PER TABLE 1106.3. 4" IS SHOWN. |
| | ****RESPONSE NOTED, BUT THE PIPE SLOPE IS NOT INDICATED |
| | ON THE PLANS AS INDICATED. THERE WERE MANY CHANGES TO |
| | THE SHEET AND I DO NOT SEE THE 1800SF. |
| | |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | |
| | 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS |
| | CALLED "WATERLESS URINALS". THE URINALS ARE ALSO |
| | DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE |
| | CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A |
| | SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB. |
| | SECTION 606.2.2. |
| | ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE |
| | BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES. |
| | SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME |
| | SIZE AS THE HOSE BIBB. |
| | |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | |
| | 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING |
| | FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY. |
| | SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE |
| | SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).-- |
| | SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE |
| | BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES. |
| | SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME |
| | SIZE AS THE HOSE BIBB.--ALSO THE RISER NOW SHOWS AN |
| | EXTRA P-3 FIXTURE, (CHANGED FROM THE P-5), AND THERE IS |
| | AN EXTRA P-4 FIXTURE INDICATED IN THE WOMEN'S TOILET |
| | ROOM. |
| | |
| | 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE & |
| | VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE |
| | SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING |
| | FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT |
| | OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION |
| | 606.2.(2) --SHOWS A P-5 FIXTURENOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO |
| | SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE P-5 FIXTURE WAS CHANGED TO |
| | A P-3 AND THAT IS ONE P-3 TOO MANY. ALSO THERE IS A P-4 |
| | FIXTURE IN THE WOMEN'S TOILET ROOM.--NO SLEEVES |
| | SHOWN FOR THE WATER RISERS. |
| | |
| | 31. OK |
| | |
| | 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER |
| | DOES NOT REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS |
| | VTR AT ONE FIXTURE, AND THE RISER SHOWS VTR AT ANOTHER |
| | FIXTURE. ALSO SHOW THE COMPLETE REVENT ON THE FLOOR |
| | PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE FLOOR PLAN DOES NOT SHOW |
| | THE RE-VENT FROM P-11 4TH FLOOR TO P-11 ON THE 5TH |
| | FLOOR. |
| | |
| | 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR |
| | ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE |
| | ABLE TO TRACE THE RISERS FROM UNDERGROUND TO |
| | TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2. |
| | ****RESPONSE NOTED, BUT RISER 6R/P-3.2 IS NOT SHOWN ON |
| | THE 2ND THRU 4TH FLOORS. ALSO CHECK RISER 2R/P-3.2. |
| | PLEASE CHECK ALL FLOORS AND SEE THAT ALL RISER |
| | DESIGNATIONS SHOWN REFLECT THE INFORMATION INDICATED ON |
| | THE FLOOR PLAN. |
| | |
| | 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN. |
| | WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE |
| | CORRELATE. |
| | ****RESPONSE NOTED, BUT THE FLOOR SINK REQUIRED AT THE |
| | ICE MACHINE IS NOT SHOWN. SECTIONS 802.3 & 802.3.2. A |
| | FLOOR DRAIN IS NOT AN APPROVED INDIRECT WASTE |
| | INTERCEPTOR. |
| | |
| | 35. OK |
| | |
| | 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN. |
| | SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT |
| | ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT SHOW COMPLETE RISER INCLUDING |
| | BUILDING DRAIN PIPING OUT OF THE BUILDING. THE FIRST |
| | FLOOR W/P-13 BOX IS NOT SHOWN ON THE 1ST FLOOR. THE |
| | W/P-13 BOX IS SHOWN ON THE OTHE SIDE OF THE RISERON |
| | THE 3RD FLOOR. PLEASE CORRELATE RISER AND FLOOR PLAN. |
| | |
| | 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF |
| | PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION 106.1.1. |
| | ****RESONSE NOTED, BUT THE COMPLETE RISER INCLUDING THE |
| | BUILDING DRAIN PIPING OUT OF THE BUILDING SHALL BE |
| | SHOWN ON THE RISER DIAGRAM. SHOW ALL CLEANOUTS REQUIRED |
| | BY SECTION 1101.8 ON THE RISER DIAGRAM. |
| | |
| | 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF |
| | DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| | FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.-- |
| | MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3. |
| | ****RESPONSE NOTED, BUT NOW THE ADDITION IS INCORRECT. |
| | THE TOTAL SHOULD BE 2,750SF, NOT 2,650SF OR 3,110SF AS |
| | SHOWN ON THE RISER. TABLE 1106.3. |
| | |
| | 39. OK |
| | |
| | 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN |
| | IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.-- |
| | THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE |
| | MAKER LINE PER SECTION 604.9. |
| | ****RESPONSE NOTED, BUT THE RISER STILL HAS MANY AREAS |
| | THAT DOES NOT REFLECT THE FLOOR PLAN. ALSO P-10 SHOWS |
| | THE HOT ON THE RIGHT SIDE OF THE FIXTURE. THE HOT WATER |
| | SHALL BE ON THE LEFT SIDE OF THE FIXTURE PER SECTION |
| | 607.4.--NOT ALL RISER DESIGNATIONS ARE SHOWN ON THE |
| | FLOOR PLAN.--WATER TO P-6 IN CEILING, THE WATER TO |
| | THE FUME HOOD IN THE CEILING, & THE 2 SUPPLY BRANCHES |
| | TO 2R/P-3.1 DO NOT REFLECT THE FLOOR PLAN. |
| | |
| | 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN |
| | AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION |
| | REQUIRED ON THIS LINE). SECTION 608.--THE WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | ****RESPONSE NOTED, BUT THE LINE TO THE A/C UNIT IS NOT |
| | SHOWN ON THE RISER DIAGRAM.--THE HOT WATER TO |
| | FIXTURE P-10 SHOWS THE HOT TO THE RIGHT SIDE OF THE |
| | FIXTURE. HOT WATER SHALL BE TO THE LEFT PER SECTION |
| | 607.4. |
| | |
| | 42. OK |
| | 43. OK DELETED NAT. GAS |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHT A4.01 DETAIL FOR MEN'S AND WOMENS RESTROOM |
| | TYPICAL DETAILS A4.01(2) & (4). THE FLUSH CONTROLS FOR |
| | THE W/C SHALL BE ON THE WIDE SIDE PER SECTION |
| | 11-4.16.5. THE FLUSH CONTROLS ARE SHOWN ON THE WALL |
| | SIDE. PLEASE CORRECT DETAILS. |
| | |
| | 2B. SHT P2.2 SHOWS 6" RWL 3,100SF & ALSO NOW INDICATES |
| | 6" RWL 4,600SF FOR THE SAME RISER. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | GARBAGE DISPOSAL. SHOW ADA COMPLIANCE. SECTION 106.1.2 |
| | & 11-4.24.5. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |