Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-22 17:05:40DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW, COMMENT NUMBERS TO REMAIN THE
 SAME TO AVOID CONFUSION:
  
 SUBMITTED AS PLAN REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR
 EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS
 INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW
 TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR
 ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLE 1106.3.
 ****RESPONSE NOTED, BUT THE RESPONSE DOES NOT ADDRESS
 THE COMMENT. --THE SQUARE FOOTAGE BEING DRAINED BY
 EACH ROOF DRAIN IS NOT INDICATED.--NO CALCULATION
 FOR THE LOWER ROOFS OR UPPER ROOFS FOR THE STAIRWAY
 WERE FOUND.--THE CALCULATIONS FOUND ON SHT. A2.06
 WERE INDICATED AS OVERFLOW SCUPPER SECONDARY ROOF
 CALCULATIONS.--SHOW THE SQUARE FOOTAGE OF EACH AREA
 WITH THE VERTICAL CONTRIBUTION FOR THAT AREA, NOT TOTAL
 AREA FOR THE WHOLE ROOF AS NOT ALL AREAS DRAIN THE SAME
 TOTAL AREA.
  
 5. OK
  
 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN
 THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3.
 ****RESPONSE NOTED, BUT THE TURNING AREAS ARE NOT
 INDICATED IN THE TOILET ROOMS.
  
 7. OK
  
 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4
 FLUSH CONTROLS.
 ****RESPONSE NOTED, BUT NO INFORMATION ON THE URINAL
 FLUSH CONTROLS FOUND.
  
 9. OK
  
 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.21.2 SIZE AND CLEARANCE
 ****RESPONSE NOTED, BUT THE SHOWER IS INDICATED AS
 36"X40". THE REQUIREMENT IS FOR THE SHOWER TO BE
 36"X36".
 B. OK
 C. OK
 D. OK
 E. OK
  
 11. OK
 12. OK
 NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR
 FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL
 BE ADA APPROVED OFFSET TYPE.
  
 13. OK
 14. OK
  
 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE).
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED
 ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE
 SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET).
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
  
 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 & ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.4 SINK DEPTH - THE MODEL NUMBER INDICATED
 ON THE PLANS DOES NOT COMPLY WITH REQUIREMENT FOR THE
 SINK TO BE A MAXIMUM 6-1/2". (SEE ATTACHED SHEET).
 B. 11-4.24.6 EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
  
 17. OK
 18. OK
 19. OK
  
 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF
 PER TABLE 1106.3. 4" IS SHOWN.
 ****RESPONSE NOTED, BUT THE PIPE SLOPE IS NOT INDICATED
 ON THE PLANS AS INDICATED. THERE WERE MANY CHANGES TO
 THE SHEET AND I DO NOT SEE THE 1800SF.
  
 21. OK
 22. OK
 23. OK
  
 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS
 CALLED "WATERLESS URINALS". THE URINALS ARE ALSO
 DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE
 CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A
 SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB.
 SECTION 606.2.2.
 ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE
 BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES.
 SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME
 SIZE AS THE HOSE BIBB.
  
 25. OK
 26. OK
 27. OK
  
 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING
 FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY.
 SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE
 SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).--
 SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE MINIMUM SIZE FOR A HOSE
 BIBB IS 1/2" AND THE PLANS SHOW 3/8" SHUT OFF VALVES.
 SECTION 604.5. THE SHUT OFF VALVE IS TO BE THE SAME
 SIZE AS THE HOSE BIBB.--ALSO THE RISER NOW SHOWS AN
 EXTRA P-3 FIXTURE, (CHANGED FROM THE P-5), AND THERE IS
 AN EXTRA P-4 FIXTURE INDICATED IN THE WOMEN'S TOILET
 ROOM.
  
 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2) --SHOWS A P-5 FIXTURENOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO
 SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE P-5 FIXTURE WAS CHANGED TO
 A P-3 AND THAT IS ONE P-3 TOO MANY. ALSO THERE IS A P-4
 FIXTURE IN THE WOMEN'S TOILET ROOM.--NO SLEEVES
 SHOWN FOR THE WATER RISERS.
  
 31. OK
  
 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER
 DOES NOT REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS
 VTR AT ONE FIXTURE, AND THE RISER SHOWS VTR AT ANOTHER
 FIXTURE. ALSO SHOW THE COMPLETE REVENT ON THE FLOOR
 PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE FLOOR PLAN DOES NOT SHOW
 THE RE-VENT FROM P-11 4TH FLOOR TO P-11 ON THE 5TH
 FLOOR.
  
 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR
 ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE
 ABLE TO TRACE THE RISERS FROM UNDERGROUND TO
 TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT RISER 6R/P-3.2 IS NOT SHOWN ON
 THE 2ND THRU 4TH FLOORS. ALSO CHECK RISER 2R/P-3.2.
 PLEASE CHECK ALL FLOORS AND SEE THAT ALL RISER
 DESIGNATIONS SHOWN REFLECT THE INFORMATION INDICATED ON
 THE FLOOR PLAN.
  
 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN.
 WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE
 CORRELATE.
 ****RESPONSE NOTED, BUT THE FLOOR SINK REQUIRED AT THE
 ICE MACHINE IS NOT SHOWN. SECTIONS 802.3 & 802.3.2. A
 FLOOR DRAIN IS NOT AN APPROVED INDIRECT WASTE
 INTERCEPTOR.
  
 35. OK
  
 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN.
 SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT
 ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT SHOW COMPLETE RISER INCLUDING
 BUILDING DRAIN PIPING OUT OF THE BUILDING. THE FIRST
 FLOOR W/P-13 BOX IS NOT SHOWN ON THE 1ST FLOOR. THE
 W/P-13 BOX IS SHOWN ON THE OTHE SIDE OF THE RISERON
 THE 3RD FLOOR. PLEASE CORRELATE RISER AND FLOOR PLAN.
  
 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF
 PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.1.1.
 ****RESONSE NOTED, BUT THE COMPLETE RISER INCLUDING THE
 BUILDING DRAIN PIPING OUT OF THE BUILDING SHALL BE
 SHOWN ON THE RISER DIAGRAM. SHOW ALL CLEANOUTS REQUIRED
 BY SECTION 1101.8 ON THE RISER DIAGRAM.
  
 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF
 DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.--
 MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3.
 ****RESPONSE NOTED, BUT NOW THE ADDITION IS INCORRECT.
 THE TOTAL SHOULD BE 2,750SF, NOT 2,650SF OR 3,110SF AS
 SHOWN ON THE RISER. TABLE 1106.3.
  
 39. OK
  
 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN
 IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.--
 THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE
 MAKER LINE PER SECTION 604.9.
 ****RESPONSE NOTED, BUT THE RISER STILL HAS MANY AREAS
 THAT DOES NOT REFLECT THE FLOOR PLAN. ALSO P-10 SHOWS
 THE HOT ON THE RIGHT SIDE OF THE FIXTURE. THE HOT WATER
 SHALL BE ON THE LEFT SIDE OF THE FIXTURE PER SECTION
 607.4.--NOT ALL RISER DESIGNATIONS ARE SHOWN ON THE
 FLOOR PLAN.--WATER TO P-6 IN CEILING, THE WATER TO
 THE FUME HOOD IN THE CEILING, & THE 2 SUPPLY BRANCHES
 TO 2R/P-3.1 DO NOT REFLECT THE FLOOR PLAN.
  
 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION
 REQUIRED ON THIS LINE). SECTION 608.--THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE LINE TO THE A/C UNIT IS NOT
 SHOWN ON THE RISER DIAGRAM.--THE HOT WATER TO
 FIXTURE P-10 SHOWS THE HOT TO THE RIGHT SIDE OF THE
 FIXTURE. HOT WATER SHALL BE TO THE LEFT PER SECTION
 607.4.
  
 42. OK
 43. OK DELETED NAT. GAS
  
 **********NEW COMMENTS**********
  
 1B. SHT A4.01 DETAIL FOR MEN'S AND WOMENS RESTROOM
 TYPICAL DETAILS A4.01(2) & (4). THE FLUSH CONTROLS FOR
 THE W/C SHALL BE ON THE WIDE SIDE PER SECTION
 11-4.16.5. THE FLUSH CONTROLS ARE SHOWN ON THE WALL
 SIDE. PLEASE CORRECT DETAILS.
  
 2B. SHT P2.2 SHOWS 6" RWL 3,100SF & ALSO NOW INDICATES
 6" RWL 4,600SF FOR THE SAME RISER. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 GARBAGE DISPOSAL. SHOW ADA COMPLIANCE. SECTION 106.1.2
 & 11-4.24.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]