| 2007-10-15 11:02:56 | REVIEW #: 2 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. ANY ADDITIONAL |
| | COMMENTS GENERATED BY NEW INFORMATION PROVIDED ON PLANS |
| | WILL BE LOCATED AT THE END. |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. OK EXCEPT, IF 12 IN. ROUND DUCT IS EXHAUSTING |
| | HAZARDOUS MATERIALS, IT SHALL BE IN COMPLIANCE WITH |
| | FBC,M 510.6. |
| | |
| | 5. (A) SEVERAL DUCTS PENETRATING NEWLY RATED CORRIDOR |
| | ARE MISSING OPENING PROTECTIVES (FIRE DAMPERS). PLEASE |
| | NOTE THAT SEVERAL DUCTS WHICH CLAIM EXCEPTION TO THIS |
| | REQUIREMENT UNDER FBC,M 607.5.3 DO NOT MEET ALL |
| | REQUIREMENTS. UNDER EXCEPTION 2, DUCTS MUST MEET ALL 6 |
| | REQUIREMENTS. IF A DUCT HAS AN OPENING IN THE CORRIDOR |
| | IT HAS NOT MET CONDITION 2.3 OF EXCEPTION 2. |
| | (B) DUCTS PENETRATING NEWLY RATED CORRIDOR WALLS SHALL |
| | BE PROTECTED WITH LISTED SMOKE DAMPERS IN ACCORDANCE |
| | WITH FBC,M 607.5.4 AND SHALL BE ACTUATED IN ACCORDANCE |
| | WITH FBC,M 607.5.4.1. NOTE THAT SUPPLY AND RETURN DUCTS |
| | FROM AHU 1-1 EACH HAVE OPENINGS IN THE CORRIDOR AND |
| | THEREFORE NONE OF THE DUCT PENETRATIONSON THE SUPPLY |
| | OR RETURN SYSTEMS HAVE MET EXCEPTION 3 UNDER THIS |
| | SECTION. |
| | PROVIDE OPENING PROTECTIVES AND SMOKE DAMPERS AS |
| | REQUIRED BY THESE SECTIONS AT ALL DUCT PENETRATIONS OF |
| | THE 1-HOUR RATED CORRIDOR WALLS. LISTED COMBINATION |
| | FIRE/SMOKE DAMPERS MAY BE USED AT THESE LOCATIONS TO |
| | MEET BOTH REQUIREMENTS. |
| | |
| | 6. ALL AREAS: DUCTS AND AIR TRANSFER OPENINGS THAT |
| | PENETRATE FIRE-RESISTANCE-RATED ASSEMBLIES AND ARE NOT |
| | REQUIRED TO HAVE DAMPERS BY THIS SECTION SHALL COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 712 OF THE FLORIDA |
| | BUILDING CODE, BUILDING IN ACCORDANCE WITH FBC,M |
| | 607.1.1. THIS IS A GENERAL REQUIREMENTS AND THEREFORE |
| | APPLIES TO ALL OF SECTION 607. ANY DUCT PENETRATING A |
| | FIRE RESISTANCE RATED ASSEMBLY SHALL BE PROTECTED BY A |
| | FIRE DAMPER OR, IF IT MEETS ANY OF THE EXCEPTIONS UNDER |
| | THIS SECTION, IT SHALL COMPLY WITH FBC 712.3 WHICH |
| | REQUIRES A THROUGH-PENETRATION FIRESTOP SYSTEM. PLEASE |
| | SEE FBC 712.3.1.2 FOR SPECIFIC REQUIREMENTS. PROVIDE |
| | DETAIL FOR ANY LISTED ASSEMBLY TO BE USED. |
| | |
| | 7 THRU 9. OK |
| | |
| | 10. FIRE/SMOKE DAMPERS HAVE BEEN ADDED. HOWEVER, THE |
| | SHAFT IS STILL NOT SHOWN ON ARCHITECTURAL PLANS. PG |
| | A2.01 THRU A2.05 SHOW A TYPE 4 NON-RATED CHASE WALL AT |
| | THAT LOCATION. SHOW COORDINATION BETWEEN PLANS BY |
| | SHOWING THE SHAFT WHICH IS REQUIRED FOR THE BATH |
| | EXHAUST RISER DUCT IN ACCORDANCE WITH FBC 707.2. |
| | |
| | 11 THRU 14. OK |
| | |
| | 15. INTAKE FOR AHU 1-2 IS WITHIN 10 FT OF EXHAUST |
| | LOUVER FOR THE HOOD IN ROOM 2-244. SHOW COMPLIANCE WITH |
| | FBC,M 501.2. |
| | |
| | 16 THRU 21. OK |
| | |
| | 22. FLEX DUCTS HAVE BEEN REMOVED. HOWEVER, RECTANGLE |
| | DUCT PENETRATIONS DO NOT SHOW OPENING PROTECTIVES AT |
| | RATED WALLS PER FBC,M 607.5. ALSO, PLEASE SEE COMMENT |
| | #5 ABOVE. |
| | |
| | 23 THRU 25. OK |
| | |
| | NEW COMMENTS: |
| | |
| | A. PG E0.02 AND P2.1 INDICATE THE GENERATOR HAS BEEN |
| | CHANGED TO DIESEL FUEL. NO INFORMATION COULD BE FOUND |
| | REGARDING THE EXTERIOR FUEL STORAGE TANK OR THE INSIDE |
| | DAY TANK. PROVIDE INSTALLATION INSTRUCTIONS/DETAILS AND |
| | LISTING INFORMATION FOR GENERATOR AND FUEL TANKS. FUEL |
| | TANKS SHALL BE SHOWN ON SITE PLAN WITH SETBACKS AND |
| | DISTANCES FROM EXISTING AS WELL AS PROPOSED |
| | STRUCTURES. |
| | |
| | |
| | B. PROVIDE DETAIL DRAWING SHOWING LAYOUT OF GENERATOR |
| | AND FORE PUMP ROOMS WITH MEANS OF VENTILATION AND |
| | EXHAUST. SHOW GENERATOR TO BE IN COMPLIANCE WITH NFPA |
| | 37-02 AND FUEL STORAGE TO BE IN COMPLIANCE WITH NFPA |
| | 30-00. |
| | NOTE: ABOVE GROUND STORAGE TANKS >550 GALLONS REQUIRE |
| | PRIOR APPROVAL BY PBC DEPARTMENT OF ENVIRONMENTAL |
| | RESOURCE MANAGEMENT (DERM). FOR MORE INFORMATION PLEASE |
| | CONTACT DERM AT 561-233-2400 OR |
| | WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP |
| | |