| 2007-10-19 20:33:27 | *****UNSAT***** |
| | |
| | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE |
| | PLAN REVIEW STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED |
| | PRIOR TO, DURING, AND AFTER CONSTRUCTION.ADD COMMENT |
| | TO SHEET C-13 |
| | |
| | 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY |
| | OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE |
| | LANES).ADD COMMENT TO SHEET C-10 |
| | |
| | 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON |
| | THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. PLEASE INCLUDE THE WIDTH (STROKE) OF THOSE |
| | ADDRESS NUMBERS ALSO |
| | |
| | 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC) |
| | SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR |
| | OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR |
| | DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A |
| | SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT |
| | CONNECTION) SHALL BE POSTED.ADD COMMENT TO SHEET |
| | FP0.01 |
| | |
| | 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE |
| | DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724. |
| | ADD COMMENT TO SHEET FP0.01 |
| | |
| | 08.A CHAIN AND LOCK IN ADDITION TO THE ELECTRONIC |
| | SWITCHES SHALL BE REQUIRED FOR THE DOUBLE CHECK |
| | DETECTOR ASSEMBLY.ADD COMMENT TO SHEET FP0.01 |
| | |
| | 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1.ADD COMMENT ALSO TO SHEET A7.01 |
| | |
| | 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE |
| | INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS. |
| | AMEND/CLARIFY TO SHOW THE NORTH ELEVATION AS FRONTING |
| | CLEMATIS STREET |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |