Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-10-19 20:33:27*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED
 PRIOR TO, DURING, AND AFTER CONSTRUCTION.ADD COMMENT
 TO SHEET C-13
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE
 LANES).ADD COMMENT TO SHEET C-10
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH. PLEASE INCLUDE THE WIDTH (STROKE) OF THOSE
 ADDRESS NUMBERS ALSO
  
 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR
 OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR
 DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A
 SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT
 CONNECTION) SHALL BE POSTED.ADD COMMENT TO SHEET
 FP0.01
  
 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT 561-804-4724.
 ADD COMMENT TO SHEET FP0.01
  
 08.A CHAIN AND LOCK IN ADDITION TO THE ELECTRONIC
 SWITCHES SHALL BE REQUIRED FOR THE DOUBLE CHECK
 DETECTOR ASSEMBLY.ADD COMMENT TO SHEET FP0.01
  
 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1.ADD COMMENT ALSO TO SHEET A7.01
  
 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE
 INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS.
 AMEND/CLARIFY TO SHOW THE NORTH ELEVATION AS FRONTING
 CLEMATIS STREET
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722