| 2007-10-04 10:11:59 | |
| | *** DENIED 2ND REVIEW *** |
| | |
| | PALM BEACH COUNTY HEALTH DEPARTMENT. |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS |
| | REVIEW WHICH NEEDS TO BE ADDRESSED. |
| | ** PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON |
| | CHANGES ON PLANS AND INFORMATION ONLY NOW SUBMITTED FOR |
| | REVIEW. |
| | THE PREVIOUS REVIEW DID NOTE THAT DUE TO INFORMATION |
| | NOT SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS. |
| | |
| | 1) NOTE: ONCE AGAIN: PLEASE KNOW THAT PLANS HAVE ONLY |
| | BEEN SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE |
| | COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS |
| | AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE |
| | VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME |
| | OF APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE NOTE #5 FROM PREVIOUS REVIEW WHICH |
| | GAVE ALL CODES RELEVANT FOR THIS ELECTRICAL REVIEWER TO |
| | BE ON PLANS. THESE WERE ADJUSTED AND CORRECTED ON MOST |
| | SHEETS HOWEVER PLEASE SEE FP0.01 WHICH STILL INDICATES |
| | THE 2002 NFPA-70 AND THE 1999 NFPA-20. |
| | PLEASE ADJUST THESE TO THE 2005 NFPA-70 AND 2003 NFPA. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE #6 WITH RESPECT TO |
| | FBC CHAPTER 13. PLEASE SEE THERE ARE STILL SOME ITEMS |
| | WHICH NEED TO BE ADDRESSED. 13-415.1.AB.1.1, 13-415.2, |
| | 13-415 |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED WHICH |
| | STILL NEED TO BE SIGNED, DATED AND SEALED ON THE |
| | CERTIFICATION SHEET. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED STILL |
| | NEED TO CORRELATE WITH PLANS. ALL LIGHTING INFORMATION |
| | WHICH IS PLACED ON THE INPUT DATA REPORT NEEDS TO |
| | COORDINATE WITH ALL LIGHTING AS SHOWN ON PLANS. PLEASE |
| | SEE ALL REFERENCES TO THE INPUT DATA REPORT BELOW WILL |
| | BE NOTED AS IDR. |
| | A) PLEASE BE SURE ALL EXTERIOR LIGHTING FIXTURES WHICH |
| | ARE ON PLANS COORDINATE WITH THE IDR. |
| | FOR EXAMPLE, THE IDR ONLY INDICATES THREE TYPES AND |
| | WATTAGES YET PLANS INDICATE MORE FIXTURES WHICH ARE NOT |
| | FIGURED. PLEASE SEE FIXTURES J, K, K1 ETC. ALL EXTERIOR |
| | LIGHTING. |
| | |
| | B) PLEASE SEE ALL LIGHTING ON PLANS FOR INTERIOR |
| | LIGHTING NEEDS TO COORDINATE WITH THE IDR FOR LIGHTING |
| | WATTAGES, TYPES, NUMBER OF FIXTURES ALONG WITH METHOD |
| | OF CONTROLS. |
| | FOR EXAMPLE, PLEASE SEE SEVERAL FIXTURES WHICH ARE ON |
| | THE PLANS AND FIXTURE LEGEND WHICH ARE NOT ON THE |
| | CALCULATIONS IDR. FIXTURES V, L2, F2, L1, T, ETC. |
| | |
| | ** AS NOTED ABOVE PLEASE GO OVER ALL FIXTURES AND KNOW |
| | THAT THESE ARE ONLY A COUPLE OF EXAMPLES GIVEN TO START |
| | WITH A BASIS OF COORDINATION. |
| | |
| | C) PLEASE SEE THE LOCATION OF OVER RIDE DEVICES MUST BE |
| | LOCATED SO THAT THE PERSON/OCCUPANT WHICH IS |
| | CONTROLLING THE LIGHTING CAN VISUALLY SEE THE LIGHTING |
| | IN WHICH IS BEING CONTROLLED. THERE IS AN EXCEPTION FOR |
| | REQUIRED PILOT/INDICATOR LIGHTS WHICH IDENTIFY THE |
| | LIGHTING WHICH IS BEING CONTROLLED. 13-415.1.ABC.1.1, |
| | .1.2. |
| | |
| | D) PLEASE SEE TYPICAL NOTE #4 WHICH IS SHOWN AS CIRCLE |
| | NOTE FOR LIGHTING ON SHEETS FOR OVER RIDE CONTROL |
| | HOWEVER PLEASE INDICATE THE OVER RIDE TIME FOR THESE |
| | SAME DEVICES. |
| | EXAMPLE: SHEET E1.04LOWER RIGHT-HAND CORNER OF PLANS |
| | IN *PLAN NOTES* |
| | |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTE #7 WITH RESPECT TO |
| | INFORMATION REQUESTED FOR FIRE PUMP ETC. |
| | THE SPECS/CUT SHEETS FOR FIRE PUMP CONTROLLER WERE |
| | SUBMITTED HOWEVER THESE SHEETS DID NOT CONTAIN ANY |
| | ELECTRICAL INFORMATION AND DETAILS NEEDED FOR REVIEW TO |
| | COMPLY WITH NFPA-20 2003. |
| | PLEASE BE SURE TO SUBMIT COMPLETED SPECS FOR THE FIRE |
| | PUMP CONTROLLER WHICH IS DETAILED. PLEASE SEE BLANK |
| | SPACES FOR INFORMATION ALSO. |
| | PLEASE BE SURE MINIMUM FUEL CONSUMPTION IS PLACED ON |
| | PLANS. THIS WAS IN RESPONSE LETTER HOWEVER AS THE |
| | RESPONSE LETTERS ARE NOT PART OF THE LEGAL RECORD SETS |
| | OF PLANS, THISINFORMATION ON LETTERS NEEDS TO BE ON |
| | PLANS. |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN ELECTRICAL |
| | ROOM IS NOT PERMITTED. |
| | PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED |
| | SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN |
| | OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING |
| | OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE |
| | FPC IS NOT PERMITTED. |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR |
| | FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE |
| | SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND |
| | 10. |
| | PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR |
| | GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE |
| | GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE |
| | INFORMATION ON PLANS. |
| | |
| | 5) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #8 AND #9. |
| | PLEASE SEE THE ATS SPECS WERE SUBMITTED AND OK ALONG |
| | WITH THE 4-POLE TRANSFER SWITCH AS NOTED ON RISER WHICH |
| | IS ALSO OK. PLEASE KNOW HOWEVER THE REVISED NOTE ON |
| | RISER SHEET WHICH IS NOTE #8 AS PLAN NOTES MENTIONS THE |
| | NEUTRAL AND GROUND SHOULD NOT BE BONDED. PLEASE CLARIFY |
| | THIS AS THE ATS IS 4-POLE, WOULD THIS GENERATOR NOT BE |
| | A SEPARATELY DERIVED UNIT? |
| | PLEASE ADJUST NOTE AS BASED ON THE INFORMATION PROVIDED |
| | THIS WOULD BE A SD SYSTEM. |
| | PLEASE SEE 250.6, 250.66, 250.50, 250.20, ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE FOR REQUIRED EGRESS |
| | LIGHTING PER NFPA-101 7.8 AND 7.9. |
| | PLEASE SEE SOME OF THESE WERE SUBMITTED AND SHOWN |
| | HOWEVER NOT ALL. PLEASE SEE ALL EXIT EGRESS PATHS |
| | INCLUDING PATHS, EXIT AND EXIT DISCHARGE PATHS TO |
| | PUBLIC RIGHT OF WAY. |
| | THIS WOULD INCLUDE STAIRS ON THE EXTERIOR OF BUILDING |
| | WHICH IS STILL PART OF THE EXIT DISCHARGE. PLEASE SEE |
| | THERE ARE SEVERAL AREAS AROUND BUILDING WHICH CONTAINS |
| | THESE EGRESS PATHS AND STAIRS. FOR EXAMPLE THIS WOULD |
| | INCLUDE NORTH SIDE OF BUILDING WHICH HAS STAIRS, |
| | LOADING DOCK AREAS, SOUTH SIDE OF BUILDING ETC. PLEASE |
| | SEE THE STAIR LAYOUTS AS SHOWN ON THE ARCHITECTURAL |
| | SHEETS DO NOT CORRELATE WITH THE STAIRS ON THE |
| | ELECTRICAL (NORTHWEST STAIRS). |
| | PLEASE SEE THE RESPONSE MENTIONS A NOTE WAS ADDED ON |
| | PLANS FOR ALL EMERGENCY LIGHTING TO CONTAIN BATTERY |
| | BACK UP. |
| | THE FIRST ITEM IS THAT THIS REVIEWER DID NOT REQUESTED |
| | ALL EMERGENCY LIGHTING TO BE BATTERY BACKED UP AS |
| | STATED IN RESPONSE LETTER. |
| | THE SECOND ITEM IS THE FIXTURE LEGEND DID NOT CHANGE TO |
| | REFLECT ANY CHANGES TO STAIR, EGRESS PATH FIXTURES. |
| | PLEASE KNOW AS THIS BUILDING WILL REMAIN OCCUPIED UNDER |
| | GENERATOR POWER FOR NORMAL OPERATION, THE METHOD OF |
| | POWER BACK UP FOR ILLUMINATION OF EGRESS LIGHTING IS |
| | DETERMINED BY THE AHJ AS STATED IN LS101 7.8,7.9. |
| | 7.8.2.1. PLEASE KNOW THIS AHJ INCLUDING THE FIRE |
| | MARSHAL OFFICE ONLY REQUIRES THE EGRESS PATHS AND |
| | STAIRWELLS TO CONTAIN A BATTERY BACK UP FIXTURE FOR |
| | EMERGENCY USE AND FOR THE 1FT CANDLE MINIMUM AS |
| | REQUIRED. |
| | PLEASE ALSO CLARIFY THE DESIGNATION OF NL FOR WHAT |
| | APPEARS TO BE NIGHT LIGHTS FOR STAIRS. IF ONLY ONE OF |
| | THE TWO FIXTURES IN STAIRS ARE *NIGHT LIGHTS* HOW ARE |
| | THE OTHER BEING CONTROLLED. PLEASE BE SURE TO SEE |
| | NFPA-101. THE FOLLOWING IS EXTRACTED FROM THE LS CODE. |
| | *7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING |
| | SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, |
| | PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR |
| | FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET |
| | FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR |
| | IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA |
| | SERVED BY THE LIGHTING UNITS. * |
| | |
| | NOT ALL EMERGENCY LIGHTING AS SHOWN ON PLANS NEEDS TO |
| | BE BATTERY BACK UP AS THERE ARE A SUBSTANTIAL AMOUNT OF |
| | FIXTURES WHICH DO NOT SEEM TO BEREQUIRED FOR EGRESS |
| | LOCATIONS.(EXAMPLE, INDIVIDUAL OFFICES) THESE SEEM TO |
| | BE PART OF WHAT WOULD BE *OPTIONAL STAND-BY SYSTEMS)? |
| | IF THERE ARE ANY ITEMS WHICH ARE NOT PART OF EMERGENCY |
| | REQUIRED OR LEGALLY REQUIRED SYSTEMS, THEN THESE |
| | OPTIONAL STANDBY MAY NOT BE FED THROUGH THE SAME |
| | TRANSFER SWITCH. 700.6D, 701.10, 701.6 |
| | PLEASE CALL TO GO OVER THESE ITEMS. |
| | PLEASE KNOW AS THE LIGHTING LEVELS ARE NOT COMPLETED AT |
| | THIS TIME PLEASE CALL TO GO OVER THESE |
| | |
| | 7) NOTE:PLEASE SEE PREVIOUS NOTE #13 WITH RESPECT TO |
| | THE IT ROOM AND REQUIRED EPO. THE RESPONSE MENTIONS TO |
| | SEE DETAIL AND DETAIL WAS LOCATED HOWEVER THE ACTUAL |
| | LOCATION COULD NOT BE LOCATED ON PLANS AT DOOR WAY |
| | LEAVING SPACE. |
| | PLEASE SHOW. |
| | PLEASE PROVIDE THE ENLARGE LAYOUT OF ROOM AND |
| | EQUIPMENT. PLEASE SEE 110.26 FOR REQUIRED CLEARANCES |
| | ALONG WITH POSSIBLE REQUIREMENTS FROM MANUFACTURE. |
| | |
| | 8) NOTE: PLEASE CLARIFY DISCONNECTS SHOWN FOR THE |
| | CHILLER PLANT CIRCUITS. THESE SEEM TO BE NOTED TO |
| | ECBRP-1 AND ECBRP-2, YET THE PLANS SHOWS DSRP-1 AND |
| | DSRP-2, ARE THESE THE SAME UNITS?THIS IS ASSUMED |
| | HOWEVER NOT 100% KNOWN AT THIS TIME. |
| | 440.11, 110.26, 225.32 |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTE # 26 WITH RESPECT TO |
| | CLARIFICATION FOR CONTINUOUS LOADS AT 125%. THE |
| | RESPONSE LETTER MENTIONS THESE WERE TAKEN INTO |
| | CONSIDERATION HOWEVER THIS WOULD NEED TO BE SHOWN OR |
| | NOTED ON PLANS. |
| | 215.3,230.42, ETC |
| | PLEASE ADJUST. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #28 WITH RESPECT TO |
| | BRANCH CIRCUITING CONDUCTORS. THE REVIEW NOTE EVEN |
| | MENTIONED THIS WAS NOT TO INCLUDE THE CONDUCTORS ON THE |
| | RISER SHEET HOWEVER THE RESPONSE LETTER SPECIFICALLY |
| | MENTIONS TO SEE THE CONDUCTOR TABLE ON RISER SHEET |
| | E3.01. |
| | THE COMMENT WAS FOR CONDUCTORS ON PANEL SCHEDULES WHICH |
| | ARE NOT ON RISER. IF THESE ARE TYPICAL THEN THIS CAN BE |
| | INDICATED HOWEVER THE BRANCH CIRCUIT CONDUCTORS WHICH |
| | ARE REQUIRED TO TAKE VOLTAGE DROP INTO CONSIDERATION IS |
| | TO BE STATED ON PANELS/PLANS. |
| | PLEASE SEE FBC 13-413.1ABC.1 FOR VD FOR THE ENERGY |
| | CODE. |
| | PLEASE SEE THAT 310.16, 240.4 ETC CAN NOT BE CONFIRMED |
| | FOR BRANCH CIRCUITS. |
| | DIVISION 16 SPECS ARE NOT PART OF THE RECORD PLANS TO |
| | SHOW THIS. |
| | FBC106.3.5.1.2, 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS NOTE #35 AND AS NOTED |
| | ABOVE FOR NOTE #9, PLEASE ADJUST NOTES/LOADS |
| | ACCORDINGLY. |
| | PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE EMERGENCY |
| | STAND-BY POWER. |
| | 220, 700,701 |
| | |
| | 12) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES FOR |
| | BUILDING WHICH REQUESTED THE STATEMENT REQUIRED ON |
| | PLANS FOR THRESHOLD BUILDINGS BE PLACED ON PLANS FOR |
| | ARCHITECTURAL, ENGINEERING ETC. THIS STATEMENT WAS |
| | ADDED TO A-SHEETS HOWEVER NOT FOR TRADES. |
| | THIS IS BEING NOTED AT THIS TIME BY ELECTRICAL REVIEWER |
| | FOR INFORMATION TO THE MEP DESIGNER. THE INFORMATION |
| | FROM THE BUILDING PLAN REVIEW NOTES MAY NOT HAVE BEEN |
| | GIVEN TO THE MEP DESIGNER FOR THIS. PLEASE SEE WORDING |
| | FOR STATEMENT BELOW: |
| | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 OF THE FLORIDA STATUTES". |
| | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| | PLANS. |
| | |
| | 13) NOTE: PLEASE BE SURE TO SUBMIT MANUFACTURE |
| | SPECS/CUT SHEETS ON THE OUTDOOR/ ABOVE GROUND FUEL |
| | TANK. THIS IS GIVEN AS INFORMATION ONLY AS THE |
| | MECHANICAL REVIEW ALONG WITH REVIEW FROM FIRE MARSHAL, |
| | ZONING AND OTHER TRADES. |
| | AS SEVERAL OTHER SHEETS INCLUDING SITE PLANS, LANDSCAPE |
| | ETC DO NOT SHOW THIS ABOVE GROUND TANK, THIS |
| | INFORMATION WILL BE FORWARDED TO THE OTHER TRADES FOR |
| | REVIEW. |
| | |
| | 14) NOTE: PLEASE PROVIDE INFORMATION ON ANY LOCATIONS |
| | PER NEC 517.13, 517.17. |
| | THIS WAS NOT NOTED ON PREVIOUS REVIEW, HOWEVER IT HAS |
| | COME TO THE ATTENTION THAT SOME OF THESE LOCATIONS MAY |
| | BE AREAS DESIGNATED IN THE SCOPE OF WORK WITH NEC 517. |
| | |
| | ** REMAIN AS NOTED FOR INFORMATION: |
| | NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE |
| | UNDER A SEPARATE PERMIT. |
| | PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE |
| | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE |
| | INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER |
| | NFPA-101 7.2.1, 7.2.1.6.2. |
| | |
| | ** REMAIN AS NOTED FOR INFORMATION: PLEASE KNOW THAT |
| | ALL OTHER LOW VOLTAGE SYSTEMS SUCH AS VOICE, DATA, |
| | CATV, PHONE ETC WILL BE REQUIRED TO BE UNDER SEPARATE |
| | PERMIT. THESE PLANS MAY BE USED AND REFERENCE FOR A |
| | *TURN-AROUND* PERMIT HOWEVER SEPARATE PERMIT IS |
| | REQUIRED ALONG WITH FEES FOR THIS VALUATION. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS |
| | OFFICE/REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-10-03 16:55:04 | 2007-10-03 16:55:04 |
| | |
| | REVIEW COMPLETED, NOTES TO FOLLOW |
| 2007-09-30 14:16:53 | 2007-09-30 14:16:53 |
| | |
| | ONE ROLL OF PLANS AND ONE SET OF SPECS/SUBMITTALS IN |
| | ELECTRICAL FOR REVIEW. |