Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop E
Sequence Number 2
Notes
Date Text
2007-10-04 10:11:59 
 *** DENIED 2ND REVIEW ***
  
 PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM PREVIOUS
 REVIEW WHICH NEEDS TO BE ADDRESSED.
 ** PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS BASED ON
 CHANGES ON PLANS AND INFORMATION ONLY NOW SUBMITTED FOR
 REVIEW.
 THE PREVIOUS REVIEW DID NOTE THAT DUE TO INFORMATION
 NOT SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS.
  
 1) NOTE: ONCE AGAIN: PLEASE KNOW THAT PLANS HAVE ONLY
 BEEN SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE
 COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS
 AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE
 VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME
 OF APPLICATION.
  
 2) NOTE: PLEASE SEE NOTE #5 FROM PREVIOUS REVIEW WHICH
 GAVE ALL CODES RELEVANT FOR THIS ELECTRICAL REVIEWER TO
 BE ON PLANS. THESE WERE ADJUSTED AND CORRECTED ON MOST
 SHEETS HOWEVER PLEASE SEE FP0.01 WHICH STILL INDICATES
 THE 2002 NFPA-70 AND THE 1999 NFPA-20.
 PLEASE ADJUST THESE TO THE 2005 NFPA-70 AND 2003 NFPA.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #6 WITH RESPECT TO
 FBC CHAPTER 13. PLEASE SEE THERE ARE STILL SOME ITEMS
 WHICH NEED TO BE ADDRESSED. 13-415.1.AB.1.1, 13-415.2,
 13-415
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED WHICH
 STILL NEED TO BE SIGNED, DATED AND SEALED ON THE
 CERTIFICATION SHEET.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED STILL
 NEED TO CORRELATE WITH PLANS. ALL LIGHTING INFORMATION
 WHICH IS PLACED ON THE INPUT DATA REPORT NEEDS TO
 COORDINATE WITH ALL LIGHTING AS SHOWN ON PLANS. PLEASE
 SEE ALL REFERENCES TO THE INPUT DATA REPORT BELOW WILL
 BE NOTED AS IDR.
 A) PLEASE BE SURE ALL EXTERIOR LIGHTING FIXTURES WHICH
 ARE ON PLANS COORDINATE WITH THE IDR.
 FOR EXAMPLE, THE IDR ONLY INDICATES THREE TYPES AND
 WATTAGES YET PLANS INDICATE MORE FIXTURES WHICH ARE NOT
 FIGURED. PLEASE SEE FIXTURES J, K, K1 ETC. ALL EXTERIOR
 LIGHTING.
  
 B) PLEASE SEE ALL LIGHTING ON PLANS FOR INTERIOR
 LIGHTING NEEDS TO COORDINATE WITH THE IDR FOR LIGHTING
 WATTAGES, TYPES, NUMBER OF FIXTURES ALONG WITH METHOD
 OF CONTROLS.
 FOR EXAMPLE, PLEASE SEE SEVERAL FIXTURES WHICH ARE ON
 THE PLANS AND FIXTURE LEGEND WHICH ARE NOT ON THE
 CALCULATIONS IDR. FIXTURES V, L2, F2, L1, T, ETC.
  
 ** AS NOTED ABOVE PLEASE GO OVER ALL FIXTURES AND KNOW
 THAT THESE ARE ONLY A COUPLE OF EXAMPLES GIVEN TO START
 WITH A BASIS OF COORDINATION.
  
 C) PLEASE SEE THE LOCATION OF OVER RIDE DEVICES MUST BE
 LOCATED SO THAT THE PERSON/OCCUPANT WHICH IS
 CONTROLLING THE LIGHTING CAN VISUALLY SEE THE LIGHTING
 IN WHICH IS BEING CONTROLLED. THERE IS AN EXCEPTION FOR
 REQUIRED PILOT/INDICATOR LIGHTS WHICH IDENTIFY THE
 LIGHTING WHICH IS BEING CONTROLLED. 13-415.1.ABC.1.1,
 .1.2.
  
 D) PLEASE SEE TYPICAL NOTE #4 WHICH IS SHOWN AS CIRCLE
 NOTE FOR LIGHTING ON SHEETS FOR OVER RIDE CONTROL
 HOWEVER PLEASE INDICATE THE OVER RIDE TIME FOR THESE
 SAME DEVICES.
 EXAMPLE: SHEET E1.04LOWER RIGHT-HAND CORNER OF PLANS
 IN *PLAN NOTES*
  
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #7 WITH RESPECT TO
 INFORMATION REQUESTED FOR FIRE PUMP ETC.
 THE SPECS/CUT SHEETS FOR FIRE PUMP CONTROLLER WERE
 SUBMITTED HOWEVER THESE SHEETS DID NOT CONTAIN ANY
 ELECTRICAL INFORMATION AND DETAILS NEEDED FOR REVIEW TO
 COMPLY WITH NFPA-20 2003.
 PLEASE BE SURE TO SUBMIT COMPLETED SPECS FOR THE FIRE
 PUMP CONTROLLER WHICH IS DETAILED. PLEASE SEE BLANK
 SPACES FOR INFORMATION ALSO.
 PLEASE BE SURE MINIMUM FUEL CONSUMPTION IS PLACED ON
 PLANS. THIS WAS IN RESPONSE LETTER HOWEVER AS THE
 RESPONSE LETTERS ARE NOT PART OF THE LEGAL RECORD SETS
 OF PLANS, THISINFORMATION ON LETTERS NEEDS TO BE ON
 PLANS.
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN ELECTRICAL
 ROOM IS NOT PERMITTED.
 PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED
 SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN
 OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING
 OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE
 FPC IS NOT PERMITTED.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR
 FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE
 SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND
 10.
 PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR
 GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE
 GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE
 INFORMATION ON PLANS.
  
 5) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES #8 AND #9.
 PLEASE SEE THE ATS SPECS WERE SUBMITTED AND OK ALONG
 WITH THE 4-POLE TRANSFER SWITCH AS NOTED ON RISER WHICH
 IS ALSO OK. PLEASE KNOW HOWEVER THE REVISED NOTE ON
 RISER SHEET WHICH IS NOTE #8 AS PLAN NOTES MENTIONS THE
 NEUTRAL AND GROUND SHOULD NOT BE BONDED. PLEASE CLARIFY
 THIS AS THE ATS IS 4-POLE, WOULD THIS GENERATOR NOT BE
 A SEPARATELY DERIVED UNIT?
 PLEASE ADJUST NOTE AS BASED ON THE INFORMATION PROVIDED
 THIS WOULD BE A SD SYSTEM.
 PLEASE SEE 250.6, 250.66, 250.50, 250.20, ETC
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE FOR REQUIRED EGRESS
 LIGHTING PER NFPA-101 7.8 AND 7.9.
 PLEASE SEE SOME OF THESE WERE SUBMITTED AND SHOWN
 HOWEVER NOT ALL. PLEASE SEE ALL EXIT EGRESS PATHS
 INCLUDING PATHS, EXIT AND EXIT DISCHARGE PATHS TO
 PUBLIC RIGHT OF WAY.
 THIS WOULD INCLUDE STAIRS ON THE EXTERIOR OF BUILDING
 WHICH IS STILL PART OF THE EXIT DISCHARGE. PLEASE SEE
 THERE ARE SEVERAL AREAS AROUND BUILDING WHICH CONTAINS
 THESE EGRESS PATHS AND STAIRS. FOR EXAMPLE THIS WOULD
 INCLUDE NORTH SIDE OF BUILDING WHICH HAS STAIRS,
 LOADING DOCK AREAS, SOUTH SIDE OF BUILDING ETC. PLEASE
 SEE THE STAIR LAYOUTS AS SHOWN ON THE ARCHITECTURAL
 SHEETS DO NOT CORRELATE WITH THE STAIRS ON THE
 ELECTRICAL (NORTHWEST STAIRS).
 PLEASE SEE THE RESPONSE MENTIONS A NOTE WAS ADDED ON
 PLANS FOR ALL EMERGENCY LIGHTING TO CONTAIN BATTERY
 BACK UP.
 THE FIRST ITEM IS THAT THIS REVIEWER DID NOT REQUESTED
 ALL EMERGENCY LIGHTING TO BE BATTERY BACKED UP AS
 STATED IN RESPONSE LETTER.
 THE SECOND ITEM IS THE FIXTURE LEGEND DID NOT CHANGE TO
 REFLECT ANY CHANGES TO STAIR, EGRESS PATH FIXTURES.
 PLEASE KNOW AS THIS BUILDING WILL REMAIN OCCUPIED UNDER
 GENERATOR POWER FOR NORMAL OPERATION, THE METHOD OF
 POWER BACK UP FOR ILLUMINATION OF EGRESS LIGHTING IS
 DETERMINED BY THE AHJ AS STATED IN LS101 7.8,7.9.
 7.8.2.1. PLEASE KNOW THIS AHJ INCLUDING THE FIRE
 MARSHAL OFFICE ONLY REQUIRES THE EGRESS PATHS AND
 STAIRWELLS TO CONTAIN A BATTERY BACK UP FIXTURE FOR
 EMERGENCY USE AND FOR THE 1FT CANDLE MINIMUM AS
 REQUIRED.
 PLEASE ALSO CLARIFY THE DESIGNATION OF NL FOR WHAT
 APPEARS TO BE NIGHT LIGHTS FOR STAIRS. IF ONLY ONE OF
 THE TWO FIXTURES IN STAIRS ARE *NIGHT LIGHTS* HOW ARE
 THE OTHER BEING CONTROLLED. PLEASE BE SURE TO SEE
 NFPA-101. THE FOLLOWING IS EXTRACTED FROM THE LS CODE.
 *7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS. *
  
 NOT ALL EMERGENCY LIGHTING AS SHOWN ON PLANS NEEDS TO
 BE BATTERY BACK UP AS THERE ARE A SUBSTANTIAL AMOUNT OF
 FIXTURES WHICH DO NOT SEEM TO BEREQUIRED FOR EGRESS
 LOCATIONS.(EXAMPLE, INDIVIDUAL OFFICES) THESE SEEM TO
 BE PART OF WHAT WOULD BE *OPTIONAL STAND-BY SYSTEMS)?
 IF THERE ARE ANY ITEMS WHICH ARE NOT PART OF EMERGENCY
 REQUIRED OR LEGALLY REQUIRED SYSTEMS, THEN THESE
 OPTIONAL STANDBY MAY NOT BE FED THROUGH THE SAME
 TRANSFER SWITCH. 700.6D, 701.10, 701.6
 PLEASE CALL TO GO OVER THESE ITEMS.
 PLEASE KNOW AS THE LIGHTING LEVELS ARE NOT COMPLETED AT
 THIS TIME PLEASE CALL TO GO OVER THESE
  
 7) NOTE:PLEASE SEE PREVIOUS NOTE #13 WITH RESPECT TO
 THE IT ROOM AND REQUIRED EPO. THE RESPONSE MENTIONS TO
 SEE DETAIL AND DETAIL WAS LOCATED HOWEVER THE ACTUAL
 LOCATION COULD NOT BE LOCATED ON PLANS AT DOOR WAY
 LEAVING SPACE.
 PLEASE SHOW.
 PLEASE PROVIDE THE ENLARGE LAYOUT OF ROOM AND
 EQUIPMENT. PLEASE SEE 110.26 FOR REQUIRED CLEARANCES
 ALONG WITH POSSIBLE REQUIREMENTS FROM MANUFACTURE.
  
 8) NOTE: PLEASE CLARIFY DISCONNECTS SHOWN FOR THE
 CHILLER PLANT CIRCUITS. THESE SEEM TO BE NOTED TO
 ECBRP-1 AND ECBRP-2, YET THE PLANS SHOWS DSRP-1 AND
 DSRP-2, ARE THESE THE SAME UNITS?THIS IS ASSUMED
 HOWEVER NOT 100% KNOWN AT THIS TIME.
 440.11, 110.26, 225.32
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE # 26 WITH RESPECT TO
 CLARIFICATION FOR CONTINUOUS LOADS AT 125%. THE
 RESPONSE LETTER MENTIONS THESE WERE TAKEN INTO
 CONSIDERATION HOWEVER THIS WOULD NEED TO BE SHOWN OR
 NOTED ON PLANS.
 215.3,230.42, ETC
 PLEASE ADJUST.
 FBC 106.1.2, 106.3.5.1.2
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #28 WITH RESPECT TO
 BRANCH CIRCUITING CONDUCTORS. THE REVIEW NOTE EVEN
 MENTIONED THIS WAS NOT TO INCLUDE THE CONDUCTORS ON THE
 RISER SHEET HOWEVER THE RESPONSE LETTER SPECIFICALLY
 MENTIONS TO SEE THE CONDUCTOR TABLE ON RISER SHEET
 E3.01.
 THE COMMENT WAS FOR CONDUCTORS ON PANEL SCHEDULES WHICH
 ARE NOT ON RISER. IF THESE ARE TYPICAL THEN THIS CAN BE
 INDICATED HOWEVER THE BRANCH CIRCUIT CONDUCTORS WHICH
 ARE REQUIRED TO TAKE VOLTAGE DROP INTO CONSIDERATION IS
 TO BE STATED ON PANELS/PLANS.
 PLEASE SEE FBC 13-413.1ABC.1 FOR VD FOR THE ENERGY
 CODE.
 PLEASE SEE THAT 310.16, 240.4 ETC CAN NOT BE CONFIRMED
 FOR BRANCH CIRCUITS.
 DIVISION 16 SPECS ARE NOT PART OF THE RECORD PLANS TO
 SHOW THIS.
 FBC106.3.5.1.2, 106.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #35 AND AS NOTED
 ABOVE FOR NOTE #9, PLEASE ADJUST NOTES/LOADS
 ACCORDINGLY.
 PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE EMERGENCY
 STAND-BY POWER.
 220, 700,701
  
 12) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES FOR
 BUILDING WHICH REQUESTED THE STATEMENT REQUIRED ON
 PLANS FOR THRESHOLD BUILDINGS BE PLACED ON PLANS FOR
 ARCHITECTURAL, ENGINEERING ETC. THIS STATEMENT WAS
 ADDED TO A-SHEETS HOWEVER NOT FOR TRADES.
 THIS IS BEING NOTED AT THIS TIME BY ELECTRICAL REVIEWER
 FOR INFORMATION TO THE MEP DESIGNER. THE INFORMATION
 FROM THE BUILDING PLAN REVIEW NOTES MAY NOT HAVE BEEN
 GIVEN TO THE MEP DESIGNER FOR THIS. PLEASE SEE WORDING
 FOR STATEMENT BELOW:
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 13) NOTE: PLEASE BE SURE TO SUBMIT MANUFACTURE
 SPECS/CUT SHEETS ON THE OUTDOOR/ ABOVE GROUND FUEL
 TANK. THIS IS GIVEN AS INFORMATION ONLY AS THE
 MECHANICAL REVIEW ALONG WITH REVIEW FROM FIRE MARSHAL,
 ZONING AND OTHER TRADES.
 AS SEVERAL OTHER SHEETS INCLUDING SITE PLANS, LANDSCAPE
 ETC DO NOT SHOW THIS ABOVE GROUND TANK, THIS
 INFORMATION WILL BE FORWARDED TO THE OTHER TRADES FOR
 REVIEW.
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON ANY LOCATIONS
 PER NEC 517.13, 517.17.
 THIS WAS NOT NOTED ON PREVIOUS REVIEW, HOWEVER IT HAS
 COME TO THE ATTENTION THAT SOME OF THESE LOCATIONS MAY
 BE AREAS DESIGNATED IN THE SCOPE OF WORK WITH NEC 517.
  
 ** REMAIN AS NOTED FOR INFORMATION:
 NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
 PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE
 INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER
 NFPA-101 7.2.1, 7.2.1.6.2.
  
 ** REMAIN AS NOTED FOR INFORMATION: PLEASE KNOW THAT
 ALL OTHER LOW VOLTAGE SYSTEMS SUCH AS VOICE, DATA,
 CATV, PHONE ETC WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMIT. THESE PLANS MAY BE USED AND REFERENCE FOR A
 *TURN-AROUND* PERMIT HOWEVER SEPARATE PERMIT IS
 REQUIRED ALONG WITH FEES FOR THIS VALUATION.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE/REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-10-03 16:55:042007-10-03 16:55:04
  
 REVIEW COMPLETED, NOTES TO FOLLOW
2007-09-30 14:16:532007-09-30 14:16:53
  
 ONE ROLL OF PLANS AND ONE SET OF SPECS/SUBMITTALS IN
 ELECTRICAL FOR REVIEW.