2007-10-21 09:24:52PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING
 BUILDING PLAN REVIEW
 PERMIT: 07050361
 ADD: 800 CLEMATIS ST
 CONT: THE MORGANTI GROUP, INC*PLAN REVIEW ONLY*
 TEL: (561)262-6771
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING TYPE;IB
 2NDREVIEW- PLAN REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME
 REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE
 2004 FBC BUILDING WITH THE2007 REVISIONS.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2-3) COMPLIED.
  
 4) COMPLIED 12-20-07 SENT TO HAROLD PISKURA!!!
 2ND REQUEST, THE THRESHOLD INSPECTOR WILL NEED PRESENT
 SIGNED THRESHOLD DOCUMENTS AND SUBMIT THEM TO ASSISTANT
 BUILDING OFFICIAL HAROLD PISKURA BEFORE THIS COMMENT
 WILL BE COMPLIED WITH. WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. CONTACT HAROLD PISKURA MANAGER
 OF THE SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR
 FURTHER INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 5-6) COMPLIED.
  
 7) NOTE TO CONTRACTOR : 109.3.10* IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO CONSENT BY THE APPLICABLE PROPERTY
 OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE
 FLOWS SERVING ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH ENGINEERING
 STANDARDS TO PRESERVE THE POSITIVE PATTERNS OF THE
 AFFECTED SITES. ACCORDINGLY, DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL DEVELOPMENT,
 INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 8) NOTE TO CONTRACTOR: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAIL TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 9-10) COMPLIED.
  
 11A) 2ND REQUEST, THIS COMMENT WAS ONLY PARTIALLY
 COMPLIED WITH YES A SURVEY IS PRESENT BUT NOT
 INCORPORATED INTO THE SET OF PLANS. THE REAL ISSUE IS
 THE PROPERTY LINE ON THE WEST BUILDING LINE OR WITHIN
 10'-0 OF THE BUILDING LINE. PLEASE PROVIDE SOME
 CLARIFICATION. A UNITY OF TITLE MAY ALSO BE REQUIRED
 PLUS AN ABANDONMENT OF AN EASEMENT. TABLE 601, TABLE
 602 AND TABLE 704.8.
  
 11B) THE SURVEY PROVIDED INDICATES THIS PROPERTY IS IN
 A A-9 FLOOD ZONE THIS PROPERTY IS LOCATED PARTIALLY IN
 A B&C FLOOD ZONE MAKING A **B** FLOOD ZONE. PLEASE HAVE
 THE SURVEY CORRECTED AS WELL AS THE CIVIL SHEET# 4.
  
 12-14) COMPLIED.
  
 15A)2ND REQUEST, THE CODE IS CLEAR WHERE A CHANGE OF
 ELEVATION OF 12 INCHES OR LESS IN THIS CASE AN EXIT
 DISCHARGE A RAMP SHALL BE PROVIDED. SHEET A2.00DETAIL#
 2, 1003.5.2.WHERE CHANGE IN ELEVATION OF 12 INCHES (305
 MM) OR LESS OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND
 EXIT DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL
 BE PROVIDED. 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF
 EGRESS NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY
 A STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 15B) NEW COMMENT DEALS WITH WHAT I BELIEVED TO BE A
 RAMP ON THE EAST SIDE OF THE BUILDING THAT LEAD TO THE
 ACCESSIBLE PARKING. SHEET A- 2.00, TOP DETAIL INDICATES
 A ELEVATION MARKER OF24.25' SEE CIVIL PLANS C-4 THEY
 ALSO APPEAR TO INDICATE A RETAINING WALL AND NOT A RAMP
 ON THE EAST SIDE OF THE BUILDING MAKING THE ACCESSIBLE
 PARKING NOT THE CLOSEST PATH OF TRAVEL.PLEASE REVIEW TO
 SEE IF THIS IS SUPPOSE TO BE A RAMP OR A ELEVATED
 WALKWAY.
  
 16-21) COMPLIED.
  
 22A) 2ND REQUEST, DEALS WITH THE LOCATION OF THE OVER
 FLOW SCUPPERS IN RELATION SHIP TO THE MAIN ROOF DRAINS.
 THE THANK YOU FOR PROVIDING THE HIGH AND LOW POINTS OF
 THE ROOF ELEVATIONS. THE PLANS INDICATE IN MANY AREAS
 OF THE ROOFTHE CURRENT HIGH POINT WOULD ALLOW FOR
 6.25 INCHES OF PONDINGBEFORE WATER WOULD START TO RUN
 OUT THE EMERGENCY OVERFLOW SCUPPERS. THERE IS 2 POINTS
 OF VIEW ON THIS CODE SECTION THE FIRST IS THAT THE
 SCUPPERS ARE TO BE 2-4 INCHES OFF THE ROOF LEVEL AT THE
 PARAPET AND THE SECOND DEALS WITH THE AMOUNT OF WATER
 (DEPTH) THAT WILL BE ON THE ROOF BEFORE THE WATER
 REACHES THE OVERFLOW SCUPPERS AND STARTS TO RUN OUT.
  
 IF THE FIRST CASEIS LOOKED AT WHICH REFLECTS THIS
 PLAN YOU WILL HAVE TRULY 6.25 INCHES OF WATER PONDING
 ON THE ROOF, PLUS THE DEFLECTION FACTOR TO BE TAKEN
 INTO ACCOUNT. PLEASE PROVIDE CALCULATIONS FOR THIS
 WEIGHT FACTOR IN THE LARGEST AREA TO BE SERVED BY ANY
 ROOF DRAIN.
 ROOF PLAN AND THE EMERGENCY OVER FLOW SCUPPERS,
 INDICATE THE SLOPE TO BE
 ?? IN 1?-0?WHENEVER THE OVERFLOW SCUPPERS ARE
 LOCATED MORE THAN 16?-0? AWAY FROM THE MAIN ROOF DRAIN
 IN SITUATIONSWHERE IN HEAVY DOWN POURS THE MAIN DRAIN
 CAN NOT TAKE ANY MORE WATER THERE IS TO BE NO MORE THAN
 4 INCHES OF WATER ON THE ROOF DECK.
 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 22B-C) COMPLIED.
  
 23) COMPLIED.
  
  
 24) 2ND REQUEST, SHEET A2.08 WINDOWS IN FIRE RATED
 PARTITIONS, SHOW COMPLIANCE WITH TABLE 715.4 AND 715.4
 AS WELL AS NFPA 80. PROVIDE NOT ONLY INFORMATION ON
 GLAZING BUT THE FRAME AS WELL. THE RESPONSE WAS TO SEE
 DRAWINGS A2.08 FOR CORRECTIONS.
  
 25) COMPLIED.
  
 26) 2ND REQUEST, DEALS WITH ELEVATOR REQUIREMENTS FOR
 STRETCHERS FOR ELEVATORS IN BUILDINGS 4 STORIES AND
 MORE, NOT BECAUSE OF POSSIBLY BEING A MEDICAL FACILITY.
 SHEET A4.03.2
 26A)PROVIDE INFORMATION FOR ELEVATOR CAR TO
 ACCOMMODATE AMBULANCE STRETCHERS.3002.4.
  
 26B) PLEASE PROVIDE THE ELEVATOR MACHINE ROOM?S SMOKE
 DETECTOR AND HOIST WAY WOULD BE LOCATED IN THE
 PLANS?3002.8. SHEET A6.01 AND DO NOT SHOW THEM.
  
 26C) PLEASE PROVIDE THE FOLLOWING INFORMATION: 3003.1
 STANDBY POWER.
 IN BUILDINGS AND STRUCTURES WHERE STANDBY POWER IS
 REQUIRED OR FURNISHED TO OPERATE AN ELEVATOR, THE
 OPERATION SHALL BE IN ACCORDANCE WITH SECTIONS 3003.1.1
 THROUGH 3003.1.4 .
 3003.1.1 MANUAL TRANSFER.
 STANDBY POWER SHALL BE MANUALLY TRANSFERABLE TO ALL
 ELEVATORS IN EACH BANK.
 3003.1.2 ONE ELEVATOR.
 WHERE ONLY ONE ELEVATOR IS INSTALLED, THE ELEVATOR
 SHALL AUTOMATICALLY TRANSFER TO STANDBY POWER WITHIN 60
 SECONDS AFTER FAILURE OF NORMAL POWER.
 3003.1.3 TWO OR MORE ELEVATORS.
 WHERE TWO OR MORE ELEVATORS ARE CONTROLLED BY A COMMON
 OPERATING SYSTEM, ALL ELEVATORS SHALL AUTOMATICALLY
 TRANSFER TO STANDBY POWER WITHIN 60 SECONDS AFTER
 FAILURE OF NORMAL POWER WHERE THE STANDBY POWER SOURCE
 IS OF SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT
 THE SAME TIME. WHERE THE STANDBY POWER SOURCE IS NOT OF
 SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT THE
 SAME TIME, ALL ELEVATORS SHALL TRANSFER TO STANDBY
 POWER IN SEQUENCE, RETURN TO THE DESIGNATED LANDING AND
 DISCONNECT FROM THE STANDBY POWER SOURCE. AFTER ALL
 ELEVATORS HAVE BEEN RETURNED TO THE DESIGNATED LEVEL,
 AT LEAST ONE ELEVATOR SHALL REMAIN OPERABLE FROM THE
 STANDBY POWER SOURCE.
 3003.1.4 VENTING.
 WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE
 MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE
 CONNECTED TO THE STANDBY POWER SOURCE.
 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION. ELEVATORS
 SHALL BE PROVIDED WITH PHASE I EMERGENCY RECALL
 OPERATION AND PHASE II EMERGENCY IN-CAR OPERATION IN
 ACCORDANCE WITH ASME A17.1.
  
 26D) 3004.2 LOCATION OF VENTS. VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF THE HOIST WAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR
 THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR.
 NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT PORTIONS OF THE
 DUCTS LOCATED OUTSIDE THE HOIST WAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE
 PROTECTION RATING REQUIRED FOR THE HOIST WAY. HOLES IN
 THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51
 MM) OF CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS. EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL NOT BE LESS THAN
 3? PERCENT OF THE AREA OF THE HOIST WAY NOR LESS THAN 3
 SQUARE FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT
 LESS THAN 3? PERCENT NOR LESS THAN 0.5 SQUARE FOOT
 (0.047 M 2 ) FOR EACH DUMBWAITER CAR IN THE HOIST WAY,
 WHICHEVER IS GREATER. OF THE TOTAL REQUIRED VENT AREA,
 NOT LESS THAN ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON DETECTION OF
 SMOKE FROM ANY OF THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 26E) PLEASE NOTE THE FOLLOWING: 3006.5 SHUNT TRIP.
 WHERE ELEVATOR HOIST WAYS OR ELEVATOR MACHINE ROOMS
 CONTAINING ELEVATOR CONTROL EQUIPMENT ARE PROTECTED
 WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED IN
 ACCORDANCE WITH NFPA 72, SECTION 3?9.4, ELEVATOR
 SHUTDOWN, SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY
 THE MAIN LINE POWER SUPPLY TO THE AFFECTED ELEVATOR
 PRIOR TO THE APPLICATION OF WATER. THIS MEANS SHALL NOT
 BE SELF-RESETTING. THE ACTIVATION OF SPRINKLERS OUTSIDE
 THE HOIST WAY OR MACHINE ROOM SHALL NOT DISCONNECT THE
 MAIN LINE POWER SUPPLY.
  
 26F) PLEASE NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1
 ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC
 ELEVATOR CYLINDERS.
 ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE
 CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT
 TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL
 CYLINDER AND GROUND CATHODE.
 1.THE PLASTIC CASING SHALL BE CAPPED AT THE
 BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED
 TO ENSURE WATER TIGHTNESS.
 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF
 POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC
 PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH
 (3.175 MM).
 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A
 MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS
 BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE
 PROTECTIVE PLASTIC CASING.
 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS
 SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE
 EXISTING PHYSICAL DIMENSIONS PERMIT
  
 27-29) COMPLIED.
  
 30) SHEET S-7/ S-13
  
 30A) COMPLIED.
  
 30B) COMPLIED.
  
 30C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 30D) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) TRAINER GLASS CURTAIN WALL LMI ,HIGHLIGHT WHICH
 GLAZING TYPE WILL BE USED, AND MULLIONS. SEE SHEET 2 OF
 14 TOP OF CHART IS CUT OFF !!!!!! 2ND REQUEST!!!!!B)
 TRAINER GLASS CURTAIN WALL SMI-, HIGHLIGHT WHICH
 GLAZING TYPE TO
  
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE
 ANCHORING INTO MASONRY AND STEEL
 SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS
 UNDER THE 2004 USUALLY INDICATE NO
 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1.
  
 D) YKK AP 35H OUT SWING ALUMINUM DOORLMI, ,NOTE THIS
 REPORT REQUIRES THE DESIGN PRESSURES TO BE DIVIDED BY
 1.33, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLE REPORTS.
  
 E)COMPLIED. FIREDOOR 8080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.
  
 F)COMPLIED. FIREDOOR 8080 SERIES OUT SWING STEEL LOUVER
 COMMERCIAL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE
 FACTOR MEETS WIND LOADS
  
 G)COMPLIED.FIREDOOR 4080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.,
  
 H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL
 AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION
 ?C? CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FORWIND LOADS
  
 I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR,
 CURRENTLY DOES NOT MEET THE REQUIRED PRESSURES. ,
 SUBSECTION **C** CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT
 MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR
 STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE
 IMPORTANCE FACTOR IS ADJUSTED TO 1.15TO BE DETERMINED
 BY THE DESIGN PROFESSIONAL.
  
 J) RUSKIN LOUVER SERIES ELF6375DXD , AS INDICATED WITH
 THE PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT
 , SUBSECTION **C** CALCULATIONS INDICATE THAT THE
 CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC
 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS 30)
 SHEET S-7
 30A) CODES AND STANDARDS ASCE 7-02 THE BUILDING
 CATEGORY II WITH AN IMPORTANCE FACTOR OF 1.0. IS THIS
 BUILDING TO BE USED AS A HEALTH CARE FACILITY THAT MAY
 EVER HAVE SURGERY OR BE USED FOR EMERGENCY TREATMENT?
 IF SO THIS BUILDING CATEGORY WOULD BE A IV WITH AN
 IMPORTANCE FACTOR OF 1.15. THE PRESSURE ZONES ON S-13
 WILL CHANGE WITH THE 1.15 IMPORTANCE FACTOR.
  
 30B) PRODUCT APPROVALS:PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE
 WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BESUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 30C) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 30D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRAINER GLASS CURTAIN WALL LMI , REQUIRES FL COVER
 SHEET, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLE
 REPORTS.
 B) TRAINER GLASS CURTAIN WALL SMI REQUIRES FL COVER
 SHEET, HIGHLIGHT WHICH GLAZING TYPE
 TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF
 THE CHARTS PLEASE PROVIDE LEGIBLE
 REPORTS.
 C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE
 ANCHORING INTO MASONRY AND STEEL
 SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS
 UNDER THE 2004 USUALLY INDICATE NO
 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1.
  
 D) YKK AP 35H OUT SWING ALUMINUM DOORLMI,NOTE THIS
 REPORT REQUIRES THE DESIGN PRESSURES TO BE DIVIDED BY
 1.33, HIGHLIGHT WHICH GLAZING TYPE TO BE USED, AND
 MULLIONS. THE HEADS ARE CUT OFF THE CHARTS PLEASE
 PROVIDE LEGIBLEREPORTS.
  
 E) COMPLIED. FIREDOOR 8080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, CURRENTLY WITH A 1.0 IMPORTANCE FACTOR
 MEETS WIND LOADS.
  
 F) COMPLIED.FIREDOOR 8080 SERIES OUT SWING STEEL
 LOUVER COMMERCIAL DOOR LMI, REQUIRES FL COVER SHEET,
 CURRENTLY WITH A 1.0 IMPORTANCE FACTOR MEETS WIND
 LOADS.
  
 G) COMPLIED. FIREDOOR 4080 SERIES OUT SWING COMMERCIAL
 STEEL DOOR LMI, HIGHLIGHT TYPE OF FASTENER TO BE USED,
 REQUIRES FL COVER SHEET, CURRENTLY WITH A 1.0
 IMPORTANCE FACTOR MEETS WIND LOADS.
  
 H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL
 AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION
 **C** CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FORWIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS
 ADJUSTED TO 1.15TO BE DETERMINED BY THE DESIGN
 PROFESSIONAL.
  
 I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR CURRENTLY
 DOES NOT MEET THE REQUIRED PRESSURES. , SUBSECTION
 **C** CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE
 NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A
 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS
 WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF
 1.33 FOR WIND LOADS.
  
 J) RUSKIN LOUVER SERIES ELF6375DXD ,THE WRONG BACKUP
 REPORT WAS SUBMITTED, THE CORRECT REPORT IS AN UL
 REPORT, PLEASE SUBMIT THE RIGHT REPORT
  
 K) RUSKIN LOUVER SERIES EME520MD, ,THE WRONG BACKUP
 REPORT WAS SUBMITTED, THE CORRECT REPORT IS AN UL
 REPORT, PLEASE SUBMIT THE RIGHT REPORT
  
 L) ROOFING ASSEMBLIES: SIPLAST/ ICOPAL, MODIFIED
 BITUMEN OVER LWC DECK. THE SUB-SYSTEM IS NOT
 HIGHLIGHTED PAGES 8-20, ALSO NOTE GENERAL LIMITATION
 NUMBER 7 AND 9. IF ENHANCED FASTING IS REQUIRED PLEASE
 PROVIDE THE CALCULATIONS FOR RAS 117.
  
 M) PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED!
  
 N) NOTE CLIP SYSTEM FOR CURTAIN WALL SYSTEM IS NOT
 CALLED OUT AND WOULD ALSO REQUIRE PRODUCT APPROVAL SEE
 DETAIL 15 SHEET S-10. PROVIDE ADDITIONAL INFORMATION.
 106.1.2*
  
 31-32) COMPLIED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]