Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop E
Sequence Number 10
Notes
Date Text
2009-05-21 08:58:22**NOTES RED-LINED **
  
 1) NOTE: GATES, OPENERS SHALL BE UNDER SEPARATE
 PERMIT(S) INCLUDING WORK FOR ELECTRICAL.
 FBC 105.1
 PLEASE BE SURE TO SUBMIT TWO COPIES OF PLANS INCLUDING:
 SITE PLANS SHOWING LOCATIONS AND ACCESS DRIVES.
 ELECTRICAL DETAILS AND SUBMITTALS FOR MOTORS ARE
 NEEDED. PLEASE BE SURE THE FAIL SAFE OPERATION FOR
 GATES UNDER POWER FAILURE IS PROVIDED. PLEASE BE SURE
 THE LISTING FOR EQUIPMENT IS FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY. NRTL 110.3
  
 2) NOTE: VALUE FOR INCREASED SCOPE OF WORK FOR ANY
 OTHER SYSTEMS ADDED TO BUILDING SUCH AS UPS, TELECOM
 SYSTEMS SUCH AS THE ONES ON NEW PLANS SUBMITTED IS
 UPDATED PER FBC 108.3
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  