Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-30 17:50:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 SUBMITTED AS PLAN REVIEW:
  
 1. ALL CIVIL SHEETS, THE SEAL SHALL IMPRESS ALL
 INFORMATION REQUIRED BY FAC61G15-23.001. MUCH OF THIS
 INFORMATION IS NOT LEGIBLE. PLEASE RESEAL ALL SHEETS SO
 THAT ALL INFORMATION REQUIRED ON THE IMPRESSION TYPE
 SEAL IS LEGIBLE. FS 471.025.
  
 2. ALL CIVIL SHEETS,THE EB NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK FOR THE
 ENGINEERING DEPARTMENT OF THE BUSINESS. FAC
 61G15-23.002(2).
  
 3. SHT A203 THE CONFERENCE ROOM SINK SHALL BE
 ACCESSIBLE. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR
 EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS
 INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW
 TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR
 ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH
 ALL SUBSECTIONS & TABLE 1106.3.
  
 5. SHT A2.09 FINISH SCHEDULE. PER SECTION 1210.2 WALLS
 WITHIN 2FT OF WATER CLOSETS AND URINALS SHALL HAVE A
 SMOOTH, HARD & NONABSORBENT SURFACE. EPOXY PAINT IS NOT
 AN APPROVED SURFACE AND DOES NOT COMPLY WITH THE "HARD"
 REQUIREMENT.
  
 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN
 THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3.
  
 7. SHT A400 STALLS IN DETAILS 2 & 3 DO NOT MEET THE
 REQUIREMENT SHOWN IN FIG 11-30E. A MINIMUM 60" CLEAR
 FLOOR SPACE FOR THE WATER CLOSET, FROM THE WALL TO THE
 SIDE OF THE LAV IS REQUIRED. THE LAV CAN NOT BE IN THE
 CLEAR FLOOR SPACE FOR THE W/C. SECTION 11-4.17.3
 (EXCEPTION NEW CONSTRUCTION).
  
 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4
 FLUSH CONTROLS.
  
 9. SHT A400 EMPLOYEE WELLNESS THE STANDARD STALL SHALL
 CONTAIN AN ACCESSIBLE LAV WITHIN IT. SECTION 11-4.17.3
 (EXCEPTION NEW CONSTRUCTION), AND BE THE SIZE AND
 ARRANGEMENT REQUIRED BY FIGURE 11-30E.
  
 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE
 WITH THE FOLLOWING:
 A. 11-4.21.2 SIZE AND CLEARANCE
 B. 11-4.21.4 GRAB BAR HEIGHT
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
  
 11. SUBMIT A DETAIL FOR THE SINK IN THE LUNCH ROOM,
 (2-244), SHOWING COMPLIANCE WITH SECTION 11-4.24 AND
 ALL SUBSECTIONS. FORWARD APPROACH CLEAR FLOOR SPACE IS
 REQUIRED AND CABINET DOORS ARE NOT ALLOWED IN THE CLEAR
 FLOOR SPACE.
  
 12. SHT A406 SHOW THE FOLLOWING INFORMATION ON THE
 DETAIL:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
 NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR
 FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL
 BE ADA APPROVED OFFSET TYPE.
  
 13. SHT A4.01 NOTES FOR MENS, WOMENS& UNISEX TOILET
 INDICATE TILE PATTERN ONLY ON THE WET WALLS & INDICATES
 THE OTHER WALLS TO BE PAINTED WITH EPOXY PAINT. SEE
 SECTION 1210.2 REQUIREMENTS FOR WALLS WITHIN 2FT OF
 WATER CLOSETS & URINALS. SHOW COMPLIANCE FOR SMOOTH,
 HARD, NONABSRORBENT SURFACE.
  
 14. SHT A4.02 MENS RESTROOM 1-117B SHOWS EPOXY PAINT ON
 THE WALL NEXT TO THE W/C. THIS IS NOT APPROVED PER
 SECTION 1210.2. PLEASE INDICATE A HARD SURFACE TO SHOW
 COMPLIANCE WITHIN 2FT OF THE W/C AND/OR URINAL.
  
 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS
 ALLOWED IN THE CLEAR FLOOR SPACE).
  
 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 & ALL SUBSECTIONS.
  
 17. SHT P-1.1 WATER HEATER 'B' DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION
 607.3.2..THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS REQUIRED
 PER SECTIONS 802.3 OR 802.3.2.
  
 18. SHT P-1.1 WATER HEATER 'A' DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION
 607.3.2.
  
 19. SHT P-2.1 INDICATES A FIXTURE P-15. THIS IS NOT
 SHOWN ON THE PLUMBING FIXTURE SCHEDULE ON SHT P-1.1.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF
 PER TABLE 1106.3. 4" IS SHOWN.
  
 21. SHTS P-2.3 & P-2.4 PLAN NOTE #12 INDICATED ON THE
 COLD WATER TO TOILET ROOMS IS NOT SHOWN ON THE PLAN
 NOTES. PLEASE CLARIFY. SECTION 106.1.1.
  
 22. SHT P-2.5 INDICATES LAVS WITH EYE WASH IN THE
 ACCESSIBLE STALLS. PLEASE CLARIFY. SECTION 106.1.1.
  
 23. SHT P-3.1 RISER 1R SHOWS 3 P-4 FIXTURES, BUT THE
 FLOOR PLAN SHOWS 1 P-4 & 2 P-14 FIXTURES.PLEASE
 CLARIFY. SECTION 106.1.1.
  
 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS
 CALLED "WATERLESS URINALS". THE URINALS ARE ALSO
 DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE
 CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A
 SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB.
 SECTION 606.2.2.
  
 25. SHT P-31 RISER 3R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 26. SHT P-3.1 RISER 4R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2).
  
 27. SHT P-3.1 RISER 5R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING
 FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY.
 SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE
 SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).--
 SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE &
 VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE
 SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN.
 PLEASE CLAIRFY. SECTION 106.1.1.
  
 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING
 FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT
 OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION
 606.2.(2) --SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO
 SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 31. SHT P-3.1 RISER 9R CONDENSATE OFFSET DOES NOT
 REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE SANT. RWL
 & CONDENSATE ALL OFFSETTING ON THE SAME FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER
 DIES NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS VTR
 AT ONE FIXTURE, AND RISER SHOWS VTR AT ANOTHER FIXTURE.
 ALSO SHOW COMPLETE REVENT ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR
 ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE
 ABLE TO TRACE THE RISERS FROM UNDERGROUND TO
 TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2.
  
 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN.
 WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE
 CORRELATE.
  
 35. SHT P-3.2 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE OFFSET. SECTION 106.1.1. PLEASE CORRELATE.
  
 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN.
 SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT
 ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF
 PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM. SECTION 106.1.1.
  
 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF
 DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE
 FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.--
 MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3.
  
 39. SHT P-3.2 RISER 9R SHOW SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM.SECTION 106.1.1.--DRAIN
 SIZE DOES NOT REFLECT THE SIZE SHOWN ON THE FLOOR PLAN.
 PLEASE CORRELATE.--MINIMUM 5" REQUIRED FOR 1780SF
 PER TABLE 1106.3. 4" IS SHOWN AND DOES NOT REFLECT THE
 FLOOR PLAN PIPE SIZE. SECTION 106.1.1.
  
 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN
 IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.--
 THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
 --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE
 MAKER LINE PER SECTION 604.9.
  
 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN
 AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION
 REQUIRED ON THIS LINE). SECTION 608.--THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 42. SUBMIT A ROOF PLAN SHOWING THE LOCATION OF ALL ROOF
 DRAIN AND SHOWING THE CALCULATIONS FOR THE ROOF DRAINS.
 SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. ALSO SHOW
 THE LOCATION OF ALL VENTS THRU ROOF. PLEASE INDICATED
 THE RWL RISER NUMBER ASSOCIATED WITH THE ROOF DRAIN,
 AND THE SANITARY RISER ASSOCIATED WITH THE VTR. SECTION
 106.1.2.
  
 43. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR APPROVAL OF THE GAS
 PERMIT.
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved