| Date |
Text |
| 2007-06-30 17:50:43 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | SUBMITTED AS PLAN REVIEW: |
| | |
| | 1. ALL CIVIL SHEETS, THE SEAL SHALL IMPRESS ALL |
| | INFORMATION REQUIRED BY FAC61G15-23.001. MUCH OF THIS |
| | INFORMATION IS NOT LEGIBLE. PLEASE RESEAL ALL SHEETS SO |
| | THAT ALL INFORMATION REQUIRED ON THE IMPRESSION TYPE |
| | SEAL IS LEGIBLE. FS 471.025. |
| | |
| | 2. ALL CIVIL SHEETS,THE EB NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK FOR THE |
| | ENGINEERING DEPARTMENT OF THE BUSINESS. FAC |
| | 61G15-23.002(2). |
| | |
| | 3. SHT A203 THE CONFERENCE ROOM SINK SHALL BE |
| | ACCESSIBLE. PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | |
| | 4. SHT A2.06 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE SQUARE FOOTAGE AREA FOR |
| | EACH ROOF DRAIN AND 1/2 AREA OF ALL VERTICLE WALLS |
| | INCLUDING PARAPETS ADDED TO THE CALCULATIONS. SHOW |
| | TOTAL AREA BEING DRAINED FOR EACH DRAIN. THIS IS FOR |
| | ALL ROOF & ROOF/DECK LEVELS. SECTIONS 1106 & 1107 WITH |
| | ALL SUBSECTIONS & TABLE 1106.3. |
| | |
| | 5. SHT A2.09 FINISH SCHEDULE. PER SECTION 1210.2 WALLS |
| | WITHIN 2FT OF WATER CLOSETS AND URINALS SHALL HAVE A |
| | SMOOTH, HARD & NONABSORBENT SURFACE. EPOXY PAINT IS NOT |
| | AN APPROVED SURFACE AND DOES NOT COMPLY WITH THE "HARD" |
| | REQUIREMENT. |
| | |
| | 6. SHT A400 DETAILS 1, 2 & 3 SHOW THE TURNING AREA IN |
| | THE TOILET ROOM, NOT THE STALL. SECTION 11-4.22.3. |
| | |
| | 7. SHT A400 STALLS IN DETAILS 2 & 3 DO NOT MEET THE |
| | REQUIREMENT SHOWN IN FIG 11-30E. A MINIMUM 60" CLEAR |
| | FLOOR SPACE FOR THE WATER CLOSET, FROM THE WALL TO THE |
| | SIDE OF THE LAV IS REQUIRED. THE LAV CAN NOT BE IN THE |
| | CLEAR FLOOR SPACE FOR THE W/C. SECTION 11-4.17.3 |
| | (EXCEPTION NEW CONSTRUCTION). |
| | |
| | 8. A400 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.18.4 |
| | FLUSH CONTROLS. |
| | |
| | 9. SHT A400 EMPLOYEE WELLNESS THE STANDARD STALL SHALL |
| | CONTAIN AN ACCESSIBLE LAV WITHIN IT. SECTION 11-4.17.3 |
| | (EXCEPTION NEW CONSTRUCTION), AND BE THE SIZE AND |
| | ARRANGEMENT REQUIRED BY FIGURE 11-30E. |
| | |
| | 10. SHT A400 ACCESSIBLE SHOWERS SHALL SHOW COMPLIANCE |
| | WITH THE FOLLOWING: |
| | A. 11-4.21.2 SIZE AND CLEARANCE |
| | B. 11-4.21.4 GRAB BAR HEIGHT |
| | C. 11-4.21.5 CONTROLS |
| | D. 11-4.21.6 SHOWER UNIT |
| | E. 11-4.21.7 CURBS |
| | |
| | 11. SUBMIT A DETAIL FOR THE SINK IN THE LUNCH ROOM, |
| | (2-244), SHOWING COMPLIANCE WITH SECTION 11-4.24 AND |
| | ALL SUBSECTIONS. FORWARD APPROACH CLEAR FLOOR SPACE IS |
| | REQUIRED AND CABINET DOORS ARE NOT ALLOWED IN THE CLEAR |
| | FLOOR SPACE. |
| | |
| | 12. SHT A406 SHOW THE FOLLOWING INFORMATION ON THE |
| | DETAIL: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | NOTE: THE GARBAGE DISPOSAL IS NOT ALLOWED IN THE CLEAR |
| | FLOOR SPACE/KNEE CLEARANCE. THE GARBAGE DISPOSAL SHALL |
| | BE ADA APPROVED OFFSET TYPE. |
| | |
| | 13. SHT A4.01 NOTES FOR MENS, WOMENS& UNISEX TOILET |
| | INDICATE TILE PATTERN ONLY ON THE WET WALLS & INDICATES |
| | THE OTHER WALLS TO BE PAINTED WITH EPOXY PAINT. SEE |
| | SECTION 1210.2 REQUIREMENTS FOR WALLS WITHIN 2FT OF |
| | WATER CLOSETS & URINALS. SHOW COMPLIANCE FOR SMOOTH, |
| | HARD, NONABSRORBENT SURFACE. |
| | |
| | 14. SHT A4.02 MENS RESTROOM 1-117B SHOWS EPOXY PAINT ON |
| | THE WALL NEXT TO THE W/C. THIS IS NOT APPROVED PER |
| | SECTION 1210.2. PLEASE INDICATE A HARD SURFACE TO SHOW |
| | COMPLIANCE WITHIN 2FT OF THE W/C AND/OR URINAL. |
| | |
| | 15. SHT A4.02 THE SINK IN ROOM 1-110 SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. (NO CABINET DOORS |
| | ALLOWED IN THE CLEAR FLOOR SPACE). |
| | |
| | 16. SHT A4.07 THE SINK IN THE CONFERENCE ROOM 3-311 |
| | SHALL BE ACCESSIBLE. SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 & ALL SUBSECTIONS. |
| | |
| | 17. SHT P-1.1 WATER HEATER 'B' DETAIL THERMAL EXPANSION |
| | CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION |
| | 607.3.2..THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. A FLOOR SINK OR A HUB DRAIN IS REQUIRED |
| | PER SECTIONS 802.3 OR 802.3.2. |
| | |
| | 18. SHT P-1.1 WATER HEATER 'A' DETAIL THERMAL EXPANSION |
| | CONTROL IS REQUIRED. PLEASE INDICATE METHOD. SECTION |
| | 607.3.2. |
| | |
| | 19. SHT P-2.1 INDICATES A FIXTURE P-15. THIS IS NOT |
| | SHOWN ON THE PLUMBING FIXTURE SCHEDULE ON SHT P-1.1. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 20. SHT P-2.2 RISER 8R MINIMUM 5" REQUIRED FOR 1800SF |
| | PER TABLE 1106.3. 4" IS SHOWN. |
| | |
| | 21. SHTS P-2.3 & P-2.4 PLAN NOTE #12 INDICATED ON THE |
| | COLD WATER TO TOILET ROOMS IS NOT SHOWN ON THE PLAN |
| | NOTES. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 22. SHT P-2.5 INDICATES LAVS WITH EYE WASH IN THE |
| | ACCESSIBLE STALLS. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 23. SHT P-3.1 RISER 1R SHOWS 3 P-4 FIXTURES, BUT THE |
| | FLOOR PLAN SHOWS 1 P-4 & 2 P-14 FIXTURES.PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 24. SHT P-3.1 RISER 2R SHOWS WATER SUPPLY TO WHAT IS |
| | CALLED "WATERLESS URINALS". THE URINALS ARE ALSO |
| | DESIGNATED AS P-4 ON THE WATER RISER DIAGRAM. PLEASE |
| | CLARIFY. SECTION 106.1.1. --THE HOSE BIBBS REQUIRE A |
| | SHUT-OFF-VALVE ON THE WATER SUPPLY TO EACH HOSE BIBB. |
| | SECTION 606.2.2. |
| | |
| | 25. SHT P-31 RISER 3R DOES NOT SHOW DRAINAGE, WASTE & |
| | VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE |
| | SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | 26. SHT P-3.1 RISER 4R NO WATER SUPPLY FOR THE DRINKING |
| | FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT |
| | OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION |
| | 606.2.(2). |
| | |
| | 27. SHT P-3.1 RISER 5R DOES NOT SHOW DRAINAGE, WASTE & |
| | VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE |
| | SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | 28. SHT P-3.1 RISER 6R NO WATER SUPPLY TO THE DRINKING |
| | FOUNTAINS ON THE 3RD & 4TH FLOORS.PLEASE CLARIFY. |
| | SECTION 106.1.1.--SHUT OFF VALVES REQUIRED ON THE |
| | SUPPLY LINES FOR EACH HOSE BIBB. SECTION 606.2(2).-- |
| | SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 29. SHT P-3.1 RISER 7R DOES NOT SHOW DRAINAGE, WASTE & |
| | VENT TO THE DRINKING FOUNTAINS. ALSO THE VENT LINE |
| | SHOWN ON THE RISER IS NOT SHOWN ON THE FLOOR PLAN. |
| | PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | 30. SHT P-3.1 RISER 8R NO WATER SUPPLY FOR THE DRINKING |
| | FOUNTAINS. PLEASE CLARIFY. SECTION 106.1.1.--SHUT |
| | OFF VALVES REQUIRED FOR HOSE BIBB SUPPLY LINES. SECTION |
| | 606.2.(2) --SHOWS 2 P-5 FIXTURESNOT SHOWN ON THE |
| | FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.--NO |
| | SLEEVE FOR WATER RISERS INDICATED ON THE FLOOR PLAN. |
| | PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 31. SHT P-3.1 RISER 9R CONDENSATE OFFSET DOES NOT |
| | REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS THE SANT. RWL |
| | & CONDENSATE ALL OFFSETTING ON THE SAME FLOOR. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 32. SHT P-3.1 RISER 12R REVENT AT THE TOP OF THE RISER |
| | DIES NOT REFLECT THE FLOOR PLAN. FLOOR PLAN SHOWS VTR |
| | AT ONE FIXTURE, AND RISER SHOWS VTR AT ANOTHER FIXTURE. |
| | ALSO SHOW COMPLETE REVENT ON THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | |
| | 33. ALL FLOOR PLANS. SHOW ALL RISER DESIGNATIONS FOR |
| | ALL SYSTEMS ON ALL FLOOR PLAN SHEETS IN ORDER TO BE |
| | ABLE TO TRACE THE RISERS FROM UNDERGROUND TO |
| | TERMINATION IN THE BUILDING OR VTR. SECTION 106.1.2. |
| | |
| | 34. SHT P-3.2 RISER 1R DOES NOT REFLECT THE FLOOR PLAN. |
| | WHEN RESUBMITTING PLEASE INDICATE THE DFU'S AS THEY |
| | ACCUMULATE IN THE SYSTEM. SECTION 106.1.1. PLEASE |
| | CORRELATE. |
| | |
| | 35. SHT P-3.2 RISER 2R DOES NOT REFLECT THE FLOOR PLAN |
| | AT THE OFFSET. SECTION 106.1.1. PLEASE CORRELATE. |
| | |
| | 36. SHT P-3.2 RISER 4R DOES NOT REFLECT THE FLOOR PLAN. |
| | SHOWS 2 P-13 FIXTURES ON EACH FLOOR ON THE RISER BUT |
| | ONLY ONE ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 37. SHT P-3.2 RISER 5R DOES NOT REFLECT THE FLOOR PLAN. |
| | PLEASE CORRELATE.--MINIMUM 8" REQUIRED FOR 6000SF |
| | PER TABLE 1106.3.--SHOW THE SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. SECTION 106.1.1. |
| | |
| | 38. SHT P-3.2 RISER 8R THE SQUARE FOOTAGE AT THE ROOF |
| | DRAINS DOES NOT REFLECT THE SQUARE FOOTAGE SHOWN ON THE |
| | FLOOR PLAN. PLEASE CORRELATE SECTION 106.1.1.-- |
| | MINIMUM 5" REQUIRED FOR 1780SF. TABLE 1106.3. |
| | |
| | 39. SHT P-3.2 RISER 9R SHOW SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM.SECTION 106.1.1.--DRAIN |
| | SIZE DOES NOT REFLECT THE SIZE SHOWN ON THE FLOOR PLAN. |
| | PLEASE CORRELATE.--MINIMUM 5" REQUIRED FOR 1780SF |
| | PER TABLE 1106.3. 4" IS SHOWN AND DOES NOT REFLECT THE |
| | FLOOR PLAN PIPE SIZE. SECTION 106.1.1. |
| | |
| | 40. SHT P-3.3 RISER 1R DOES NOT REFLECT THE FLOOR PLAN |
| | IN MANY AREAS. PLEASE CORRELATE. SECTION 106.1.1.-- |
| | THE WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | --AWATER HAMMER ARRESTOR IS REQUIRED ON THE ICE |
| | MAKER LINE PER SECTION 604.9. |
| | |
| | 41. SHT P-3.3 RISER 2R DOES NOT REFLECT THE FLOOR PLAN |
| | AT THE LINE TO THE AC UNIT. (BACKFLOW PREVENTION |
| | REQUIRED ON THIS LINE). SECTION 608.--THE WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. |
| | PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 42. SUBMIT A ROOF PLAN SHOWING THE LOCATION OF ALL ROOF |
| | DRAIN AND SHOWING THE CALCULATIONS FOR THE ROOF DRAINS. |
| | SECTIONS 1106 & 1107 WITH ALL SUBSECTIONS. ALSO SHOW |
| | THE LOCATION OF ALL VENTS THRU ROOF. PLEASE INDICATED |
| | THE RWL RISER NUMBER ASSOCIATED WITH THE ROOF DRAIN, |
| | AND THE SANITARY RISER ASSOCIATED WITH THE VTR. SECTION |
| | 106.1.2. |
| | |
| | 43. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR APPROVAL OF THE GAS |
| | PERMIT. |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |