2007-06-19 17:52:41------------DENIED-------------
  
 FBC CODE FAMILY W/ 2006 REVISIONS
 FBC H.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
 FAC 9B-72
  
 NOTE: ONE SET OF PLANS WAS MARKED-UP DURING THIS REVIEW
 IN ORDER TO HELP CLARIFY THE REVIEW COMMENTS THAT
 FOLLOW:
  
 1. M1.01: AIR BALANCE SCHEDULE AND FLOOR PLAN SHOW AHU
 1-1 AT 7050 CFM BUT AHU SCHEDULE ON M0.02 SHOWS AHU 1-1
 AT 6500 CFM. PLEASE SHOW CORRELATION BETWEEN FLOOR PLAN
 AND SCHEDULE. WHICH ONE IS CORRECT?
 PLEASE CLARIFY NOTE 13 ON AHU SCHEDULE. PROVIDE
 MANUFACTURER'S SUBMITTALS SHOWING CAPACITY OF EQUIPMENT
 TO BE COMPATIBLE WITH DEMAND SHOWN ON PLAN.
  
 2. M1.01 AIR BALANCE SCHEDULE ON FIRST FLOR SHOWS
 SUPPLY, RETURN AND OUTSIDE AIR TO BE IN BALANCE AT 0.
 THE COMBINED EXHAUST AND RELIEF AIR FOR THE FLOOR
 CREATE A NEGATIVE BALANCE OF -3290 CFM. MECHANICAL
 SYSTEMS SHALL BE DESIGNED TO ASSURE THAT BUILDINGS ARE
 PRESSURIZED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.ALSO, THE AMOUNT OF SUPPLY AIR SHALL BE
 APPROXIMATELY EQUAL TO THE AMOUNT OF RETURN AND EXHAUST
 AIR PER FBC,M 403.1.
  
 3. M1.01: FIRE DAMPER IS REQUIRED ON THE 8X8 EXHAUST
 DUCT IN THE WALL BETWEEN ROOMS 1-127 AND 1-129. IT DOES
 NOT MEET EXCEPTION 2.4 OF FBC,M 607.5.3. IT IS NOT
 ABOVE A CEILING.
  
 4. M1.01: ALL DUCT PENETRATIONS THROUGH THE RATED WALL
 INTO AND OUT OF ROOM 1-119 REQUIRE FIRE DAMPERS. THEY
 DO NOT MEET EXCEPTION 2.4 OF FBC,M 607.5.3. THEY ARE
 NOT ABOVE A CEILING.
  
 5. M1.01: CORRIDOR 1-109 MAY BE REQUIRED (SEE BUILDING
 PLAN REVIEW COMMENTS) TO HAVE A 1-HOUR FIRE RESISTANCE
 RATING BASED ON FBC TABLE 1016.1. PLEASE REVIEW BOTH
 SIDES OF THE CORRIDOR FOR THE NEED FOR OPENING
 PROTECTIVES SUCH AS FIRE AND SMOKE DAMPERS. FBC,M
 607.5.4. ALSO, SEE FBC,M 401.4 REGARDING VENTILATION
 REQUIREMENTS FOR EXIT ENCLOSURES.
  
 6. M1.01 AND ALL FLOORS: DUCTS AND AIR TRANSFER
 OPENINGS IN RATED WALLS WHICH ARE NOT REQUIRED TO HAVE
 DAMPERS BY FBC,M SEC.607 SHALL COMPLY WITH THE
 REQUIREMENTS OF FBC SEC.712. PLEASE PROVIDE DETAIL
 DRAWINGS AND LISTED ASSEMBLIES AS REQUIRED BY THIS
 SECTION.
  
 7. M2.01: PLEASE SHOW THE SIZE OF THE EXHAUST DUCT IN
 ROOM 2-244 RELATED TO NOTE #4.
  
 8. M2.01: THE AIR BALANCE SCHEDULE ON THIS PAGE SHOWS
 THE 2ND FLOOR AT A NEGATIVE BALANCE OF -2580 CFM.
 PLEASE SEE COMMENT #2 FOR RELEVANT CODE SECTIONS AND
 REQUIREMENTS.
  
 9. M2.01 ROOMS 2-237 ANS 2-240: WHAT IS THE MEANING OF
 "TR/380? AND "TR/180?" THE DESIGNATION COULD NOT BE
 FOUND ON PLANS OR SCHEDULES. FBC 106.1.1
  
 10. M1.01 THRU M5.01: EXHAUST DUCTS IN GANG BATHROOMS
 WHICH PENETRATE THE RATED SHAFT ENCLOSURE REQUIRE FIRE
 AND SMOKE DAMPERS PER FBC,M 607.5.5.1. PLEASE PROVIDE A
 RISER DETAIL SHOWING EXHAUST RISERS WITH DUCT SIZES AND
 LOCATIONS OF TRANSITIONS. ALSO, THE RATED SHAFT
 ENCLOSURE IS NOT SHOWN ON ARCHITECTURAL FLOOR PLANS.
 PLEASE COORDINATE DRAWINGS. FBC 106.1.1
  
 11. M3.01: AIR BALANCE ON THE 3RD FLOOR IS AT A
 NEGATIVE BALANCE OF -1750 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 12. M3.01: THE 10X10 R/A DUCT PENETRATION AT ROOM 3-303
 DOES NOT MEET EXCEPTION 2.5 UNDER FBC,M 607.5.3. A FIRE
 DAMPER IS REQUIRED.
  
 13. M4.01: AIR BALANCE ON THE 4TH FLOOR IS AT A
 NEGATIVE BALANCE OF -1550 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 14. M5.01: AIR BALANCE ON THE 5TH FLOOR IS AT A
 NEGATIVE BALANCE OF -1670 CFM. PLEASE SEE COMMENT #2
 FOR RELEVANT CODES AND REQUIREMENTS.
  
 15. M6.01: AHU 1-2 OUTSIDE AIR INTAKE SHALL BE MINIMUM
 10' FROM STREETS, ALLEYS, PARKING LOTS OR LOADING DOCKS
 PER FBC,M 401.5.1.
  
 16. M6.02 RELIEF AIR RISER DIAGRAM: FIRE AND SMOKE
 DAMPERS ARE REQUIRED AT ALL SHAFT ENCLOSURE DUCT
 PENETRATIONS (RF 2-1 THRU RF 4-1) PER FBC,M 607.5.5.1.
  
 17. M6.02: RELIEF AIR RISER SHOWS RF 5-1 CONNECTING TO
 RISER, BUT ON M6.03 THERE IS NO RF 5-1. THERE IS RF 5-2
 AND IT DISCHARGES DIRECTLY TO THE OUTDOORS, NOT THROUGH
 THE RISER. RF 5-1 IS ALSO SHOWN ON THE EXHAUST FAN
 SCHEDULE ON M0.03 AS A ROOFTOP FAN. PLEASE COORDINATE
 PLANS AND SCHEDULES AND CORRECT AS NEEDED. FBC 106.1.1
  
 18. M7.03 DETAIL #7: PLEASE SHOW HEIGHT OF CONDENSER
 ABOVE FINISHED ROOF TO BE IN COMPLIANCE WITH FBC TABLE
 1509.7. ALSO, PRE-ENGINEERED A/C STANDS ARE STRUCTURAL
 COMPONENTS AND REQUIRE PRODUCT APPROVAL. PLEASE PROVIDE
 PRODUCT APPROVAL DOCUMANTATION AND INSTALLATION
 INSTRUCTIONS IN ACCORDANCE WITH THEIR LISTING. FAC
 9B-72.
  
 19. PLEASE SHOW ALL OUTDOOR EQUIPMENT SECURED TO
 STRUCTURE IN A MANNER THAT MEETS 140 MPH WIND LOADS PER
 FBC,M 301.13 AND FBC SEC.1609.
  
 20. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE
 DAMPERS AND CEILING DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS
 SECTION, AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING. FBC,M 607.2
  
 21. PLEASE SHOW MEANS OF SECONDARY/AUXILIARY DRAIN
 PROTECTION FOR ALL AHU'S AND CRU-1 PER FBC,M 307.2.3.
  
 22. M1.01 EMERGENCY STORAGE ROOM 1-113: FLEXIBLE DUCTS
 AND AIR CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY. FBC,M 607.7
  
 23. M2.01: WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET, SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
  
 24. ENERGY CALCULATIONS SHALL BE SIGNED AND SEALED BY
 AN ARCHITECT OR ENGINEER LICENSED TO PRACTICE IN THE
 STATE OF FLORIDA. DESIGN PROFESSIONALS RESPONSIBLE
 UNDER FLORIDA LAW FOR THE DESIGN OF LIGHTING,
 ELECTRICAL, MECHANICAL, AND PLUMBING SYSTEMS AND THE
 BUILDING SHELL, SHALL CERTIFY COMPLIANCE OF THOSE
 BUILDING SYSTEMS WITH THE CODE BY SIGNING AND PROVIDING
 THEIR PROFESSIONAL REGISTRATION NUMBER ON THE ENERGY
 CODE FORM PROVIDED AS PART OF THE PLANS AND
 SPECIFICATIONS TO THE BUILDING DEPARTMENT. FBC
 13-103.1.1.1
  
 25. ENERGY CALCULATIONS: INPUT DATA REPORT; NO DETAIL
 OR INFORMATION COULD BE FOUND IN PLANS WHICH CORRESPOND
 WITH THE EXTERIOR WALL/INSULATION ASSEMBLY OR THE
 ROOF/INSULATION ASSEMBLY AS THEY ARE SHOWN IN THE
 REPORT. PLEASE PROVIDE SUFFICIENT INFORMATION ON PLANS
 AND ENSURE THAT CONSTRUCTION TYPES ARE CORRELATED ON
 PLANS AND ENERGY CALCULATIONS. FBC 106.1.1
  