Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-22 19:16:23*****DENIED*****INCOMPLETE AT THIS TIME
  
  
 01.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED
 PRIOR TO, DURING, AND AFTER CONSTRUCTION.
  
 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY
 OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE
 LANES).
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON
 THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION,
 POST/DISPLAY THE LOCATION OF THE REQUIRED KNOX BOX FOR
 EMERGENCY FIRE DEPARTMENT ENTRY INTO THE BUILDING.FOR
 KNOX BOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.
  
 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR
 OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR
 DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A
 SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT
 CONNECTION) SHALL BE POSTED.
  
 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 08.A CHAIN AND LOCK IN ADDITION TO THE ELCTRONIC
 SWITHCES SHALL BE REQUIRED FOR THE DOUBLE CHECK
 DETECTOR ASSEMBLY.
  
 09.PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR
 STAIRS AND RAMPS WILL BE SLIP RESISTANT.
  
 10.OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED TO
 MINIMIZE WATER ACCUMULATIONON THEIR SURFACES.
  
 11.FIRE WINDOWS IN ADDITION TO FIRE DOORS SHALL
 COMPLY WITH NFPA 80.
  
 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE
 FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME
 A17.1.
  
 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS.
  
 14.PLEASE SHOW STAIRWAY MARKING WITHIN THE ENCLOSURE
 AT EACH FLOOR LEVEL.THE SIGN SHALL INDICATE THE FLOOR
 LEVEL, THE TERMINUS OF THE TOP AND BOTTOM, AND THE
 IDENTITY OF THE STAIR ENCLOSURE.THE SIGNAGE ALSO
 SHALL INDICATE THE FLOOR LEVEL OF, AND THE DIRECTION
 TO, EXIT DISCHARGE.
  
 15.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM AS PER 2003 NFPA 101, 7.2.1.6.2; HOWEVER
 CLARIFICATION NEEDED AS TO THE LOCATION OF THE ACCESS
 CONTROL DEVICE.IS IT ON THE FLOOR LEADING TO THE EXIT
 STAIRWAY ENCLOSURE?ORIS IT IN THE STAIRWAY
 ENCLOSURE LEADING TO THE FLOOR?
  
 16.PLEASE EXPLAIN THE NEED FOR ALL THE KNOX BOX
 APPLIANCES AS INDICATED/LEGENDED BY A SQUARE WITH A
 CAPITAL K INSIDE.I.E. SHEET E1.03
  
 17.THE NUMBER AND/OR LOCATION OF THE EXIT LIGHTS ON
 SOMEPLAN SHEETS DO NOT CORRELATE WITH THOSE ON OTHER
 PLAN SHEETS.PLEASE AMEND.I.E. SHEETSE1.01 &
 LS0.02,E1.04 & LS0.03
  
 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE
 INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS.
  
 19.ON SHEET E1.01, IT APPEARS THAT THERE IS EMERGENCY
 LIGHTING FOR THE LANDING IN STAIR 2 BUT NOT IN STAIR
 1.
  
 20. PLEASE PROVIDE SPEC SHEETS FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 21.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM.
  
 22.SEPARATE PLANS AND PERMIT REQUIRED FOR THE
 COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER
 SYSTEM.
  
 23.FLOW TEST DATA ON SHEET FP0.01 HAS GPM DISCHARGE
 WHICH IS INCORRECT.A RESIDUAL PRESSURE OF 71 PSI
 USING A 2.5" DISCHARGE WILL HAVE A GPM DISCHARGE OF
 1410 NOT 11410 AS LISTED IN THE DATA.
  
 24.CORRELATE STAIR 'A' AND STAIR 'B' ON FP SHEETS
 WITH STAIR 1 AND STAIR 2 AS EXPRESSED ON OTHER SHEETS
 THROUGHOUT THE PLANS.
  
 25.FIRE SPRINKLER SHALL BE MONITORED.
  
 26.SEPARATE PLANS AND PERMIT REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 27.THE FIRE ALARM SYSTEM SHALL BEU.L. CERTIFICATED
 APPROVED FOR CENTRAL STATION SERVICE.
  
 28.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL FIRE ALARM.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722