| 2007-07-22 19:16:23 | *****DENIED*****INCOMPLETE AT THIS TIME |
| | |
| | |
| | 01.THE ACTUAL ADDRESS SHALL BE IN THE TITLE BLOCK OF |
| | EACH SUBMITTED PLAN SHEET. |
| | |
| | 02.THE PROPOSED WET FIRE HYDRANT(S) ARE REQUIRED |
| | PRIOR TO, DURING, AND AFTER CONSTRUCTION. |
| | |
| | 03.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY |
| | OR THE VICINITY THEREOF (INCLUDING STREETS, FIRE |
| | LANES). |
| | |
| | 04.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | CLEMATIS STREET, POST/DISPLAY THE NUMERICAL ADDRESS ON |
| | THE BUILDING.AS PER WEST PALM BEACH CODE, THE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" |
| | IN WIDTH. |
| | |
| | 05.ON THE APPROPIATE EXTERIOR ELEVATION, |
| | POST/DISPLAY THE LOCATION OF THE REQUIRED KNOX BOX FOR |
| | EMERGENCY FIRE DEPARTMENT ENTRY INTO THE BUILDING.FOR |
| | KNOX BOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE |
| | PREVENTION BUREAU AT 561-804-4724. |
| | |
| | 06.THE ACCESS TO THE FIRE DEPARTMENT CONNECTION (FDC) |
| | SHALL BE MAINTAINED AND SHALL NOT BE BLOCKED OR |
| | OBSTRUCTED BY LANDSCAPING, VEHICLES, EQUIPMENT, AND/OR |
| | DESIGN FEATURES.IF THE FDC IS NOT READILY VISIBLE, A |
| | SIGN OF 6" LETTERS (FDC) OR 2" WORDS (FIRE DEPARTMENT |
| | CONNECTION) SHALL BE POSTED. |
| | |
| | 07.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE |
| | DEPARTMENT CONNECTION.FOR KNOX APPLICATIONS, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 08.A CHAIN AND LOCK IN ADDITION TO THE ELCTRONIC |
| | SWITHCES SHALL BE REQUIRED FOR THE DOUBLE CHECK |
| | DETECTOR ASSEMBLY. |
| | |
| | 09.PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR |
| | STAIRS AND RAMPS WILL BE SLIP RESISTANT. |
| | |
| | 10.OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED TO |
| | MINIMIZE WATER ACCUMULATIONON THEIR SURFACES. |
| | |
| | 11.FIRE WINDOWS IN ADDITION TO FIRE DOORS SHALL |
| | COMPLY WITH NFPA 80. |
| | |
| | 12.ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE |
| | FIGHTERS' EMERGENCY OPERATIONS REQUIREMENTS OF ASME |
| | A17.1. |
| | |
| | 13.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| | FOR ALL HANDRAILS AND GUARDRAILS. |
| | |
| | 14.PLEASE SHOW STAIRWAY MARKING WITHIN THE ENCLOSURE |
| | AT EACH FLOOR LEVEL.THE SIGN SHALL INDICATE THE FLOOR |
| | LEVEL, THE TERMINUS OF THE TOP AND BOTTOM, AND THE |
| | IDENTITY OF THE STAIR ENCLOSURE.THE SIGNAGE ALSO |
| | SHALL INDICATE THE FLOOR LEVEL OF, AND THE DIRECTION |
| | TO, EXIT DISCHARGE. |
| | |
| | 15.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO |
| | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS |
| | CONTROL SYSTEM AS PER 2003 NFPA 101, 7.2.1.6.2; HOWEVER |
| | CLARIFICATION NEEDED AS TO THE LOCATION OF THE ACCESS |
| | CONTROL DEVICE.IS IT ON THE FLOOR LEADING TO THE EXIT |
| | STAIRWAY ENCLOSURE?ORIS IT IN THE STAIRWAY |
| | ENCLOSURE LEADING TO THE FLOOR? |
| | |
| | 16.PLEASE EXPLAIN THE NEED FOR ALL THE KNOX BOX |
| | APPLIANCES AS INDICATED/LEGENDED BY A SQUARE WITH A |
| | CAPITAL K INSIDE.I.E. SHEET E1.03 |
| | |
| | 17.THE NUMBER AND/OR LOCATION OF THE EXIT LIGHTS ON |
| | SOMEPLAN SHEETS DO NOT CORRELATE WITH THOSE ON OTHER |
| | PLAN SHEETS.PLEASE AMEND.I.E. SHEETSE1.01 & |
| | LS0.02,E1.04 & LS0.03 |
| | |
| | 18.THE EXTERIOR ELEVATION ON SHEETS S-12 AND S-13 ARE |
| | INCONSISTENT WITH THOSE LISTED ELSEWHERE IN THE PLANS. |
| | |
| | 19.ON SHEET E1.01, IT APPEARS THAT THERE IS EMERGENCY |
| | LIGHTING FOR THE LANDING IN STAIR 2 BUT NOT IN STAIR |
| | 1. |
| | |
| | 20. PLEASE PROVIDE SPEC SHEETS FOR FIRE PUMP AND |
| | ASSOCIATED EQUIPMENT. |
| | |
| | 21.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 22.SEPARATE PLANS AND PERMIT REQUIRED FOR THE |
| | COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 23.FLOW TEST DATA ON SHEET FP0.01 HAS GPM DISCHARGE |
| | WHICH IS INCORRECT.A RESIDUAL PRESSURE OF 71 PSI |
| | USING A 2.5" DISCHARGE WILL HAVE A GPM DISCHARGE OF |
| | 1410 NOT 11410 AS LISTED IN THE DATA. |
| | |
| | 24.CORRELATE STAIR 'A' AND STAIR 'B' ON FP SHEETS |
| | WITH STAIR 1 AND STAIR 2 AS EXPRESSED ON OTHER SHEETS |
| | THROUGHOUT THE PLANS. |
| | |
| | 25.FIRE SPRINKLER SHALL BE MONITORED. |
| | |
| | 26.SEPARATE PLANS AND PERMIT REQUIRED FOR THE |
| | INSTALLATION OF THE FIRE ALARM SYSTEM. |
| | |
| | 27.THE FIRE ALARM SYSTEM SHALL BEU.L. CERTIFICATED |
| | APPROVED FOR CENTRAL STATION SERVICE. |
| | |
| | 28.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM. |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |