| Date |
Text |
| 2007-06-10 18:30:10 | 2007-06-10 18:30:10 |
| | |
| | *** UNSAT *** |
| | |
| | PALM BEACH COUNTY HEALTH DEPARTMENT. |
| | |
| | ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS |
| | SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW |
| | COMMENTS ON RE-SUBMITTAL OF PLANS. |
| | |
| | 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE |
| | COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS |
| | AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE |
| | VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME |
| | OF APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE ADDRESSING OF SAID PROJECT IS STILL |
| | YET TO BE FINALIZED. ONCE THIS IS DONE ALL |
| | DOCUMENTATION SUBMITTED IS REQUIRED TO CONTAIN THE |
| | CORRECT ADDRESS ON TITLE BLOCKS AS WELL AS SUPPORTING |
| | DOCUMENTS. |
| | PLEASE SEE COMMENTS FORM ADDRESSING REVIEWER. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL FIRMS |
| | SHALL BE COMPLETE ON ALL SHEETS WITH ALL INFORMATION AS |
| | REQUIRED PER FLORIDA ADMINISTRATIVE CODES. 61G1-16.004, |
| | 61G15-23.002 |
| | PLEASE SEE ALL SHEETS WHICH CONTAIN TITLE BLOCKS SHALL |
| | CONTAIN THE INFORMATION. |
| | PLEASE SEE LANDSCAPE PLANS MISSING REQUIRED PRINTED |
| | NAME, PRINTED LICENSE NUMBER OF ARCHITECT AS WELL AS |
| | PRINTED CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE |
| | MEP PLANS WHICH CONTAINS TITLE BLOCKS FOR FIRMS, YET |
| | THE CA # IS MISSING. |
| | PLEASE SEE THE MEP PLANS WHICH CONTAINS TITLE BLOCKS |
| | FOR A SEPARATE LANDSCAPE DESIGN FIRM AS LISTED ON COVER |
| | SHEET AND AS SUBMITTED IN PROJECT ROLL OF PLANS. ** |
| | PLEASE KNOW THERE ARE MANY ITEMS MISSING, PLEASE BE |
| | SURE TO THROUGH ALL SHEETS. |
| | ** PLEASE SEE THE CA # ON MANY SHEETS IS VERY |
| | SMALL/BLURRED AND NOT EASILY READ. |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE SEE THE SEAL IN USE ON THE LANDSCAPE |
| | SHEETS IS NOT ACCEPTABLE PER FAC 61G1-16.002 WHICH |
| | REQUIRES A MINIMUM SIZE. THIS IS NOT A NEW CHANGE TO |
| | THE FAC. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 5) NOTE: PLEASE BE SURE ARCHITECTURAL PLANS AND |
| | ELECTRICAL PLANS CONTAIN THE FOLLOWING CODES AT A |
| | MINIMUM. (SOME ARE ALREADY ON PLANS ON SOME SHEETS. |
| | 2004 FBC W/2006 REVISIONS, ON A SHEETS. |
| | 2003 NFPA-101 ON A SHEETS. |
| | 2002 NFPA-72 ON A SHEETS. |
| | 2003 NFPA-20 NOT ON ANY. |
| | 2002 NFPA-110 NOT ON ANY. |
| | 2005 NFPA-70 (NEC) ON A SHEETS. |
| | |
| | **THERE MAY BE OTHER CODES REQUESTED FROM OTHER |
| | TRADES. |
| | |
| | 6) NOTE:PLEASE SEE THE FOLLOWING NOTES ARE FOR FBC |
| | 2004 W/2006 REVISIONS TO CHAPTER 13. THERE ARE ITEMS |
| | MISSING WHICH CAN NOT BE REVIEWED AT THIS TIME. |
| | A) PLEASE SEE ENERGY CALCULATIONS AS THESE NEED TO BE |
| | SIGNED, DATED AND SEALED BY THE RESPONSIBLE DESIGNER(S) |
| | OF RECORD. 13-103.1.1.1 ALL THREE SETS. |
| | B) PLEASE SEE THESE SAME SHEETS REQUIRES THE |
| | OWNER/AGENT TO SIGN ALL THREES SETS. |
| | C) PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH PLANS FOR THE METHODS OF CONTROLS. THE |
| | CALCULATIONS INDICATE *MANUAL ON/OFF* CONTROLS WHICH IS |
| | NOT POSSIBLE WHEN A FULLY AUTOMATED SYSTEM(S) AND |
| | DEVICES ARE REQUIRED. SOME OF THESE ARE SHOWN ON |
| | PLANS.13-415.1AB.1.1, 13-415.2 |
| | D) PLEASE SEE MISSING ZONES FOR SYSTEM(S). PLEASE SEE |
| | PLANS MENTIONS LIGHTING CONTACTOR FOR HALLWAYS, HOWEVER |
| | NO DETAILS OR INFORMATION FOR EACH OF THESE REQUIRED |
| | FOR EACH FLOOR PER 13-415.1.ABC.1.1, .1.2 AND .1.3 WAS |
| | SUBMITTED. PLEASE SEE LOCATIONS OF OVER RIDES REQUIRE |
| | THESE TO BE LOCATED SO THE OPERATOR CAN VISUALLY SEE |
| | THE LIGHTING BEING OVER-RIDDEN. THIS IS NOT POSSIBLE IF |
| | THIS OVER RIDE IS IN A JANITOR'S CLOSET. |
| | E) PLEASE INDICATE ALL DEVICES FOR ALL SEPARATE SPACES |
| | AS THERE ARE ROOMS/AREAS WHICH DO NOT INDICATE ANY |
| | CONTROL DEVICE(S). |
| | F) PLEASE BE SURE TO INCLUDE SCHEDULING FOR SYSTEM(S) |
| | PROPOSED. |
| | G) PLEASE INCLUDE ALL DEVICES, OVER RIDE TIMES |
| | (MAXIMUM) AND COORDINATE ON DEVICE LEGEND. |
| | H) PLEASE SEE LIGHTING DETAIL ON E5.01 IS NOT |
| | POSSIBLE. |
| | I) PLEASE SEE THERE ARE SEVERAL FIXTURES ON ENERGY |
| | CALCULATIONS WHICH DO NOT MATCH WITH FIXTURE LEGEND OR |
| | PLANS AND REVERSE AS WELL AS FIXTURES ON FIXTURE LEGEND |
| | NOT IN CALCULATIONS. THE NUMBER OF FIXTURES, WATTAGES |
| | ON CALCULATIONS NEEDS TO CORRELATE WITH THE PLANS AND |
| | FIXTURE LEGEND. |
| | |
| | 7) NOTE: PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN |
| | ELECTRICAL ROOM IS NOT PERMITTED. |
| | PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED |
| | SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN |
| | OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING |
| | OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE |
| | FPC IS NOT PERMITTED. |
| | PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR |
| | FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE |
| | SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND |
| | 10. |
| | PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR |
| | GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE |
| | GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE |
| | INFORMATION ON PLANS. |
| | |
| | 8) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED ATS AND GENERATOR. |
| | 110.3, 90.7, NFPA-110 |
| | |
| | 9) NOTE: PLEASE VERIFY THE ATS WHICH IS BEING AS 3-POLE |
| | AS THE MAIN ON THE NORMAL SIDE INDICATES GFP. EVEN |
| | THOUGH GFP IS NOT REQUIRED, NOT RECOMMENDED DUE TO THE |
| | LS REASONS THERE IS STILL GF SENSING ON THE EM SIDE |
| | WHICH IN ORDER FOR COORDINATION OF THE SYSTEM A 4-POLE |
| | ATS IS REQUIRED. PLEASE SEE SEVERAL DOCUMENTS FROM |
| | ASCO, CAT, DETROIT D AND MANY OTHERS WHICH HAVE |
| | RELEASED DOCUMENTATION ON THIS. PLEASE SEE THE |
| | FOLLOWING SECTIONS LISTED IN THE CODES.700.7D, 700.26, |
| | 240.13, 230.95. NFPA-110 6.2.15 |
| | |
| | 10) NOTE: PLEASE SEE THE LAYOUT IN THE MAIN ELECTRICAL |
| | ROOM IS BEING REQUIRED TO BE CHANGED IN ORDER FOR THE |
| | EMERGENCY MAIN NOT TO BE LOCATED ON THE WALL |
| | IMMEDIATELY ADJACENT TO THE NORMAL POWER WHICH ALREADY |
| | HAS THE EMERGENCY SYSTEMS NORMAL POWER IN MAIN SERVICE |
| | EQUIPMENT(?) (SEE OTHER NOTES). |
| | PLEASE SEE NFPA-110 DOES PERMIT THIS. 7.2.2, 7.2.2.1 |
| | PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT |
| | CANDLES, THIS WILL NEED TO BE SHOWN ON PLANS. PLEASE |
| | SEE NOTE FOR REQUIRED PHOTO-METRICS WHICH THIS CAN BE |
| | ON THOSE NEW SHEETS. |
| | |
| | ** PLEASE SEE CHAPTER AND 10 FOR OTHER REQUIREMENTS FOR |
| | GEN ROOM. |
| | |
| | 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL |
| | EGRESS PATHS INCLUDING HALLWAYS AND STAIRS. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2 WHICH REQUIRES 10FT |
| | CANDLES UNDER NORMAL FOR STAIRS AND 1FT CANDLES UNDER |
| | EMERGENCY CONDITIONS. |
| | ** SEE NOTE ABOVE FOR GEN ROOM. |
| | |
| | 12) NOTE: PLEASE KNOW THE FOLLOWING LOCATIONS WILL BE |
| | REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME |
| | SORT. PLEASE SEE STAIRS WILL BE REQUIRED TO CONTAIN |
| | BATTERY BACK UP FIXTURES TO MEET THE MINIMUM 1FT CD |
| | LEVEL. |
| | PLEASE SEE THE ELEVATOR ROOMS, MAINS ELECTRICAL ROOM, |
| | THE IT ROOM, FIRE PUMP ROOM, GENERATOR ROOMAND |
| | BATHROOMS WHICH ARE NOT SINGLE POINT OF USE WILL ALL |
| | REQUIRE BATTERY BACK UP FIXTURES OF SOME SORT. SOME OF |
| | THESE LOCATIONS DO HAVE THESE ALREADY HOWEVER NOT ALL. |
| | PLEASE SEE 700.12F, 700.16, LS 7.8 AND 7.9 |
| | |
| | 13) NOTE: PLEASE SUBMIT DETAILS FOR THE IT ROOMS AND |
| | COMPLIANCE WITH NFPA-75, AND NEC 645.; |
| | PLEASE SEE NO DETAILS FOR MANY ITEMS INCLUDING CIRCUIT |
| | MINIMUM SIZES. 645.5, 645.10 ETC. |
| | PLEASE SUBMIT ANY UPS SYSTEM SPECS/CUT SHEETS FOR |
| | REVIEW. 90.7, 110.3, 645.11 |
| | PLEASE SEE ROOM DOES NOT SHOW COMPLETE LAYOUT. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 14) NOTE: PLEASE SEE PANEL SCHEDULES WHICH REQUIRE |
| | CIRCUITS TO BE SPECIFIC TO ALL ROOMS AND AREAS WHICH |
| | THEY FEED. THE USE OF *RECEPTACLES* OR LIGHTING* IS NOT |
| | ACCEPTABLE. THE ROOM OR NUMERICAL DESIGNATION(S) AS |
| | SHOWN ON PLANS MAY BE USED. |
| | PLEASE SEE 408.4 AND THE FOLLOWING TEXT WHICH IS TAKEN |
| | FROM THE NEC. |
| | **EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL |
| | BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON |
| | THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| | PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A |
| | SWITCHBOARD. |
| | THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND |
| | LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANEL-BOARDS AND |
| | SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT |
| | DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE |
| | OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND |
| | EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND |
| | LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT |
| | IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS |
| | AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE |
| | PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR |
| | CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS |
| | SPECIFIC TO SWITCHBOARDS AND PANE-BOARDS; HOWEVER, THE |
| | IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL |
| | DISCONNECTING MEANS. |
| | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.** |
| | |
| | PLEASE ADJUST. |
| | |
| | 15) NOTE: PLEASE LIST ALL MINIMUM LEVELS FOR FA HORNS, |
| | STROBES AND HORN/STROBE PER FBC ADA 11-4.28.1,.2 AND |
| | .3(4). |
| | CHAPTER 11 IS QUOTED AND MOST DEVICES ARE NOTED, |
| | HOWEVER NOT ALL. |
| | THIS CAN BE ON DEVICE LEGEND OF ELECTRICAL AND FA |
| | SHEETS. |
| | |
| | 16) NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE |
| | UNDER A SEPARATE PERMIT. |
| | PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE |
| | EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE |
| | INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER |
| | NFPA-101 7.2.1, 7.2.1.6.2. |
| | |
| | 17) NOTE: PLEASE KNOW THAT ALL OTHER LOW VOLTAGE |
| | SYSTEMS SUCH AS VOICE, DATA, CATV, PHONE ETC WILL BE |
| | REQUIRED TO BE UNDER SEPARATE PERMIT. THESE PLANS MAY |
| | BE USED AND REFERENCE FOR A *TURN-AROUND* PERMIT |
| | HOWEVER SEPARATE PERMIT IS REQUIRED ALONG WITH FEES FOR |
| | THIS VALUATION. |
| | |
| | 18) NOTE: PLEASE SUBMIT A GROUNDING ELECTRODE RISER FOR |
| | BUILDING. THIS MAY ON A SEPARATE SHEET OR ON THE |
| | ONE-LINE DIAGRAM. |
| | 250.50, 250.30, 250.58. |
| | FBC 106.1.2 |
| | |
| | 19) NOTE: PLEASE PROVIDE SHEET FOR WALL/FLOOR |
| | PENETRATIONS DETAILS FOR LISTED RATINGS OF WALL/FLOOR |
| | RATINGS. |
| | 300.21, FBC 106.1.2 |
| | |
| | 20) NOTE: PLEASE INDICATE THE DISCONNECTING MEANS FOR |
| | CIRCUITS AT THE DETACHED BUILDING/STRUCTURE AS SHOWN. |
| | 225.31-225.39. |
| | |
| | 21) NOTE: PLEASE CLARIFY AND SHOW WHERE DISCONNECTS ARE |
| | LOCATED FOR THE CHILLER PLANT A/C EQUIPMENT ARE |
| | LOCATED. |
| | 440.11, 110.26 ETC. |
| | |
| | 22) NOTE: PLEASE EXPLAIN FIXTURE TYPE CHANGE IN STAIRS |
| | AS THE LOWER LEVEL SHOWS ONE TYPE AND THEN CHANGES. |
| | PLEASE BE SURE TO SEE COMMENT ABOVE WITH RESPECT TO |
| | REQUIRED BATTERY BACK UP. |
| | FBC 106.1.2 |
| | |
| | 23) NOTE: PLEASE SEE 620.22,23 AND 24 AS DEDICATED |
| | CIRCUITS ARE REQUIRED FOR THESE AREAS. PLEASE KNOW SOME |
| | OF THESE CIRCUITS AS SHOWN ON PLANS FEEDING DEVICES IN |
| | OTHER AREAS. |
| | PLEASE SEE SOME ARE OK, HOWEVER PLEASE DETAIL CIRCUIT |
| | DESIGNATIONS AS STATED FOR 408.4 NOTE # 14. |
| | |
| | 24) NOTE: PLEASE SEE PLANS INDICATE SYMBOLS WHICH ARE |
| | NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE BE SURE TO GO |
| | OVER PLANS. |
| | FBC 106.1.2 |
| | |
| | 25) NOTE: PLEASE SEE WIRE CONDUIT SCHEDULE C-15 |
| | MENTIONS TO SEE GROUNDING NOTE FOR TRANSFORMERS. PLEASE |
| | CLARIFY WHERE THIS IS. PLEASE SHOW DETAIL WHERE THESE |
| | ATTACHED. SEE NOTE 18 ABOVE. |
| | PLEASE ALSO SEE C-2 WHICH STATES THE SAME ETC. PLEASE |
| | SEE THE ONLY NOTE AT THE BOTTOM RIGHT HAND SIDE OF |
| | E3.01 STATES *AND/OR* FOR CONNECTIONS. PLEASE SEE THAT |
| | CODE REQUIRES THE ATTACHED LOCATIONS AND CAN NOT BE |
| | *OR*, ALL ARE REQUIRED. |
| | 250.20,250.30, 250.50 |
| | |
| | 26) NOTE: PLEASE SUBMIT LOAD CALCULATIONS/SUMMARY ON |
| | HOW LOADS WERE DERIVED. PLEASE INCLUDE ALL LARGEST |
| | MOTOR LOADS AND CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42, NEC 220. |
| | |
| | 27) NOTE: PLEASE SEE H5 ON RISER IS NOTED AS 225AMPS |
| | WITH A 125AMP FEED FROM MSBD, HOWEVER H5 SCHEDULE SHOWS |
| | THIS PANEL AS 100AMPS. |
| | PLEASE CORRELATE. |
| | |
| | 28) NOTE: PLEASE COMPLETE ALL BRANCH CIRCUIT CONDUCTORS |
| | ON PANELS FOR OTHER THAN THE FEEDERS/CONDUCTORS WHICH |
| | ARE NOTED ON ONE-LINE. |
| | 240.4, 310.16, 215.5 408.4 ETC |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 29) NOTE: PLEASE SEE L1 AS RISER SHOWS THIS WITH A |
| | 250AMP MCB AND A 400AMP RATED PANEL, YE THE PANEL |
| | SCHEDULE SHOWS THIS AS A 225AMP RATED PANEL? PLEASE |
| | ADJUST. |
| | NEC. |
| | FBC 106.1.2 |
| | |
| | 30) NOTE: PLEASE SEE PANEL L2 WHICH IS SHOWN WITH OUT |
| | ANY OCP FOR MAIN BREAKER AND THIS IS SHOWN AS A 225AMP |
| | PANEL ALSO. PLEASE SEE RISER WHICH SHOWS THIS AS 250AMP |
| | MCB ON A 400AMP RATED PANEL. |
| | |
| | 31) NOTE: PLEASE SEE FEEDERS TO T-5 ARE NOT RATED FOR |
| | THE 70AMP BREAKER. |
| | 310.16, 110.14 |
| | |
| | 32) NOTE: PLEASE SEE PANEL SCHEDULE L3 WHICH DOES NOT |
| | SHOW ANY OCP FOR EACH OF THE PANELS L3A AND L3B. PLEASE |
| | CORRELATE WITH RISER. |
| | FBC 106.1.2 |
| | |
| | 33) NOTE: PLEASE SEE FEEDERS FROM SH-3 AND SH-5 FOR |
| | T-S3 AND T-S5 ARE NOT RATED FOR THE OCP AS SHOWN ON |
| | PANEL SCHEDULES. |
| | PLEASE SEE 310.16, 240.4, 110.14. |
| | PLEASE ADJUST. |
| | |
| | 34) NOTE: PLEASE SEE SHEET E5.10 WHICH BLOCK FOR PANEL |
| | SCHEDULES INDICATES SL1C AS SLC. |
| | MISPRINT) |
| | |
| | 35) NOTE: PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE |
| | EMERGENCY STAND-BY POWER. |
| | 220, 700,701. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-10 14:13:59 | 2007-06-10 14:13:59 |
| | IN PROGRESS. |
| 2007-06-08 20:33:48 | 2007-06-08 20:33:48 |
| | REVIEW TO CONTINUE ON 6/9 OR 6/10 |
| 2007-06-08 20:24:50 | 2007-06-08 20:24:50 |
| | HOLD RELEASED, NEW SHEETS BROUGHT IN. 1-ROLL IN |
| | ELECTRIC FOR REVIEW. |
| 2007-06-08 09:51:04 | 2007-06-08 09:51:04 |
| | PLANS IN ELEC FOR REVIEW. |
| | |
| | INFORMED BY LUIS MARTINEZ, REVIEW IS TO BE PLACED ON |
| | HOLD AS CONTRACTOR IS BRINGING IN NEW REVISED SHEETS TO |
| | BE INSERTED INTO SETS. REVIEW FOR DATED ORDER WILL BE |
| | PASSED. |