Plan Review Notes
Plan Review Notes For Permit 07050361
Permit Number 07050361
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-10 18:30:102007-06-10 18:30:10
  
 *** UNSAT ***
  
 PALM BEACH COUNTY HEALTH DEPARTMENT.
  
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT. EVEN WHEN PLANS ARE CODE
 COMPLIANT, PLANS WILL STILL REMAIN IN A FAILED STATUS
 AS THE REVIEW OF PERMIT APPLICATIONS, LICENSES, LICENSE
 VERIFICATION ETC WILL STILL NEED TO BE DONE AT THE TIME
 OF APPLICATION.
  
 2) NOTE: PLEASE SEE ADDRESSING OF SAID PROJECT IS STILL
 YET TO BE FINALIZED. ONCE THIS IS DONE ALL
 DOCUMENTATION SUBMITTED IS REQUIRED TO CONTAIN THE
 CORRECT ADDRESS ON TITLE BLOCKS AS WELL AS SUPPORTING
 DOCUMENTS.
 PLEASE SEE COMMENTS FORM ADDRESSING REVIEWER.
 FAC 61G1-16.004, 61G15-23.002
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ALL FIRMS
 SHALL BE COMPLETE ON ALL SHEETS WITH ALL INFORMATION AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODES. 61G1-16.004,
 61G15-23.002
 PLEASE SEE ALL SHEETS WHICH CONTAIN TITLE BLOCKS SHALL
 CONTAIN THE INFORMATION.
 PLEASE SEE LANDSCAPE PLANS MISSING REQUIRED PRINTED
 NAME, PRINTED LICENSE NUMBER OF ARCHITECT AS WELL AS
 PRINTED CERTIFICATE OF AUTHORIZATION NUMBER. PLEASE SEE
 MEP PLANS WHICH CONTAINS TITLE BLOCKS FOR FIRMS, YET
 THE CA # IS MISSING.
 PLEASE SEE THE MEP PLANS WHICH CONTAINS TITLE BLOCKS
 FOR A SEPARATE LANDSCAPE DESIGN FIRM AS LISTED ON COVER
 SHEET AND AS SUBMITTED IN PROJECT ROLL OF PLANS. **
 PLEASE KNOW THERE ARE MANY ITEMS MISSING, PLEASE BE
 SURE TO THROUGH ALL SHEETS.
 ** PLEASE SEE THE CA # ON MANY SHEETS IS VERY
 SMALL/BLURRED AND NOT EASILY READ.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 4) NOTE: PLEASE SEE THE SEAL IN USE ON THE LANDSCAPE
 SHEETS IS NOT ACCEPTABLE PER FAC 61G1-16.002 WHICH
 REQUIRES A MINIMUM SIZE. THIS IS NOT A NEW CHANGE TO
 THE FAC.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 5) NOTE: PLEASE BE SURE ARCHITECTURAL PLANS AND
 ELECTRICAL PLANS CONTAIN THE FOLLOWING CODES AT A
 MINIMUM. (SOME ARE ALREADY ON PLANS ON SOME SHEETS.
 2004 FBC W/2006 REVISIONS, ON A SHEETS.
 2003 NFPA-101 ON A SHEETS.
 2002 NFPA-72 ON A SHEETS.
 2003 NFPA-20 NOT ON ANY.
 2002 NFPA-110 NOT ON ANY.
 2005 NFPA-70 (NEC) ON A SHEETS.
  
 **THERE MAY BE OTHER CODES REQUESTED FROM OTHER
 TRADES.
  
 6) NOTE:PLEASE SEE THE FOLLOWING NOTES ARE FOR FBC
 2004 W/2006 REVISIONS TO CHAPTER 13. THERE ARE ITEMS
 MISSING WHICH CAN NOT BE REVIEWED AT THIS TIME.
 A) PLEASE SEE ENERGY CALCULATIONS AS THESE NEED TO BE
 SIGNED, DATED AND SEALED BY THE RESPONSIBLE DESIGNER(S)
 OF RECORD. 13-103.1.1.1 ALL THREE SETS.
 B) PLEASE SEE THESE SAME SHEETS REQUIRES THE
 OWNER/AGENT TO SIGN ALL THREES SETS.
 C) PLEASE SEE THE CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH PLANS FOR THE METHODS OF CONTROLS. THE
 CALCULATIONS INDICATE *MANUAL ON/OFF* CONTROLS WHICH IS
 NOT POSSIBLE WHEN A FULLY AUTOMATED SYSTEM(S) AND
 DEVICES ARE REQUIRED. SOME OF THESE ARE SHOWN ON
 PLANS.13-415.1AB.1.1, 13-415.2
 D) PLEASE SEE MISSING ZONES FOR SYSTEM(S). PLEASE SEE
 PLANS MENTIONS LIGHTING CONTACTOR FOR HALLWAYS, HOWEVER
 NO DETAILS OR INFORMATION FOR EACH OF THESE REQUIRED
 FOR EACH FLOOR PER 13-415.1.ABC.1.1, .1.2 AND .1.3 WAS
 SUBMITTED. PLEASE SEE LOCATIONS OF OVER RIDES REQUIRE
 THESE TO BE LOCATED SO THE OPERATOR CAN VISUALLY SEE
 THE LIGHTING BEING OVER-RIDDEN. THIS IS NOT POSSIBLE IF
 THIS OVER RIDE IS IN A JANITOR'S CLOSET.
 E) PLEASE INDICATE ALL DEVICES FOR ALL SEPARATE SPACES
 AS THERE ARE ROOMS/AREAS WHICH DO NOT INDICATE ANY
 CONTROL DEVICE(S).
 F) PLEASE BE SURE TO INCLUDE SCHEDULING FOR SYSTEM(S)
 PROPOSED.
 G) PLEASE INCLUDE ALL DEVICES, OVER RIDE TIMES
 (MAXIMUM) AND COORDINATE ON DEVICE LEGEND.
 H) PLEASE SEE LIGHTING DETAIL ON E5.01 IS NOT
 POSSIBLE.
 I) PLEASE SEE THERE ARE SEVERAL FIXTURES ON ENERGY
 CALCULATIONS WHICH DO NOT MATCH WITH FIXTURE LEGEND OR
 PLANS AND REVERSE AS WELL AS FIXTURES ON FIXTURE LEGEND
 NOT IN CALCULATIONS. THE NUMBER OF FIXTURES, WATTAGES
 ON CALCULATIONS NEEDS TO CORRELATE WITH THE PLANS AND
 FIXTURE LEGEND.
  
 7) NOTE: PLEASE SEE THE FIRE PUMP MAIN SHOWN IN MAIN
 ELECTRICAL ROOM IS NOT PERMITTED.
 PLEASE ALSO SUBMIT COMPLETE DETAILS FOR THE PROPOSED
 SCENARIO AS THE FIRE PUMP USUALLY CONTAINS THE MAIN
 OCP, ATS AND LOCKED ROTOR CURRENT SETTINGS PER LISTING
 OF EQUIPMENT. PLEASE SEE SHOWING OCP IN FRONT OF THE
 FPC IS NOT PERMITTED.
 PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS FOR
 FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER. PLEASE
 SEE 110.3,90.7, 695.4B1, 695.3 NFPA-20 CHAPTERS 9 AND
 10.
 PLEASE SEE 9.6.2.2 FOR MINIMUM FUEL REQUIRED FOR
 GENERATOR. PLEASE KNOW ONCE THE FUEL CONSUMPTION ON THE
 GENERATOR WITH THESE LOADS CAN BE VERIFIED THEN PROVIDE
 INFORMATION ON PLANS.
  
 8) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED ATS AND GENERATOR.
 110.3, 90.7, NFPA-110
  
 9) NOTE: PLEASE VERIFY THE ATS WHICH IS BEING AS 3-POLE
 AS THE MAIN ON THE NORMAL SIDE INDICATES GFP. EVEN
 THOUGH GFP IS NOT REQUIRED, NOT RECOMMENDED DUE TO THE
 LS REASONS THERE IS STILL GF SENSING ON THE EM SIDE
 WHICH IN ORDER FOR COORDINATION OF THE SYSTEM A 4-POLE
 ATS IS REQUIRED. PLEASE SEE SEVERAL DOCUMENTS FROM
 ASCO, CAT, DETROIT D AND MANY OTHERS WHICH HAVE
 RELEASED DOCUMENTATION ON THIS. PLEASE SEE THE
 FOLLOWING SECTIONS LISTED IN THE CODES.700.7D, 700.26,
 240.13, 230.95. NFPA-110 6.2.15
  
 10) NOTE: PLEASE SEE THE LAYOUT IN THE MAIN ELECTRICAL
 ROOM IS BEING REQUIRED TO BE CHANGED IN ORDER FOR THE
 EMERGENCY MAIN NOT TO BE LOCATED ON THE WALL
 IMMEDIATELY ADJACENT TO THE NORMAL POWER WHICH ALREADY
 HAS THE EMERGENCY SYSTEMS NORMAL POWER IN MAIN SERVICE
 EQUIPMENT(?) (SEE OTHER NOTES).
 PLEASE SEE NFPA-110 DOES PERMIT THIS. 7.2.2, 7.2.2.1
 PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT
 CANDLES, THIS WILL NEED TO BE SHOWN ON PLANS. PLEASE
 SEE NOTE FOR REQUIRED PHOTO-METRICS WHICH THIS CAN BE
 ON THOSE NEW SHEETS.
  
 ** PLEASE SEE CHAPTER AND 10 FOR OTHER REQUIREMENTS FOR
 GEN ROOM.
  
 11) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS INCLUDING HALLWAYS AND STAIRS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2 WHICH REQUIRES 10FT
 CANDLES UNDER NORMAL FOR STAIRS AND 1FT CANDLES UNDER
 EMERGENCY CONDITIONS.
 ** SEE NOTE ABOVE FOR GEN ROOM.
  
 12) NOTE: PLEASE KNOW THE FOLLOWING LOCATIONS WILL BE
 REQUIRED TO CONTAIN A BATTERY BACK UP FIXTURE OF SOME
 SORT. PLEASE SEE STAIRS WILL BE REQUIRED TO CONTAIN
 BATTERY BACK UP FIXTURES TO MEET THE MINIMUM 1FT CD
 LEVEL.
 PLEASE SEE THE ELEVATOR ROOMS, MAINS ELECTRICAL ROOM,
 THE IT ROOM, FIRE PUMP ROOM, GENERATOR ROOMAND
 BATHROOMS WHICH ARE NOT SINGLE POINT OF USE WILL ALL
 REQUIRE BATTERY BACK UP FIXTURES OF SOME SORT. SOME OF
 THESE LOCATIONS DO HAVE THESE ALREADY HOWEVER NOT ALL.
 PLEASE SEE 700.12F, 700.16, LS 7.8 AND 7.9
  
 13) NOTE: PLEASE SUBMIT DETAILS FOR THE IT ROOMS AND
 COMPLIANCE WITH NFPA-75, AND NEC 645.;
 PLEASE SEE NO DETAILS FOR MANY ITEMS INCLUDING CIRCUIT
 MINIMUM SIZES. 645.5, 645.10 ETC.
 PLEASE SUBMIT ANY UPS SYSTEM SPECS/CUT SHEETS FOR
 REVIEW. 90.7, 110.3, 645.11
 PLEASE SEE ROOM DOES NOT SHOW COMPLETE LAYOUT.
 FBC 106.1.2, 106.3.5.1.2
  
 14) NOTE: PLEASE SEE PANEL SCHEDULES WHICH REQUIRE
 CIRCUITS TO BE SPECIFIC TO ALL ROOMS AND AREAS WHICH
 THEY FEED. THE USE OF *RECEPTACLES* OR LIGHTING* IS NOT
 ACCEPTABLE. THE ROOM OR NUMERICAL DESIGNATION(S) AS
 SHOWN ON PLANS MAY BE USED.
 PLEASE SEE 408.4 AND THE FOLLOWING TEXT WHICH IS TAKEN
 FROM THE NEC.
 **EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.
 THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND
 LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANEL-BOARDS AND
 SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT
 DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE
 OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND
 LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT
 IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS
 AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE
 PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR
 CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS
 SPECIFIC TO SWITCHBOARDS AND PANE-BOARDS; HOWEVER, THE
 IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL
 DISCONNECTING MEANS.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 PLEASE ADJUST.
  
 15) NOTE: PLEASE LIST ALL MINIMUM LEVELS FOR FA HORNS,
 STROBES AND HORN/STROBE PER FBC ADA 11-4.28.1,.2 AND
 .3(4).
 CHAPTER 11 IS QUOTED AND MOST DEVICES ARE NOTED,
 HOWEVER NOT ALL.
 THIS CAN BE ON DEVICE LEGEND OF ELECTRICAL AND FA
 SHEETS.
  
 16) NOTE: PLEASE SEE THE LV SECURITY IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
 PLEASE KNOW ANY ACCESS CONTROL DEVICES MAY NOT IMPEDE
 EGRESS UNDER NORMAL OR EMERGENCY CONDITIONS. MORE
 INFORMATION MAY BE REQUIRED UNDER THIS PERMIT PER
 NFPA-101 7.2.1, 7.2.1.6.2.
  
 17) NOTE: PLEASE KNOW THAT ALL OTHER LOW VOLTAGE
 SYSTEMS SUCH AS VOICE, DATA, CATV, PHONE ETC WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT. THESE PLANS MAY
 BE USED AND REFERENCE FOR A *TURN-AROUND* PERMIT
 HOWEVER SEPARATE PERMIT IS REQUIRED ALONG WITH FEES FOR
 THIS VALUATION.
  
 18) NOTE: PLEASE SUBMIT A GROUNDING ELECTRODE RISER FOR
 BUILDING. THIS MAY ON A SEPARATE SHEET OR ON THE
 ONE-LINE DIAGRAM.
 250.50, 250.30, 250.58.
 FBC 106.1.2
  
 19) NOTE: PLEASE PROVIDE SHEET FOR WALL/FLOOR
 PENETRATIONS DETAILS FOR LISTED RATINGS OF WALL/FLOOR
 RATINGS.
 300.21, FBC 106.1.2
  
 20) NOTE: PLEASE INDICATE THE DISCONNECTING MEANS FOR
 CIRCUITS AT THE DETACHED BUILDING/STRUCTURE AS SHOWN.
 225.31-225.39.
  
 21) NOTE: PLEASE CLARIFY AND SHOW WHERE DISCONNECTS ARE
 LOCATED FOR THE CHILLER PLANT A/C EQUIPMENT ARE
 LOCATED.
 440.11, 110.26 ETC.
  
 22) NOTE: PLEASE EXPLAIN FIXTURE TYPE CHANGE IN STAIRS
 AS THE LOWER LEVEL SHOWS ONE TYPE AND THEN CHANGES.
 PLEASE BE SURE TO SEE COMMENT ABOVE WITH RESPECT TO
 REQUIRED BATTERY BACK UP.
 FBC 106.1.2
  
 23) NOTE: PLEASE SEE 620.22,23 AND 24 AS DEDICATED
 CIRCUITS ARE REQUIRED FOR THESE AREAS. PLEASE KNOW SOME
 OF THESE CIRCUITS AS SHOWN ON PLANS FEEDING DEVICES IN
 OTHER AREAS.
 PLEASE SEE SOME ARE OK, HOWEVER PLEASE DETAIL CIRCUIT
 DESIGNATIONS AS STATED FOR 408.4 NOTE # 14.
  
 24) NOTE: PLEASE SEE PLANS INDICATE SYMBOLS WHICH ARE
 NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE BE SURE TO GO
 OVER PLANS.
 FBC 106.1.2
  
 25) NOTE: PLEASE SEE WIRE CONDUIT SCHEDULE C-15
 MENTIONS TO SEE GROUNDING NOTE FOR TRANSFORMERS. PLEASE
 CLARIFY WHERE THIS IS. PLEASE SHOW DETAIL WHERE THESE
 ATTACHED. SEE NOTE 18 ABOVE.
 PLEASE ALSO SEE C-2 WHICH STATES THE SAME ETC. PLEASE
 SEE THE ONLY NOTE AT THE BOTTOM RIGHT HAND SIDE OF
 E3.01 STATES *AND/OR* FOR CONNECTIONS. PLEASE SEE THAT
 CODE REQUIRES THE ATTACHED LOCATIONS AND CAN NOT BE
 *OR*, ALL ARE REQUIRED.
 250.20,250.30, 250.50
  
 26) NOTE: PLEASE SUBMIT LOAD CALCULATIONS/SUMMARY ON
 HOW LOADS WERE DERIVED. PLEASE INCLUDE ALL LARGEST
 MOTOR LOADS AND CONTINUOUS LOADS AT 125%.
 215.3, 230.42, NEC 220.
  
 27) NOTE: PLEASE SEE H5 ON RISER IS NOTED AS 225AMPS
 WITH A 125AMP FEED FROM MSBD, HOWEVER H5 SCHEDULE SHOWS
 THIS PANEL AS 100AMPS.
 PLEASE CORRELATE.
  
 28) NOTE: PLEASE COMPLETE ALL BRANCH CIRCUIT CONDUCTORS
 ON PANELS FOR OTHER THAN THE FEEDERS/CONDUCTORS WHICH
 ARE NOTED ON ONE-LINE.
 240.4, 310.16, 215.5 408.4 ETC
 FBC 106.3.5.1.2, 106.1.2
  
 29) NOTE: PLEASE SEE L1 AS RISER SHOWS THIS WITH A
 250AMP MCB AND A 400AMP RATED PANEL, YE THE PANEL
 SCHEDULE SHOWS THIS AS A 225AMP RATED PANEL? PLEASE
 ADJUST.
 NEC.
 FBC 106.1.2
  
 30) NOTE: PLEASE SEE PANEL L2 WHICH IS SHOWN WITH OUT
 ANY OCP FOR MAIN BREAKER AND THIS IS SHOWN AS A 225AMP
 PANEL ALSO. PLEASE SEE RISER WHICH SHOWS THIS AS 250AMP
 MCB ON A 400AMP RATED PANEL.
  
 31) NOTE: PLEASE SEE FEEDERS TO T-5 ARE NOT RATED FOR
 THE 70AMP BREAKER.
 310.16, 110.14
  
 32) NOTE: PLEASE SEE PANEL SCHEDULE L3 WHICH DOES NOT
 SHOW ANY OCP FOR EACH OF THE PANELS L3A AND L3B. PLEASE
 CORRELATE WITH RISER.
 FBC 106.1.2
  
 33) NOTE: PLEASE SEE FEEDERS FROM SH-3 AND SH-5 FOR
 T-S3 AND T-S5 ARE NOT RATED FOR THE OCP AS SHOWN ON
 PANEL SCHEDULES.
 PLEASE SEE 310.16, 240.4, 110.14.
 PLEASE ADJUST.
  
 34) NOTE: PLEASE SEE SHEET E5.10 WHICH BLOCK FOR PANEL
 SCHEDULES INDICATES SL1C AS SLC.
 MISPRINT)
  
 35) NOTE: PLEASE SUBMIT A COMPLETE LOAD SUMMARY FOR THE
 EMERGENCY STAND-BY POWER.
 220, 700,701.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-10 14:13:592007-06-10 14:13:59
 IN PROGRESS.
2007-06-08 20:33:482007-06-08 20:33:48
 REVIEW TO CONTINUE ON 6/9 OR 6/10
2007-06-08 20:24:502007-06-08 20:24:50
 HOLD RELEASED, NEW SHEETS BROUGHT IN. 1-ROLL IN
 ELECTRIC FOR REVIEW.
2007-06-08 09:51:042007-06-08 09:51:04
 PLANS IN ELEC FOR REVIEW.
  
 INFORMED BY LUIS MARTINEZ, REVIEW IS TO BE PLACED ON
 HOLD AS CONTRACTOR IS BRINGING IN NEW REVISED SHEETS TO
 BE INSERTED INTO SETS. REVIEW FOR DATED ORDER WILL BE
 PASSED.