| 2007-06-27 09:21:41 | PALM BEACH COUNTY HEALTH DEPARTMENT BUILDING |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07050361 |
| | ADD: 800 CLEMATIS ST |
| | CONT: THE MORGANTI GROUP, INC ?PLAN REVIEW |
| | ONLY? |
| | TEL: (561)262-6771 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING TYPE;IB |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1B) PLANS SUBMITTED FOR PERMIT APPLICATION(FIRST TIME |
| | REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE |
| | 2004 FBC BUILDING WITH THE2007 REVISIONS. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL |
| | |
| | 2) COMPLIED. FBC 1802.2.1 QUESTIONABLE SOILS, WHERE |
| | THE SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR |
| | WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| | IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL |
| | REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 3)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 4)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION |
| | SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT |
| | HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM |
| | AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE |
| | PERMIT MAY BE ISSUED. |
| | |
| | 5)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING |
| | ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT |
| | IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| | WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE |
| | OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED |
| | TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE |
| | FINAL INSPECTION. |
| | |
| | |
| | 8) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION |
| | TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 9) THE TITLE BLOCK INFORMATION IS TO PROVIDE THE |
| | ADDRESS, LOCATION OF THE PROJECT, FAC 61G1-16.004 |
| | (ARCHITECTS) AND 61G15-23.002 (ENGINEERS). |
| | |
| | 10) SHEET LS0.01: |
| | 10A) TABLE-VI BUILDING HEIGHT AND AREA SEE THE |
| | ALLOWABLE HEIGHT IN STORIES WAS PLACED IN THE WRONG |
| | LINE. |
| | |
| | 10B) TABLE-IV TYPE OF CONSTRUCTION SEE BEAMS SUPPORTING |
| | ROOF ONLY REQUIRES A 2HR RATING, SEE FOOTNOTE ?C? FOR |
| | EXCEPTIONS. |
| | |
| | 11) THE SET OF PLANS HAVE CIVIL PLANS INDICATING THE |
| | VARIOUS WORK TO BE COMPLETED ON THE PROJECT, WHAT I |
| | WASN?T ABLE TO FIND WAS A SURVEY. THERE APPEARS TO BE |
| | AN EASEMENT OR ALLEYWAY RUNNING EAST TO WEST ON THIS |
| | LOT. WHAT ALSO APPEARS THERE IS A PROPERTY LINE EITHER |
| | IN THE WEST PORTION OF THE BUILDING OR DIRECTLY TO THE |
| | WEST WALL OF THE PROPOSED BUILDING. |
| | PLEASE PROVIDE SOME CLARIFICATION. A UNITY OF TITLE MAY |
| | ALSO BE REQUIRED PLUS AN ABANDONMENT OF AN EASEMENT. |
| | TABLE 601, TABLE 602 AND TABLE 704.8. |
| | |
| | 12)SITE PLAN A1.01 INDICATES THE MAIN ENTRY ON THE |
| | EAST SIDE BUT THE PARKING AREA TO BE ON THE SOUTHWEST |
| | SIDE OF THE BUILDING. PLEASE LOOK AT THE SECTION 11-6.1 |
| | AND 11-6.2 FOR ENTRANCES. PLEASE INDICATE HOW |
| | COMPLIANCE WILL BE MET? |
| | |
| | 11-6.1 GENERAL. |
| | MEDICAL CARE FACILITIES INCLUDED IN THIS SECTION ARE |
| | THOSE IN WHICH PEOPLE RECEIVE PHYSICAL OR MEDICAL |
| | TREATMENT OR CARE AND WHERE PERSONS MAY NEED ASSISTANCE |
| | IN RESPONDING TO AN EMERGENCY AND WHERE THE PERIOD OF |
| | STAY MAY EXCEED 24 HOURS. IN ADDITION TO THE |
| | REQUIREMENTS OF SECTIONS 11-4.1 THROUGH 11-4.35 , |
| | MEDICAL CARE FACILITIES AND BUILDINGS SHALL COMPLY WITH |
| | SECTION 11-6 . |
| | 11-6.2 ENTRANCES. |
| | AT LEAST ONE ACCESSIBLE ENTRANCE THAT COMPLIES WITH |
| | SECTION 11-4.14 SHALL BE PROTECTED FROM THE WEATHER BY |
| | CANOPY OR ROOF OVERHANG. SUCH ENTRANCES SHALL |
| | INCORPORATE A PASSENGER LOADING ZONE THAT COMPLIES WITH |
| | SECTION 11-4.6.6 . |
| | |
| | 13) PLEASE PROVIDE ADDITIONAL INFORMATION AS TO THE |
| | TYPES OF MEDICAL CARE AND OR TREATMENT THIS FACILITY |
| | WILL MANAGE. 11-4.1.2(5)(D)AT FACILITIES PROVIDING |
| | MEDICAL CARE AND OTHER SERVICES FOR PERSONS WITH |
| | MOBILITY IMPAIRMENTS, PARKING SPACES COMPLYING WITH |
| | SECTION 11-4.6 SHALL BE PROVIDED IN ACCORDANCE WITH |
| | SECTION 11-4.1.2 (5)(A) EXCEPT AS FOLLOWS: |
| | (I)OUTPATIENT UNITS AND FACILITIES: 10 PERCENT OF |
| | THE TOTAL NUMBER OF PARKING SPACES PROVIDED SERVING |
| | EACH SUCH OUTPATIENT UNIT OR FACILITY; |
| | (II)UNITS AND FACILITIES THAT SPECIALIZE IN |
| | TREATMENT OR SERVICES FOR PERSONS WITH MOBILITY |
| | IMPAIRMENTS; 20 PERCENT OF THE TOTAL NUMBER OF PARKING |
| | SPACES PROVIDED SERVING EACH SUCH UNIT OR FACILITY. |
| | |
| | 14) BUILDINGS WITH MULTIPLE ACCESSIBLE ENTRANCES: |
| | 11-4.6.2 LOCATION. |
| | ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING |
| | SHALL BE LOCATED ON THE SHORTEST SAFELY ACCESSIBLE |
| | ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE |
| | ENTRANCE. IN PARKING FACILITIES THAT DO NOT SERVE A |
| | PARTICULAR BUILDING, ACCESSIBLE PARKING SHALL BE |
| | LOCATED ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL TO |
| | AN ACCESSIBLE PEDESTRIAN ENTRANCE OF THE PARKING |
| | FACILITY. IN BUILDINGS WITH MULTIPLE ACCESSIBLE |
| | ENTRANCES WITH ADJACENT PARKING, ACCESSIBLE PARKING |
| | SPACES SHALL BE DISPERSED AND LOCATED CLOSEST TO THE |
| | ACCESSIBLE ENTRANCES |
| | |
| | 15)SHEET A2.00DETAIL# 2, 1003.5.2.WHERE CHANGE IN |
| | ELEVATION OF 12 INCHES (305 MM) OR LESS OCCURS IN EXIT |
| | ACCESS CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS |
| | COMPLYING WITH SECTION 1010 SHALL BE PROVIDED. 1003.5.1 |
| | WHERE A CHANGE IN LEVEL MEANS OF EGRESS NOT EXCEEDING |
| | 21 INCHES (533 MM) IS ACHIEVED BY A STAIR, THE MINIMUM |
| | TREAD DEPTH OF SUCH STAIR SHALL BE 13 INCHES (330 MM) |
| | AND THE PRESENCE AND LOCATION OF EACH STEP SHALL BE |
| | READILY APPARENT. |
| | |
| | 16) SHEET A2.00.1 THE RAMP SECTIONS DO NOT PROVIDE THE |
| | LENGTH OF THE BOTTOM LANDING. |
| | 11-.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT |
| | BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCES. |
| | |
| | 17) SHEET A2.00.1 ON THE RIGHT HAND SIDE OF THE SHEET |
| | THERE ARE THREE DETAILS WITH NO REFERENCE NUMBERS? |
| | PLEASE INDICATE DIMENSIONS ON THE BOTTOM POST DETAIL. |
| | |
| | 18) SHEET A2.01 |
| | 18A) THE CONFERENCE ROOM 1-112 IS A A3 OCCUPANCY GROUP |
| | AND THE PLAN DOES INDICATE A 2HR FIRE PARTITION BETWEEN |
| | THE A3 OCCUPANCY AND THE BUSINESS OCCUPANCY BUT THE |
| | PLAN FAILS TO IDENTIFY THE FIRE AND SMOKE RATED |
| | CORRIDOR REQUIRED FOR THE A3 OCCUPANCY. SEE TABLE |
| | 1016.1. FOR RATED CORRIDORS WITH FIRE SPRINKLERS. |
| | 715.3.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE |
| | BARRIERS. |
| | FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE |
| | PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN |
| | CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A |
| | FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 715.3 |
| | SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C |
| | WITHOUT THE HOSE STREAM TEST. IF A 20-MINUTE FIRE DOOR |
| | ASSEMBLY CONTAINS GLAZING MATERIAL, THE GLAZING |
| | MATERIAL IN THE DOOR ITSELF SHALL HAVE A MINIMUM FIRE |
| | PROTECTION RATING OF 20 MINUTES AND BE EXEMPT FROM THE |
| | HOSE STREAM TEST. GLAZING MATERIAL IN ANY OTHER PART OF |
| | THE DOOR ASSEMBLY, INCLUDING TRANSOM LITES AND |
| | SIDELITES, SHALL BE TESTED IN ACCORDANCE WITH NFPA 257, |
| | INCLUDING THE HOSE STREAM TEST, IN ACCORDANCE WITH |
| | SECTION 715.4 . FIRE DOOR ASSEMBLIES SHALL ALSO MEET |
| | THE REQUIREMENTS FOR A SMOKE- AND DRAFT-CONTROL DOOR |
| | ASSEMBLY TESTED IN ACCORDANCE WITH UL 1784 WITH AN |
| | ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS THE FULL WIDTH |
| | OF THE BOTTOM OF THE DOOR ASSEMBLY |
| | |
| | AS THE PLANS ARE DRAWN CURRENTLY ALL THE CORRIDOR BOTH |
| | SIDES WILL NEED TO BE 1 HR FIRE RATED THE LOBBY |
| | INCLUDINGROOM 1-158 AND CORRIDOR TO DOORS 159 AND |
| | 159A. |
| | |
| | 18B) IN LOOKING AT THE DOOR SCHEDULE FOR RATED DOORS |
| | THE DOOR SCHEDULE FOUND ON SHEET A2.07 INDICATES THE |
| | TYPES OF DOORS, PLEASE RATE DOORS AS PER TABLE 715.3 IN |
| | MINUTES AND HRS. A ?B? LABEL DOOR MEETS THE NOTE 3 |
| | FOUND UNDER DOOR NOTES ON SHEET A2.07 |
| | |
| | 18C) DISCREPANCY PLEASE SEE WALL TAGS (6) AND (6A) |
| | SHEET A9.01 FOR WALL TYPE (6) AND (6A) APPEAR TO HAVE |
| | TYPO? |
| | |
| | 18D) STEEL FIREPROOFING DETAILS FOUND ON A9.0.1.1, |
| | PLEASE PROVIDE THE MANUFACTURERS SPEC FOR FIRE PROOFING |
| | THICKNESS/ HR. RATING FOR COLUMNS AND BEAMS. TABLE |
| | 601. |
| | |
| | 18E) STEEL COLUMN FOUND ON GRID LINE G1 AND 2A PLEASE |
| | PROVIDE PRODUCT INFORMATION ON THE INTUMESCENT PAINT TO |
| | BE APPLIED TO THE COLUMN FACE, 2 HR RATING. TABLE 601. |
| | |
| | 19) SHEET A2.02 |
| | 19A) PLEASE PROVIDE ADDITIONAL INFORMATION FOR THE |
| | FOLLOWING (2) ROOMS, STD/HIV, AND THE |
| | SCHOOL HEALTH ROOMS. THE PLAN JUST SHOWS SQ FT AREA, BY |
| | AREA THEY COULD BE CLASSIFIED AS AN A-3 ASSEMBLY |
| | OCCUPANCY, ARE THERE DESK IN THESE AREAS? IF THEY HAVE |
| | DESKTHE |
| | AREA WOULD BE CONSIDERED BUSINESS? IF CONSIDERED A3 |
| | ASSEMBLY AGAIN AS ON THE FIRST FLOOR THE CORRIDORS AND |
| | DOORS WOULD NEED TO BE RATED. TABLE 1016.1. |
| | |
| | 19B) SHOWER ROOMS 2-239 & 2-240 PLEASE PROVIDE ENLARGED |
| | PLAN WITH DIMENSIONS, PLEASE LOOK AT THE FIGURE 36A |
| | TYPE STALL AND THE 12? OVERLAY BEYOND THE SEAT, PLANS |
| | DO NOT INDICATE THIS CONFIGURATION. NOTE THE 36? ARE |
| | ABSOLUTES! ALSO SHOW THE LOCATION OF THE CONTROLS. SEE |
| | SHEET A4.00. |
| | |
| | 19C) THE MECHANICAL ROOMS LOCATED ON FLOORS 2-5 ALL |
| | HAVE IN COMMON A STRUCTURAL COLUMN, HOW WILL THE FIRE |
| | RATINGS BE COMPLIED WITH TABLE 601? |
| | |
| | 20) SHEET A2.03 |
| | 20A) PLEASE INDICATE THE OCCUPANT LOAD OF COMMUNITY |
| | HEALTH AREA, ARE THERE DESK? |
| | |
| | 20B) THERE IS A LARGE AREA THAT THE ROOM IS NOT |
| | IDENTIFIED APPROXIMATELY COLUMN LINE G AND 5-6? AGAIN |
| | IS THERE TO BE DESK PROVIDE THE OCCUPANT LOAD. |
| | |
| | 20C) IN THE COMPUTER ROOM IS THERE A RAISED DECK OR |
| | FLOOR? IF SO PROVIDE DETAILS AND INCLUDE THE HEIGHT OF |
| | THE RAISED FLOOR. ALSO SEE ACCESSIBLE RAMPS 11-4-8. |
| | |
| | 21) SHEET A2.04 |
| | 21A) PLANS INDICATE LARGE AREAS PLEASE INDICATE IF |
| | THESE AREAS WILL HAVE DESK OR CUBICLES, IF CUBICLES HOW |
| | HIGH WILL THE WALLS BE? MAY INTERFERE WITH EXIT |
| | SIGNAGE! |
| | PROVIDE OCCUPANT LOADS. |
| | |
| | 21B) ROOM 4-420 HIGH DENSITY FILES PLEASE PROVIDE THE |
| | LIVE LOAD TO BE FIGURED FOR THIS AREA? 1607.4 |
| | CONCENTRATED LOADS. |
| | |
| | 22) A2.06 |
| | 22A) ROOF PLAN AND THE EMERGENCY OVER FLOW SCUPPERS, |
| | INDICATE THE SLOPE TO BE |
| | ?? IN 1?-0?WHENEVER THE OVERFLOW SCUPPERS ARE |
| | LOCATED MORE THAN 16?-0? AWAY FROM THE MAIN ROOF DRAIN |
| | IN SITUATIONSWHERE IN HEAVY DOWN POURS THE MAIN DRAIN |
| | CAN?T TAKE ANY MORE WATER THERE IS TO BE NO MORE THAN |
| | 4? OF WATER ON THE ROOF DECK. |
| | 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF |
| | DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW |
| | SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS |
| | THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) |
| | ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED |
| | AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR |
| | DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW |
| | SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, PLUMBING. |
| | |
| | 22B) ROOF PLAN INDICATES DETAIL7 ON SHEET A3.10B1, NO |
| | SUCH PLAN? |
| | |
| | 22C)SECTION 1 OF A3.07 PROVIDES A SECTION DETAIL OF A |
| | CURTAIN WALL SECTION THROUGH TO THE ROOF. THE TOP OF |
| | THE CURTAIN WALL SECTION REFERS TO THE STRUCTURAL SHEET |
| | S10 DETAIL NUMBER |
| | 18, IT APPEARS THAT NO CONNECTION INFORMATION IS |
| | PROVIDED, BOLTS OR WELDS? |
| | |
| | 23) PLAN A2.07.2 & A2.08 BOTH INDICATE BACK TO BACK |
| | STUDS AT DOOR OPENINGS, NOTE TYPE I AND TYPE II |
| | BUILDINGS NO COMBUSTIBLE STUDS, SEE 603.1. |
| | |
| | 24) SHEET A2.08 WINDOWS IN FIRE RATED PARTITIONS, SHOW |
| | COMPLIANCE WITH TABLE 715.4 & 715.4 AND NFPA 80. |
| | PROVIDE NOT ONLY INFORMATION ON THE GLAZING BUT THE |
| | FRAME AS WELL. |
| | |
| | 25) A2.09 FLOOR COVERINGS INDICATES A ?C2? CARPET |
| | PROVIDE THE FOLLOWING MINIMUM CRITICAL RADIANT FLUX FOR |
| | THE CARPET 804.5.1. |
| | |
| | 26) SHEET A4.03.2 |
| | 26A)PROVIDE INFORMATION FOR ELEVATOR CAR TO |
| | ACCOMMODATE AMBULANCE STRETCHERS.3002.4. |
| | |
| | 26B) PLEASE PROVIDETHE ELEVATOR MACHINE ROOM?S SMOKE |
| | DETECTOR AND HOIST WAY WOULD BE LOCATED IN THE |
| | PLANS?3002.8. SHEET A6.01 AND DO NOT SHOW THEM. |
| | |
| | 26C) PLEASE PROVIDE THE FOLLOWING INFORMATION: 3003.1 |
| | STANDBY POWER. |
| | IN BUILDINGS AND STRUCTURES WHERE STANDBY POWER IS |
| | REQUIRED OR FURNISHED TO OPERATE AN ELEVATOR, THE |
| | OPERATION SHALL BE IN ACCORDANCE WITH SECTIONS 3003.1.1 |
| | THROUGH 3003.1.4 . |
| | 3003.1.1 MANUAL TRANSFER. |
| | STANDBY POWER SHALL BE MANUALLY TRANSFERABLE TO ALL |
| | ELEVATORS IN EACH BANK. |
| | 3003.1.2 ONE ELEVATOR. |
| | WHERE ONLY ONE ELEVATOR IS INSTALLED, THE ELEVATOR |
| | SHALL AUTOMATICALLY TRANSFER TO STANDBY POWER WITHIN 60 |
| | SECONDS AFTER FAILURE OF NORMAL POWER. |
| | 3003.1.3 TWO OR MORE ELEVATORS. |
| | WHERE TWO OR MORE ELEVATORS ARE CONTROLLED BY A COMMON |
| | OPERATING SYSTEM, ALL ELEVATORS SHALL AUTOMATICALLY |
| | TRANSFER TO STANDBY POWER WITHIN 60 SECONDS AFTER |
| | FAILURE OF NORMAL POWER WHERE THE STANDBY POWER SOURCE |
| | IS OF SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT |
| | THE SAME TIME. WHERE THE STANDBY POWER SOURCE IS NOT OF |
| | SUFFICIENT CAPACITY TO OPERATE ALL ELEVATORS AT THE |
| | SAME TIME, ALL ELEVATORS SHALL TRANSFER TO STANDBY |
| | POWER IN SEQUENCE, RETURN TO THE DESIGNATED LANDING AND |
| | DISCONNECT FROM THE STANDBY POWER SOURCE. AFTER ALL |
| | ELEVATORS HAVE BEEN RETURNED TO THE DESIGNATED LEVEL, |
| | AT LEAST ONE ELEVATOR SHALL REMAIN OPERABLE FROM THE |
| | STANDBY POWER SOURCE. |
| | 3003.1.4 VENTING. |
| | WHERE STANDBY POWER IS CONNECTED TO ELEVATORS, THE |
| | MACHINE ROOM VENTILATION OR AIR CONDITIONING SHALL BE |
| | CONNECTED TO THE STANDBY POWER SOURCE. |
| | 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION. ELEVATORS |
| | SHALL BE PROVIDED WITH PHASE I EMERGENCY RECALL |
| | OPERATION AND PHASE II EMERGENCY IN-CAR OPERATION IN |
| | ACCORDANCE WITH ASME A17.1. |
| | |
| | 26D) 3004.2 LOCATION OF VENTS. VENTS SHALL BE LOCATED |
| | BELOW THE FLOOR OR FLOORS AT THE TOP OF THE HOIST WAY, |
| | AND SHALL OPEN EITHER DIRECTLY TO THE OUTER AIR OR |
| | THROUGH NONCOMBUSTIBLE DUCTS TO THE OUTER AIR. |
| | NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO PASS THROUGH |
| | THE ELEVATOR MACHINE ROOM PROVIDED THAT PORTIONS OF THE |
| | DUCTS LOCATED OUTSIDE THE HOIST WAY OR MACHINE ROOM ARE |
| | ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE |
| | PROTECTION RATING REQUIRED FOR THE HOIST WAY. HOLES IN |
| | THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES, |
| | CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE |
| | LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51 |
| | MM) OF CLEARANCE ON ALL SIDES. |
| | |
| | 3004.3 AREA OF VENTS. EXCEPT AS PROVIDED FOR IN SECTION |
| | 3004.3.1 , THE AREA OF THE VENTS SHALL NOT BE LESS THAN |
| | 3? PERCENT OF THE AREA OF THE HOIST WAY NOR LESS THAN 3 |
| | SQUARE FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR, AND NOT |
| | LESS THAN 3? PERCENT NOR LESS THAN 0.5 SQUARE FOOT |
| | (0.047 M 2 ) FOR EACH DUMBWAITER CAR IN THE HOIST WAY, |
| | WHICHEVER IS GREATER. OF THE TOTAL REQUIRED VENT AREA, |
| | NOT LESS THAN ONE-THIRD SHALL BE OF THE PERMANENTLY |
| | OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON DETECTION OF |
| | SMOKE FROM ANY OF THE ELEVATOR LOBBY SMOKE DETECTORS. |
| | |
| | 26E) PLEASE NOTE THE FOLLOWING: 3006.5 SHUNT TRIP. |
| | WHERE ELEVATOR HOIST WAYS OR ELEVATOR MACHINE ROOMS |
| | CONTAINING ELEVATOR CONTROL EQUIPMENT ARE PROTECTED |
| | WITH AUTOMATIC SPRINKLERS, A MEANS INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, SECTION 3?9.4, ELEVATOR |
| | SHUTDOWN, SHALL BE PROVIDED TO DISCONNECT AUTOMATICALLY |
| | THE MAIN LINE POWER SUPPLY TO THE AFFECTED ELEVATOR |
| | PRIOR TO THE APPLICATION OF WATER. THIS MEANS SHALL NOT |
| | BE SELF-RESETTING. THE ACTIVATION OF SPRINKLERS OUTSIDE |
| | THE HOIST WAY OR MACHINE ROOM SHALL NOT DISCONNECT THE |
| | MAIN LINE POWER SUPPLY. |
| | |
| | 26F) PLEASE NOTE NEW TO THE 2006 FBC REVISIONS: 3009.1 |
| | ELECTROLYSIS PROTECTION FOR UNDERGROUND HYDRAULIC |
| | ELEVATOR CYLINDERS. |
| | ALL NEWLY INSTALLED UNDERGROUND HYDRAULIC PRESSURE |
| | CYLINDERS SHALL BE ENCASED IN OUTER PLASTIC CONTAINMENT |
| | TO MINIMIZE ELECTROLYTIC CORROSION BETWEEN THE METAL |
| | CYLINDER AND GROUND CATHODE. |
| | 1.THE PLASTIC CASING SHALL BE CAPPED AT THE |
| | BOTTOM, AND ALL JOINTS MUST BE SOLVENT OR HEAT WELDED |
| | TO ENSURE WATER TIGHTNESS. |
| | 2.THE PLASTIC CASING SHALL BE CONSTRUCTED OF |
| | POLYETHYLENE OR POLYVINYL CHLORIDE (PVC). THE PLASTIC |
| | PIPE WALL THICKNESS MUST NOT BE LESS THAN 0.125 INCH |
| | (3.175 MM). |
| | 3.THE NECK OF THE PLASTIC CASING SHALL HAVE A |
| | MEANS OF INSPECTION PROVIDED TO MONITOR THE ANNULUS |
| | BETWEEN THE PRESSURIZED HYDRAULIC CYLINDER AND THE |
| | PROTECTIVE PLASTIC CASING. |
| | 4.REPLACEMENTS OF EXISTING HYDRAULIC CYLINDERS |
| | SHALL BE PROTECTED BY THE AFOREMENTIONED METHOD WHERE |
| | EXISTING PHYSICAL DIMENSIONS PERMIT |
| | |
| | 27) SHEET A4.0527A) DETAIL (4A) SINKS:11-4.24.2 |
| | SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH THE COUNTER |
| | NO HIGHER THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH |
| | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH |
| | SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK |
| | |
| | 28) A4.07SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE |
| | THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 29) SHEET A5.00 |
| | 29A) AT THE BOTTOM AND TOP LANDING HANDRAILS ARE TO: |
| | 11-4.9.4(2) (2) IF HANDRAILS ARE NOT CONTINUOUS, THEY |
| | SHALL EXTEND AT LEAST 12 INCHES (305 MM) BEYOND THE TOP |
| | RISER AND AT LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF |
| | ONE TREAD BEYOND THE BOTTOM RISER. AT THE TOP, THE |
| | EXTENSION SHALL BE PARALLEL WITH THE FLOOR OR GROUND |
| | SURFACE. AT THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO |
| | SLOPE FOR A DISTANCE OF THE WIDTH OF ONE TREAD FROM THE |
| | BOTTOM RISER; THE REMAINDER OF THE EXTENSION SHALL BE |
| | HORIZONTAL [SEE FIGURE 19 (C) AND FIGURE 19 (D)]. |
| | HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4 . |
| | |
| | 29B) 1009.5.3 STAIR IDENTIFICATION. AN APPROVED SIGN |
| | SHALL BE LOCATED AT EACH FLOOR LEVEL LANDING IN ALL |
| | ENCLOSED STAIRWAYS OF BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT. THE SIGN SHALL INDICATE THE FLOOR LEVEL AND THE |
| | AVAILABILITY OF ROOF ACCESS FROM THAT STAIRWAY AND AN |
| | IDENTIFICATION OF THE STAIRWAY. THE SIGN SHALL ALSO |
| | STATE THE FLOOR LEVEL OF AND DIRECTION TO EXIT |
| | DISCHARGE. THE SIGN SHALL BE LOCATED APPROXIMATELY 5 |
| | FEET (1524 MM) ABOVE THE FLOOR LANDING IN A POSITION |
| | WHICH IS READILY VISIBLE WHEN THE DOOR IS IN THE OPEN |
| | OR CLOSED POSITION. THE FLOOR LEVEL DESIGNATION SHALL |
| | ALSO BE TACTILE IN ACCORDANCE WITH CHAPTER 11 . |
| | |
| | 29C)1009.12 ACCESS TO ROOF. BUILDINGS FOUR STORIES OR |
| | MORE IN HEIGHT, EXCEPT THOSE WITH A ROOF SLOPE GREATER |
| | THAN 4:12, SHALL BE PROVIDED WITH A STAIRWAY TO THE |
| | ROOF. SUCH STAIRWAY SHALL BE MARKED AT STREET AND FLOOR |
| | LEVELS WITH A SIGN INDICATING THAT IT CONTINUES TO THE |
| | ROOF. WHERE ROOFS ARE USED FOR ROOF GARDENS OR FOR |
| | OTHER PURPOSES, STAIRWAYS SHALL BE PROVIDED AS REQUIRED |
| | FOR SUCH USE OR OCCUPANCY. |
| | |
| | 30) SHEET S-7 |
| | 30A) CODES AND STANDARDS ASCE 7-02 THE BUILDING |
| | CATEGORY II WITH AN IMPORTANCE FACTOR OF 1.0. IS THIS |
| | BUILDING TO BE USED AS A HEALTH CARE FACILITY THAT MAY |
| | EVER HAVE SURGERY OR BE USED FOR EMERGENCY TREATMENT? |
| | IF SO THIS BUILDING CATEGORY WOULD BE A IV WITH AN |
| | IMPORTANCE FACTOR OF 1.15. THE PRESSURE ZONES ON S-13 |
| | WILL CHANGE WITH THE 1.15 IMPORTANCE FACTOR. |
| | |
| | 30B) PRODUCT APPROVALS:PRODUCT APPROVALS |
| | SUBMITTED WITH PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT |
| | APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE STATE |
| | WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BESUBMITTED WITH A |
| | COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE |
| | APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 30C) ) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 30D)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) |
| | OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRAINER GLASS CURTAIN WALL LMI , REQUIRES FL COVER |
| | SHEET, HIGHLIGHT WHICH GLAZING TYPE |
| | TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF |
| | THE CHARTS PLEASE PROVIDE LEGIBLE |
| | REPORTS. |
| | B) TRAINER GLASS CURTAIN WALL SMI |
| | REQUIRES FL COVER SHEET, HIGHLIGHT WHICH GLAZING TYPE |
| | |
| | TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF |
| | THE CHARTS PLEASE PROVIDE LEGIBLE |
| | REPORTS. |
| | C) BOTH TRAINER GLASS REPORTS DO NOT INDICATE IF THE |
| | ANCHORING INTO MASONRY AND STEEL |
| | SUBSTRATE TOOK THE 1.33 INCREASE NEWER REPORTS |
| | UNDER THE 2004 USUALLY INDICATE NO |
| | 1/3 STRESS INCREASE TAKEN? 2004 FBC 16.5.3.1.1. |
| | |
| | D) YKK AP 35H OUT SWING ALUMINUM DOORLMI, , REQUIRES |
| | FL COVER SHEET, NOTE THIS REPORT REQUIRES THE DESIGN |
| | PRESSURES TO BE DIVIDED BY 1.33, HIGHLIGHT WHICH |
| | GLAZING TYPE |
| | TO BE USED, AND MULLIONS. THE HEADS ARE CUT OFF THE |
| | CHARTS PLEASEPROVIDE LEGIBLE |
| | REPORTS. |
| | |
| | E) FIREDOOR 8080 SERIES OUT SWING COMMERCIAL STEEL DOOR |
| | LMI, REQUIRES FL COVER SHEET, |
| | CURRENTLY WITH A 1.0 IMPORTANCE FACTOR MEETS WIND |
| | LOADS, TO BE DETERMINED BY THE DESIGN PROFESSIONAL |
| | IMPORTANCE FACTOR OF 1.15. |
| | |
| | F) FIREDOOR 8080 SERIES OUT SWING STEEL LOUVER |
| | COMMERCIAL DOOR LMI, REQUIRES FL COVER SHEET, CURRENTLY |
| | WITH A 1.0 IMPORTANCE FACTOR MEETS WIND LOADS, TO BE |
| | DETERMINED BY THE DESIGN PROFESSIONAL IMPORTANCE FACTOR |
| | OF 1.15. |
| | |
| | G) FIREDOOR 4080 SERIES OUT SWING COMMERCIAL STEEL |
| | DOOR LMI, HIGHLIGHT TYPE OF FASTENER TO BE USED, |
| | REQUIRES FL COVER SHEET, CURRENTLY WITH A 1.0 |
| | IMPORTANCE FACTOR MEETS WIND LOADS, TO BE DETERMINED BY |
| | THE DESIGN PROFESSIONAL IMPORTANCE FACTOR OF 1.15. |
| | |
| | H) BESAM AUTOMATIC ENTRANCE SYSTEM, POWER GLIDE MODEL |
| | AM-2 AUTOMATIC ALUMINUM SLIDING GLASS DOOR, SUBSECTION |
| | ?C? CALCULATIONS INDICATE THAT THE CALCULATIONS HAVE |
| | NOT BEEN REVISITED TO THE 2004 FBC 1605.3.1.1.WITH A |
| | 1.0 IMPORTANCE FACTOR THIS PRODUCT MAY MEET WIND LOADS |
| | WITH THE UNKNOWN FASTENING FACTOR STEEL INCREASE OF |
| | 1.33 FORWIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS |
| | ADJUSTED TO 1.15TO BE DETERMINED BY THE DESIGN |
| | PROFESSIONAL. |
| | |
| | I) OVERHEAD DOOR, 10? WIDE ROLLING STEEL DOOR, REQUIRES |
| | FLORIDA COVER SHEET, CURRENTLY DOESN?T MEET THE |
| | REQUIRED PRESSURES. , SUBSECTION ?C? CALCULATIONS |
| | INDICATE THAT THE CALCULATIONS HAVE NOT BEEN REVISITED |
| | TO THE 2004 FBC 1605.3.1.1.WITH A 1.0 IMPORTANCE |
| | FACTOR THIS PRODUCT MAY MEET WIND LOADS WITH THE |
| | UNKNOWN FASTENING FACTOR STEEL INCREASE OF 1.33 FOR |
| | WIND LOADS, ALSO IF THE IMPORTANCE FACTOR IS ADJUSTED |
| | TO 1.15TO BE DETERMINED BY THE DESIGN PROFESSIONAL. |
| | |
| | J) RUSKIN LOUVER SERIES ELF6375DXD , AS INDICATED WITH |
| | THE PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT |
| | , SUBSECTION ?C? CALCULATIONS INDICATE THAT THE |
| | CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC |
| | 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT |
| | MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR |
| | STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE |
| | IMPORTANCE FACTOR IS ADJUSTED TO 1.15 TO BE DETERMINED |
| | BY THE DESIGN PROFESSIONAL. |
| | |
| | K) RUSKIN LOUVER SERIES EME520MD, AS INDICATED WITH THE |
| | PRESSURES AS STATED ON THE PLAN MEETS PRESSURES BUT , |
| | SUBSECTION ?C? CALCULATIONS INDICATE THAT THE |
| | CALCULATIONS HAVE NOT BEEN REVISITED TO THE 2004 FBC |
| | 1605.3.1.1.WITH A 1.0 IMPORTANCE FACTOR THIS PRODUCT |
| | MAY MEET WIND LOADS WITH THE UNKNOWN FASTENING FACTOR |
| | STEEL INCREASE OF 1.33 FOR WIND LOADS, ALSO IF THE |
| | IMPORTANCE FACTOR IS ADJUSTED TO 1.15 TO BE DETERMINED |
| | BY THE DESIGN PROFESSIONAL. |
| | |
| | L) ROOFING ASSEMBLIES: SIPLAST/ ICOPAL, MODIFIED |
| | BITUMEN OVER LWC DECK. REQUIRES FLORIDA COVER SHEET, |
| | SUB-SYSTEM IS NOT HIGHLIGHTED PAGES 12-20, ALSO NOTE |
| | GENERAL LIMITATION NUMBER 7 AND 9. IF ENHANCED FASTING |
| | IS REQUIRED PLEASE PROVIDE THE CALCULATIONS FOR RAS |
| | 117. |
| | |
| | M) PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED! |
| | |
| | N) NOTE CLIP SYSTEM FOR CURTAIN WALL SYSTEM ISN?T |
| | CALLED OUT AND WOULD ALSO REQUIRE PRODUCT APPROVAL SEE |
| | DETAIL 15 SHEET S-10. PROVIDE ADDITIONAL INFORMATION. |
| | 106.1.2* |
| | 31) SHEET S-10 DETAIL # 7 DEALS WITH EXCAVATION NEXT TO |
| | WALL FOUNDATIONS. WHEN THE SLOPE OF AN EXCAVATION IN A |
| | BED OF SAND EXCEEDS THE ANGLE OF INTERNAL FRICTION OF |
| | THE MATERIAL, THE SAND WILL SLIDE DOWN THE SLOPE, |
| | THEREFORE THE STEEPEST SLOPE THAT SAND CAN ATTAIN IS |
| | EQUAL TO THE ANGLE OF INTERNAL FRICTION. |
| | 1803.1 EXCAVATIONS NEAR FOOTINGS OR FOUNDATIONS. |
| | EXCAVATIONS FOR ANY PURPOSE SHALL NOT REMOVE LATERAL |
| | SUPPORT FROM ANY FOOTING OR FOUNDATION WITHOUT FIRST |
| | UNDERPINNING OR PROTECTING THE FOOTING OR FOUNDATION |
| | AGAINST SETTLEMENT OR LATERAL TRANSLATION. |
| | TO THE ANGLE OF INTERNAL FRICTION. |
| | |
| | 32)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW II |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |