| Plan Review Notes For Permit 07050354 |
| Permit Number |
07050354 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-09-20 13:40:09 | | | | | | | ** DENIED ** | | | | | | 1) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS. | | | PLEASE CORRELATE ALL AS SUBMITTED. | | | FOR EXAMPLE: | | | PLEASE SEE THE LOAD CALCULATIONS ABOVE THE RISER | | | DIAGRAM ON THE UPPER LEFT HAND SIDE OF PLANS INDICATES | | | THE LOAD CALCULATIONS FOR THE EXISTING PANEL *A* WITH | | | THE NEW LOAD OF PANEL *C* BEING ADDED. HOW IS THIS | | | POSSIBLE WHEN THE RISER DIAGRAM AND PANEL SCHEDULES | | | INDICATE PANEL *C* BEING FED FROM PANEL *B*? | | | PLEASE SEE THE LOAD CALCULATIONS ON PANEL **B* WHICH IS | | | WHAT IS SHOWN FEEDING THE NEW SUB PANEL *C* IS STILL | | | NEEDED. | | | PLEASE SEE LOAD FOR PANEL *B* A/C LOAD IS ONLY SHOWN AS | | | 10KW. HOW IS THIS POSSIBLE IF THE EXISTING UNIT IS 10KW | | | AND THE NEW UNIT IS 5KW WHICH IS ON PANEL *C* WHICH IS | | | FED FROM *B*? | | | PLEASE SEE CODE SECTION AS PREVIOUSLY GIVEN. WHEN USING | | | OPTIONAL CALCULATION AS SHOWN AND ADDING A/C HEAT TO AN | | | EXISTING SERVICE/PANEL. | | | 1ST 8KW AT 100%, REMAINDER AT 40% AND THE A/C HEAT | | | (WHICHIS LARGER?) AT 100%. | | | | | | ** PLEASE ADJUST CALCULATIONS. | | | ** PLEASE KNOW THIS REVIEWER?S DIRECT PHONE NUMBER AND | | | E-MAIL ADDRESS HAS BEEN PLACED ON THE LAST THREE | | | REVIEWS AND IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|