Plan Review Notes
Plan Review Notes For Permit 07050354
Permit Number 07050354
Review Stop E
Sequence Number 4
Notes
Date Text
2007-09-20 13:40:09 
  
 ** DENIED **
  
 1) NOTE: PLEASE SEE 220.83B FOR LOAD CALCULATIONS.
 PLEASE CORRELATE ALL AS SUBMITTED.
 FOR EXAMPLE:
 PLEASE SEE THE LOAD CALCULATIONS ABOVE THE RISER
 DIAGRAM ON THE UPPER LEFT HAND SIDE OF PLANS INDICATES
 THE LOAD CALCULATIONS FOR THE EXISTING PANEL *A* WITH
 THE NEW LOAD OF PANEL *C* BEING ADDED. HOW IS THIS
 POSSIBLE WHEN THE RISER DIAGRAM AND PANEL SCHEDULES
 INDICATE PANEL *C* BEING FED FROM PANEL *B*?
 PLEASE SEE THE LOAD CALCULATIONS ON PANEL **B* WHICH IS
 WHAT IS SHOWN FEEDING THE NEW SUB PANEL *C* IS STILL
 NEEDED.
 PLEASE SEE LOAD FOR PANEL *B* A/C LOAD IS ONLY SHOWN AS
 10KW. HOW IS THIS POSSIBLE IF THE EXISTING UNIT IS 10KW
 AND THE NEW UNIT IS 5KW WHICH IS ON PANEL *C* WHICH IS
 FED FROM *B*?
 PLEASE SEE CODE SECTION AS PREVIOUSLY GIVEN. WHEN USING
 OPTIONAL CALCULATION AS SHOWN AND ADDING A/C HEAT TO AN
 EXISTING SERVICE/PANEL.
 1ST 8KW AT 100%, REMAINDER AT 40% AND THE A/C HEAT
 (WHICHIS LARGER?) AT 100%.
  
 ** PLEASE ADJUST CALCULATIONS.
 ** PLEASE KNOW THIS REVIEWER?S DIRECT PHONE NUMBER AND
 E-MAIL ADDRESS HAS BEEN PLACED ON THE LAST THREE
 REVIEWS AND IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]