| 2007-07-31 17:40:46 | *** PROVISO *** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL |
| | NEEDS TO BE ADDRESSED. |
| | |
| | 1) NOTE:PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR |
| | PANEL *A* INCLUDING NEW AND EXISTING LOADS BEFORE ANY |
| | ROUGH ELECTRICAL INSPECTION IS CALLED IN. REVISED PLANS |
| | WILL BE REQUIRED TO BE REVIEWED, STAMPED AND ON |
| | JOB-SITE. |
| | PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO NOT |
| | CORRELATE WITH THE EXISTING REFERENCED PLANS FOR LOADS |
| | NOR DO THEY MEET THE NEC 220.83B. |
| | PLEASE SEE THE LOAD AS SHOWN ON THIS 150A RATED PANEL |
| | IS BEING SHOWN AT 147/PLUS AMPS AND IS CLOSE TO |
| | EXCEEDING THE RATING OF THE PANEL AND MAIN. |
| | IF THE LOADS EXCEED THE RATING OF THE MAIN AND PANEL, |
| | IT WILL BE THE RESPONSIBILITY OF THE GENERAL |
| | CONTRACTOR, ELECTRICAL CONTRACTOR AND ARCHITECT OF |
| | RECORD TO UPGRADE SERVICE. THIS *PROVISO* IS GIVEN TO |
| | PROCEED TO ROUGH ELECTRICAL INSPECTION AT YOUR OWN RISK |
| | AS THE CALCULATIONS ARE NOT CODE COMPLIANT. |
| | |
| | ** THE ABOVE MUST BE SUBMITTED FOR CORRECTIONS BEFORE |
| | ANY ROUGH ELECTRICAL INSPECTION.A HOLD MAY BE PLACED |
| | ON ELECTRICAL FOR THE ROUGH INSPECTION. ELECTRICAL |
| | PERMIT MAY ALSO BE REVOKED OR PLACED ON HOLD IF NOT |
| | ADDRESSED. |
| | ** IF PLANS ARE RETURNED FOR ANY OTHER COMMENTS FROM |
| | OTHER TRADES BEFORE ISSUANCE, PLEASE ADDRESS AT THIS |
| | TIME. |
| | |
| | AS STATED ON THE PREVIOUS REVIEWS, IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |