Plan Review Notes
Plan Review Notes For Permit 07050354
Permit Number 07050354
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-31 17:40:46*** PROVISO ***
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH STILL
 NEEDS TO BE ADDRESSED.
  
 1) NOTE:PLEASE SUBMIT REVISED LOAD CALCULATIONS FOR
 PANEL *A* INCLUDING NEW AND EXISTING LOADS BEFORE ANY
 ROUGH ELECTRICAL INSPECTION IS CALLED IN. REVISED PLANS
 WILL BE REQUIRED TO BE REVIEWED, STAMPED AND ON
 JOB-SITE.
 PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE EXISTING REFERENCED PLANS FOR LOADS
 NOR DO THEY MEET THE NEC 220.83B.
 PLEASE SEE THE LOAD AS SHOWN ON THIS 150A RATED PANEL
 IS BEING SHOWN AT 147/PLUS AMPS AND IS CLOSE TO
 EXCEEDING THE RATING OF THE PANEL AND MAIN.
 IF THE LOADS EXCEED THE RATING OF THE MAIN AND PANEL,
 IT WILL BE THE RESPONSIBILITY OF THE GENERAL
 CONTRACTOR, ELECTRICAL CONTRACTOR AND ARCHITECT OF
 RECORD TO UPGRADE SERVICE. THIS *PROVISO* IS GIVEN TO
 PROCEED TO ROUGH ELECTRICAL INSPECTION AT YOUR OWN RISK
 AS THE CALCULATIONS ARE NOT CODE COMPLIANT.
  
 ** THE ABOVE MUST BE SUBMITTED FOR CORRECTIONS BEFORE
 ANY ROUGH ELECTRICAL INSPECTION.A HOLD MAY BE PLACED
 ON ELECTRICAL FOR THE ROUGH INSPECTION. ELECTRICAL
 PERMIT MAY ALSO BE REVOKED OR PLACED ON HOLD IF NOT
 ADDRESSED.
 ** IF PLANS ARE RETURNED FOR ANY OTHER COMMENTS FROM
 OTHER TRADES BEFORE ISSUANCE, PLEASE ADDRESS AT THIS
 TIME.
  
 AS STATED ON THE PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]